Fenwal SERIES 35-67 Manual Download Page 1

FEATURES

n

Combustion blower output

n

Proven pressure switch input

n

24/120/240 VAC hot surface ignitor models available

n

ASME CSD-1 compatible models available (consult factory)

n

Pre-purge and lockout indicator outputs

n

Non-volatile lockout option

n

Diagnostic LED and remote LED connection

n

Multiple trials for ignition

n

Thermostat, pushbutton or remote reset

n

Full-time flame sensing

n

Remote flame sensor option

n

Flame current test pins

APPLICATIONS

Commercial and industrial appliances with combustion 
chambers in excess of 400K BTU.  Applications requiring 
CSD-1 certification.

DESCRIPTION

The Series 35-67 is a hot surface ignition system in which  
the ignition source is proven to be capable of ignition prior to 
the gas valve being opened and is suitable for appliances over 
400K BTU.  Models compatible to the requirements of ASME 
standard CSD-1 are available.  

The microprocessor circuit design provides precise, repeatable 
timing sequences for ignition times and purge times (pre-, inter-,
and post-) as well as multiple tries for ignition.  The control also 
continuously monitors the pressure switch, thermostat and main
burner flame to ensure safe system operation.  On-board diagnostics
with LED output provide assistance with troubleshooting to ensure
safe and efficient burner operation.

Agency Certifications

Design certified by CSA International to CAN C22.2 #199-M89 and
ANSI Z21.20 for Automatic Ignition Systems, including UL1998
Software Review.

Special models approved to EN298:2003 available upon request.

SERIES 35-67

24 VAC Microprocessor Based Proven HSI Control 
with Combustion Blower Relay 

SPECIFICATIONS

www.fenwalcontrols.com

1-800-FENWAL-1

Series 35-67, 24 VAC Hot Surface Ignition Control 

Page 1

INPUT VOLTAGES

Control

18 to 30 VAC, 400mA max

(not including gas valve)

Line (L1 & L2 to Ignitor)

120 VAC standard, 24 VAC and 240 VAC 

models available

Thermostat

18 to 30 VAC 30mA max  (not incl. Gas Valve)

Pressure Switch (Airflow)

18 to 30 VAC 25mA max

OUTPUT RATINGS

Combustion Blower

15A max (0.6 pf) or 1/2 HP @ 120 or 240 VAC

Hot Surface Ignitor

5.0A max @ 24, 120 or 240 VAC

Gas Valve Rating

5.0A max (0.6 pf) @ 24 VAC

Lockout & Pre-Purge Indicators

1.0A max @ 24 VAC

OPERATING TEMPERATURE

-40ºF to +165ºF (-40ºC to +73ºC)

FLAME SENSITIVITY

1.0 micro Amp minimum

FLAME FAILURE 

0.8 seconds max

RESPONSE TIME

TYPES OF GAS

Natural, LP, or manufactured

ENCLOSURE

Gray (Noryl N-190)

MOISTURE RESISTANCE

Conformal coated to operate non-condensing 
to 95% R.H. Care must be taken to protect 
module from direct exposure to water

SIZE WITH ENCLOSURE

See Figures 6 & 7

WEIGHT

8oz including options and cover

35.67.03

®

Summary of Contents for SERIES 35-67

Page 1: ...h LED output provide assistance with troubleshooting to ensure safe and efficient burner operation Agency Certifications Design certified by CSA International to CAN C22 2 199 M89 and ANSI Z21 20 for Automatic Ignition Systems including UL1998 Software Review Special models approved to EN298 2003 available upon request SERIES 35 67 24 VAC Microprocessor Based Proven HSI Control with Combustion Blo...

Page 2: ...current through the ignition element When the current reaches a pre determined level the LED will flash once Dwell Time From the point when the current has been proven there will be a delay called dwell time Dwell time assures that the ignition element has sufficient time to reach ignition temperature 4 IGNITION When dwell time is completed the gas valve will open The ignition element will turn of...

Page 3: ...fications could result in failure of the Fenwal product and other equipment with injury or death to people and damage to property Service to this product should only be preformed by a qualified technician 5 Series 35 67 24 VAC Hot Surface Ignition Control Page 3 www fenwalcontrols com 1 800 FENWAL 1 PIN LOCATION 1 2 3 4 5 6 7 8 9 10 11 WIRE COLOR ORANGE RED VIOLET GRAY BROWN BLUE YELLOW GREEN WHIT...

Page 4: ...lect the proper harness based on the 35 67 control s termination connection Once the terminal configuration is determined complete the part number by replacing the last two digits XX with the length in inches l dimension Standard wire lengths are 12 18 24 30 36 and 48 inches Example 05 129845 018 18 inches For other lengths please contact Fenwal Part Number 22 100001 110 REMOTE FLAME SENSE ROD ...

Page 5: ...Series 35 67 24 VAC Hot Surface Ignition Control Page 5 www fenwalcontrols com 1 800 FENWAL 1 WIRING Figure 4A STANDARD DESIGN AUTOMATIC RESET PIN LAYOUT Figure 5A ...

Page 6: ...www fenwalcontrols com 1 800 FENWAL 1 Page 6 Series 35 67 24 VAC Hot Surface Ignition Control OPTIONAL DESIGN MANUAL RESET WIRING Figure 4B PIN LAYOUT Figure 5B ...

Page 7: ...Series 35 67 24 VAC Hot Surface Ignition Control Page 7 www fenwalcontrols com 1 800 FENWAL 1 DIMENSIONS Figure 6 Figure 7 ...

Page 8: ...ge 30 Interpurge 30 Postpurge Full Time Power 7 0 Prepurge 15 Interpurge 15 Postpurge Full Time Power 8 0 Prepurge 30 Interpurge 30 Postpurge Full Time Power Tries For Ignition 0 Single Try Local Sense Recycle On Flame Loss 1 Single Try Remote Sense Recycle On Flame Loss 2 Single Try Local Sense Lockout On Flame Loss 3 Single Try Remote Sense Lockout On Flame Loss 5 Three Tries Local Sense Recycle...

Reviews: