Fenwal FenwalNET 2000 Installation, Operation And Maintenance Manual Download Page 16

xii

Any fire alarm system may fail for a variety of reasons:
• Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in walls, or

roofs, or on the other side of closed doors.  Smoke detectors also may not sense a fire on another level or floor of

a building.  A second floor detector, for example, may not sense a first floor or basement fire.  Furthermore, all

types of smoke detectors - both ionization and photoelectric types, have sensing limitations.  No type of smoke

detector can sense every kind of fire caused by carelessness and safety hazards like smoking in bed, violent

explosions, escaping gas, improper storage of flammable materials, overloaded electrical circuits, children play-

ing with matches, or arson.

• Audible warning devices such as bells may not alert people if these devices are located on the other side of closed

or partly open doors or are located on another floor of a building.

• A fire alarm system will not operate without electrical power.  If AC power fails, the system will operate from

standby batteries only for a specified time.

• Rate-of-Rise heat detectors may be subject to reduced sensitivity over time.  For this reason, the rate-of-rise

feature of each detector should be tested at least once per year by a qualified fire protection specialist.

• Auxiliary Equipment used in the system may not be technically compatible with the control panel.  It is essential

to use only equipment listed for service with your control panel.

• Telephone lines needed to transmit alarm signals from a premise to a central monitoring station  may be out of

service or temporarily disabled.

The most common cause of fire alarm malfunctions, however, is inadequate maintenance.  All devices and system

wiring should be tested and maintained by professional fire alarm installers following written procedures supplied

with each device.  System inspection and testing should be scheduled monthly or as required by National and/or

local fire codes.  Adequate written records of all inspections should be kept.

GENERAL SAFETY NOTICES.  THE FOLLOWING MUST BE OBSERVED TO MAINTAIN PERSONNEL SAFETY.

The following general safety notices supplement specific warnings and cautions appearing in the manual.  The safety

precautions in this section must be understood and applied during operation and maintenance. This manula is to

be used by trained distributors/technicians. The entire manual should be read and fully understood prior to instal-

lation.

Test Equipment
Make certain test equipment is in good operating condition.  Do not touch live equipment or personnel working on

live equipment while holding a test meter.  Some types of measuring devices should not be grounded; these devices

should not be held when taking measurements.

First Aid
Any injury, no matter how slight, should never go unattended.  Always obtain first aid or medical attention immedi-

ately.

GENERAL PRECAUTIONS

The following general safety precautions are to be observed at all times:
1. All electrical components associated with equipment shall be installed and grounded in accordance with NEC,

NFPA and local regulation requirements.

2. Special precautionary measures are essential to prevent applying power to equipment at any time maintenance

work is in progress.

3. Before working on electrical equipment, use a voltmeter to ensure that system is not energized.
4. When working near electricity, do not use metal rules, flashlights, metallic pencils, or any other objects having

exposed conductive material.

5. When connecting a meter to terminals for measurement, use range higher than expected voltage.

Summary of Contents for FenwalNET 2000

Page 1: ...alNETTM 2000 Fire Alarm Suppression Control System Installation Operation and Maintenance Manual Date May 2001 P N 74 200016 001 UL Listing File No S2422 Factory Mutual Approval J I No 3005511 R LISTED TM R ...

Page 2: ......

Page 3: ...FenwalNETTM 2000 Fire Alarm Suppression Control System Installation Operation and Maintenance Manual ...

Page 4: ...THIS PAGE INTENTIONALLY LEFT BLANK ...

Page 5: ...ries Listing File Number S2422 FM Factory Mutual Engineering Corp Factory Mutual System Approval J I Number 3005511 CSFM California State Fire Marshal Listing Number 7165 1076 141 NYC New York City Listing Number MEA 454 91 E Vol VI FenwalNET 2000 Multi Loop System P N 74 200000 600 UL Underwriter s Laboratories Listing File Number S2422 FM Factory Mutual Engineering Corp Factory Mutual System App...

Page 6: ...ii THIS PAGE IS INTENTIONALLY LEFT BLANK ...

Page 7: ...Module 1 5 1 2 8 Standby Batteries 1 5 1 2 9 Intelligent Loop Devices 1 5 1 2 9 1 SmartOne Ionization Detectors 1 5 1 2 9 2 SmartOne Photoelectric Detectors 1 5 1 2 9 3 SmartOne Heat Detectors 1 5 1 2 10 SmartOne Detector Bases 1 5 1 2 11 Addressable Contact Input Devices 1 6 1 2 12 Addressable Relay Output Devices 1 6 1 2 13 Model DH 2000 Air Duct Housing 1 6 1 2 14 Loop Isolator Devices 1 7 1 2 ...

Page 8: ...aLASER Interface Module Inputs HSD DCC 2 14 2 8 3 4 RX TX Loops 2 14 2 8 3 5 System Outputs 2 14 2 8 3 6 System I O Modules 2 14 2 8 4 Addressing I O Modules 2 14 2 8 5 Registering I O Module Assignments 2 15 2 8 5 1 Listing I O Module Assignment 2 15 2 8 6 Addressing RCUs 2 15 2 8 7 Registering RCUs 2 15 2 8 7 1 Detector Registration 2 16 2 8 7 2 Addressable Contact Monitor Registration 2 16 2 8 ...

Page 9: ...imulation Test AST 4 3 4 3 5 1 AST Procedure 4 3 4 4 Disarming and Rearming Release Circuits 4 3 4 4 1 Disarming Release Circuits 4 4 4 4 2 Arming Release Circuits 4 4 4 5 Power Down System 4 4 4 5 1 Power Down Procedure 4 4 4 6 Power Up System 4 4 4 6 1 Power Up Procedure 4 4 5 Troubleshooting and Corrective Maintenance 5 1 5 1 Introduction 5 1 5 2 Standard Fault Isolation Techniques 5 1 5 2 1 Vi...

Page 10: ...nclosure 7 7 7 9 2 Batteries 7 7 7 10 Field Device Connection to RX TX Module 7 7 7 10 1 Wiring the RX TX PC Line 7 7 7 11 Output Signal Connection 7 9 7 12 External Power Failure Indicator Connection 7 9 7 13 Detector Installation 7 10 7 14 Setting and Adjusting Smoke and Heat Detector Sensitivities 7 10 7 14 1 Setting And Adjusting Smoke and Heat Detector Sensitivity Procedure 7 10 7 15 Addressa...

Page 11: ...ossary F 1 G Display Abbreviations G 1 H Index H 1 I System Drawings I 1 J FenwalNET Network Interface Card J 1 K Addressable Signal Sounder Module K 1 L Remote Display Control Module and Remote Display Module L 1 M Addressable AlarmLine Module M 1 N Networkable Central Control Module N 1 O Central Station Operation O 1 APPENDICES APPENDIX TITLE PAGE ...

Page 12: ...etector 1 7 1 25 AnaLASER Interface Module for the AnaLASER II Detector 1 7 2 1 System Front Panel 2 1 2 2 Level One Menu Structure 2 7 2 3 Level Two Menu Structure 2 8 3 1 Overall Block Diagram Single Loop System 3 1 3 2 Overall Block Diagram Multi Loop System 3 1 3 3 Central Control Module Details 3 2 3 4 Receiver Transmitter Module Details 3 4 3 5 Obsolete Power Supply Charger Assembly Revision...

Page 13: ... A Wiring Diagram 7 5 7 7 Power Supply Charger Rev C Wiring Diagram 7 5 7 8 Power Supply Charger Rev A Wiring Diagram for Expansion Enclosure 7 5 7 9 Power Supply Charger Rev C Wiring Diagram for Expansion Enclosure 7 5 7 10 Battery Enclosure 7 7 7 11 Conduit to CCP 7 8 7 12 Shielded Wire to CCP 7 8 7 13 Style 4 RX TX PC Line Connections 7 8 7 14 Style 6 RX TX PC Line Connections 7 8 7 15 Style 6 ...

Page 14: ... 3 1 Multi Loop I O Motherboard Connectors 3 6 3 2 Approved Release Output Devices 3 7 5 1 Troubleshooting Index 5 1 5 2 RX TX Configuration Selection 5 3 6 1 FenwalNET 2000 System Parts List 6 1 7 1 RX TX Configuration Selection 7 3 7 2 Aux Power Supply Module Connections to Rev A Main Power Supply Charger Assembly 7 6 7 3 Aux Power Supply Module Connections to Rev C Main Power Supply Charger Ass...

Page 15: ...y or can be damaged when subjected to lightning induced transients Although no system is completely immune from lightning transients and interference proper grounding will reduce susceptibility The use of overhead or outside aerial wiring is not recommended due to the increased susceptibility to nearby lightning strikes Consult with the Applications Engineering Department if any problems are antic...

Page 16: ...uate maintenance All devices and system wiring should be tested and maintained by professional fire alarm installers following written procedures supplied with each device System inspection and testing should be scheduled monthly or as required by National and or local fire codes Adequate written records of all inspections should be kept GENERAL SAFETY NOTICES THE FOLLOWING MUST BE OBSERVED TO MAI...

Page 17: ...xiii THIS PAGE IS INTENTIONALLY LEFT BLANK ...

Page 18: ...FenwalNET 2000 74 200016 001 1 D May 2001 Figure 1 1 FenwalNET 2000 System Overall Diagram ...

Page 19: ... have operating firmware in the Central Control Module CCM that ranges from Ver sion 48 0 to Version 61 1 Networkable systems have a modified CCM that can accept a Network Interface Card NIC for peer to peer control unit operations and can accommodate Remote Display Modules and Remote Display Control Modules Networkable systems have CCM firmware that ranges from Version 70 0 to Version 71 0 Networ...

Page 20: ...er supervision 24 Vdc supervision Battery load test 24 Vdc ground fault detection Auxiliary 24 Vdc outputs Loop Isolator for Style 7 Figure 1 4 Receiver Transmitter Module RX TX 1 2 COMPONENT DESCRIPTION The following paragraphs give a brief description of each components used in the FenwalNET 2000 system For functional descriptions of each component see Chapter 3 of this manual 1 2 1 Central Cont...

Reviews: