background image

xi

SAFETY SUMMARY

Installation Precautions  Adherence to the following will aid in problem-free installation with long-term reliability:

WARNING

!

Several different sources of power can be connected to this fire alarm control panel.  Disconnect all

sources of power before servicing.  Control unit and associated equipment may be  damaged by removing

and/or inserting cards, modules, or interconnecting cables while the unit is energized.  Do not attempt

to install, service, or operate this unit until this manual is read and understood.

CAUTION

!

System Re-acceptance Test after Software Changes:  To  ensure proper system operation, this product

must be tested in accordance with NFPA - 1999 Chapter 7 after any programming operation or change

in site-specific software.  Re-acceptance testing is required after any change, addition or deletion of

system components, or after any modification, repair or adjustment to system hardware or wiring.

All components, circuits, system operations, or software functions known to be affected by a change must be 100%

tested.  In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices

that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system

operation verified.
This system meets NFPA requirements for operation at 0 to 49° C and at a relative humidity of 85% RH (non-

condensing) @ 30°C.  However, the useful life of the system’s standby batteries and the electronic components may

be adversely affected by extreme temperature ranges and humidity.  Therefore, it is recommended that this system

and its peripherals be installed in an environment with a nominal room temperature of 60-80°F.
Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to

lightning induced transients.  Although no system is completely immune from lightning transients and interference,

proper grounding will reduce susceptibility.  

The use of overhead or outside aerial wiring is not recommended

due to the increased susceptibility to  nearby lightning strikes.  

Consult with the Applications Engineering

Department  if any problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or inserting circuit boards.  Failure to do so can damage

circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure.  When possible,

make all cable entries from the sides.  Before making modifications, verify that they will not interfere with battery

and printed circuit board location.
Do not over tighten screw terminals, over tightening may damage threads, resulting in reduced terminal contact

pressure and difficult with screw terminal removal.
This system contains static-sensitive components.  Always ground yourself with a proper wrist strap before han-

dling any circuits so that static charges are removed from the body.  Use static suppressive packaging to protect

electronic assemblies removed from the unit.
Follow the Instructions in the installation, operating, and programming manuals.  These instructions must be

followed to avoid damage to the control panel and associated equipment.  FN-2000  operation and reliability depend

upon proper installation.
Fire Alarm System Limitations: 

While installing a fire alarm system may make lower insurance rates pos-

sible, it is not a substitute for fire insurance

!

An automatic fire alarm system - typically made up of smoke detectors, heat detectors, manual pull stations, audible

warning devices, and a fire alarm control with remote notification-capability can provide early warning of a develop-

ing fire.  Such a system, however, does not assure protection against property damage or loss of life resulting from a

fire.

Summary of Contents for FenwalNET 2000

Page 1: ...alNETTM 2000 Fire Alarm Suppression Control System Installation Operation and Maintenance Manual Date May 2001 P N 74 200016 001 UL Listing File No S2422 Factory Mutual Approval J I No 3005511 R LISTED TM R ...

Page 2: ......

Page 3: ...FenwalNETTM 2000 Fire Alarm Suppression Control System Installation Operation and Maintenance Manual ...

Page 4: ...THIS PAGE INTENTIONALLY LEFT BLANK ...

Page 5: ...ries Listing File Number S2422 FM Factory Mutual Engineering Corp Factory Mutual System Approval J I Number 3005511 CSFM California State Fire Marshal Listing Number 7165 1076 141 NYC New York City Listing Number MEA 454 91 E Vol VI FenwalNET 2000 Multi Loop System P N 74 200000 600 UL Underwriter s Laboratories Listing File Number S2422 FM Factory Mutual Engineering Corp Factory Mutual System App...

Page 6: ...ii THIS PAGE IS INTENTIONALLY LEFT BLANK ...

Page 7: ...Module 1 5 1 2 8 Standby Batteries 1 5 1 2 9 Intelligent Loop Devices 1 5 1 2 9 1 SmartOne Ionization Detectors 1 5 1 2 9 2 SmartOne Photoelectric Detectors 1 5 1 2 9 3 SmartOne Heat Detectors 1 5 1 2 10 SmartOne Detector Bases 1 5 1 2 11 Addressable Contact Input Devices 1 6 1 2 12 Addressable Relay Output Devices 1 6 1 2 13 Model DH 2000 Air Duct Housing 1 6 1 2 14 Loop Isolator Devices 1 7 1 2 ...

Page 8: ...aLASER Interface Module Inputs HSD DCC 2 14 2 8 3 4 RX TX Loops 2 14 2 8 3 5 System Outputs 2 14 2 8 3 6 System I O Modules 2 14 2 8 4 Addressing I O Modules 2 14 2 8 5 Registering I O Module Assignments 2 15 2 8 5 1 Listing I O Module Assignment 2 15 2 8 6 Addressing RCUs 2 15 2 8 7 Registering RCUs 2 15 2 8 7 1 Detector Registration 2 16 2 8 7 2 Addressable Contact Monitor Registration 2 16 2 8 ...

Page 9: ...imulation Test AST 4 3 4 3 5 1 AST Procedure 4 3 4 4 Disarming and Rearming Release Circuits 4 3 4 4 1 Disarming Release Circuits 4 4 4 4 2 Arming Release Circuits 4 4 4 5 Power Down System 4 4 4 5 1 Power Down Procedure 4 4 4 6 Power Up System 4 4 4 6 1 Power Up Procedure 4 4 5 Troubleshooting and Corrective Maintenance 5 1 5 1 Introduction 5 1 5 2 Standard Fault Isolation Techniques 5 1 5 2 1 Vi...

Page 10: ...nclosure 7 7 7 9 2 Batteries 7 7 7 10 Field Device Connection to RX TX Module 7 7 7 10 1 Wiring the RX TX PC Line 7 7 7 11 Output Signal Connection 7 9 7 12 External Power Failure Indicator Connection 7 9 7 13 Detector Installation 7 10 7 14 Setting and Adjusting Smoke and Heat Detector Sensitivities 7 10 7 14 1 Setting And Adjusting Smoke and Heat Detector Sensitivity Procedure 7 10 7 15 Addressa...

Page 11: ...ossary F 1 G Display Abbreviations G 1 H Index H 1 I System Drawings I 1 J FenwalNET Network Interface Card J 1 K Addressable Signal Sounder Module K 1 L Remote Display Control Module and Remote Display Module L 1 M Addressable AlarmLine Module M 1 N Networkable Central Control Module N 1 O Central Station Operation O 1 APPENDICES APPENDIX TITLE PAGE ...

Page 12: ...etector 1 7 1 25 AnaLASER Interface Module for the AnaLASER II Detector 1 7 2 1 System Front Panel 2 1 2 2 Level One Menu Structure 2 7 2 3 Level Two Menu Structure 2 8 3 1 Overall Block Diagram Single Loop System 3 1 3 2 Overall Block Diagram Multi Loop System 3 1 3 3 Central Control Module Details 3 2 3 4 Receiver Transmitter Module Details 3 4 3 5 Obsolete Power Supply Charger Assembly Revision...

Page 13: ... A Wiring Diagram 7 5 7 7 Power Supply Charger Rev C Wiring Diagram 7 5 7 8 Power Supply Charger Rev A Wiring Diagram for Expansion Enclosure 7 5 7 9 Power Supply Charger Rev C Wiring Diagram for Expansion Enclosure 7 5 7 10 Battery Enclosure 7 7 7 11 Conduit to CCP 7 8 7 12 Shielded Wire to CCP 7 8 7 13 Style 4 RX TX PC Line Connections 7 8 7 14 Style 6 RX TX PC Line Connections 7 8 7 15 Style 6 ...

Page 14: ... 3 1 Multi Loop I O Motherboard Connectors 3 6 3 2 Approved Release Output Devices 3 7 5 1 Troubleshooting Index 5 1 5 2 RX TX Configuration Selection 5 3 6 1 FenwalNET 2000 System Parts List 6 1 7 1 RX TX Configuration Selection 7 3 7 2 Aux Power Supply Module Connections to Rev A Main Power Supply Charger Assembly 7 6 7 3 Aux Power Supply Module Connections to Rev C Main Power Supply Charger Ass...

Page 15: ...y or can be damaged when subjected to lightning induced transients Although no system is completely immune from lightning transients and interference proper grounding will reduce susceptibility The use of overhead or outside aerial wiring is not recommended due to the increased susceptibility to nearby lightning strikes Consult with the Applications Engineering Department if any problems are antic...

Page 16: ...uate maintenance All devices and system wiring should be tested and maintained by professional fire alarm installers following written procedures supplied with each device System inspection and testing should be scheduled monthly or as required by National and or local fire codes Adequate written records of all inspections should be kept GENERAL SAFETY NOTICES THE FOLLOWING MUST BE OBSERVED TO MAI...

Page 17: ...xiii THIS PAGE IS INTENTIONALLY LEFT BLANK ...

Page 18: ...FenwalNET 2000 74 200016 001 1 D May 2001 Figure 1 1 FenwalNET 2000 System Overall Diagram ...

Page 19: ... have operating firmware in the Central Control Module CCM that ranges from Ver sion 48 0 to Version 61 1 Networkable systems have a modified CCM that can accept a Network Interface Card NIC for peer to peer control unit operations and can accommodate Remote Display Modules and Remote Display Control Modules Networkable systems have CCM firmware that ranges from Version 70 0 to Version 71 0 Networ...

Page 20: ...er supervision 24 Vdc supervision Battery load test 24 Vdc ground fault detection Auxiliary 24 Vdc outputs Loop Isolator for Style 7 Figure 1 4 Receiver Transmitter Module RX TX 1 2 COMPONENT DESCRIPTION The following paragraphs give a brief description of each components used in the FenwalNET 2000 system For functional descriptions of each component see Chapter 3 of this manual 1 2 1 Central Cont...

Reviews: