4.

 Specification

 

(1) 

Name 

  Photoelectric Smoke Detector 

(2) 

Type 

  F1H-RYW1 - xx xx x 

 

 

 

 

 

 

Sensitivity 

Type of Output 

Length of cable 

 
Standard setting    F1H-RYW1-05BB2 
Sensitivity 5%/m, Alarm Output B, Trouble Output B, Cable length 2m. 

 

 

 

 

 

 

 

Sensitivity

3%/m

10%/m(Value = 03

10) 

Standard Setting is 5%/m.(Value=05) 

 

 

 

Type of Output

Type of Alarm & Trouble Output 

             

Standard Setting is Alarm=B

Trouble=B. 

             

(Value = BB) 

 

 

 

Length of cable

Cable Length    0

None

2

2m

5

5m

 

Standard Setting is 2m. (Value = 2) 

 

4.1.

 Electrical Specification

 

(1) 

Rated Current

 

  DC

 

30mA 

 

(2) 

Range 

of 

Operating Voltage

 

  DC10.0V

DC30.0V 

Acceptable ripple voltage 300mVp-p 
Power supply with connector cable.

See bellow(6)

 

 

(3) 

Sensitivity 

  Depend on Type of Product. 5

/

m(

Nominal

 

 

(4) 

State 

Indication 

LED

 

  RED LED 

 

State of LED 

Normal mode 

10 seconds interval 

Alarm mode 

1 seconds interval 

Trouble mode 

Off (not blinking) 

Alarm will override trouble. 
 

(5) 

Output 

  Alarm, Trouble Relay Output 

Capacity of Relay DC24V,0.5A Resistance loading

 

State depends on Type of relay. 

Type 

Contact 

Normal 

mode 

Alarm 

mode 

Trouble 

mode 

Power 

OFF 

AA 

Alarm 

Open 

Close 

Open 

Open 

Trouble 

Open 

Open 

Close 

Open 

AB 

Alarm 

Open 

Close 

Open 

Open 

Trouble 

Close 

Close 

Open 

Open 

BA 

Alarm 

Close 

Open 

Close 

Open 

Trouble 

Open 

Open 

Close 

Open 

BB 

(

Standard

Alarm 

Close 

Open 

Close 

Open 

Trouble 

Close 

Close 

Open 

Open 

State of output will be normal about a second after power supply. 

Output relay is PhotoMOS relay. 

On resistance Max.0.7

Ω

.Off state leakage current 1

μ

A. 

Insulation  Test  under  DC24V  between  Relay  and  Relay,  Relay  and 

Power supply. 
 
 
 
 

Summary of Contents for F1H-RYW1

Page 1: ...al we have shown the important notice in order for you to use the device just and the method of handling this system In additional to you read this manual well before the utilization understanding well and use After you read in the place where it seen with it is seen with anytime please to be sure to keep ...

Page 2: ...730110 K0 2 ES1255 Page Table of contents 1 Safety Instructions 3 2 Name and Function of each section 4 3 Install 5 4 Specification 8 5 Maintenance and Inspection 10 6 Disposal 13 7 Support 13 ...

Page 3: ...nd moving and falling etc at your corporation breakdown and the loss with inadequate handling 3 When cause of breakdown due to the reason other than the payment item 4 Error in regard to use of the consumer breakdown and the loss with repairing remodeling other than our company and error connecting Furthermore the guarantee referred to here being something which means the guarantee of the payment ...

Page 4: ...on Detector Mounting Base State Indication LED Normal supervision 10 seconds interval Alarm mode 1 seconds interval Trouble mode Off not blinking Power Supply Signal output connector Guide of installation Insert Terminal 3 4 Smoke Air flow Insert Terminal 1 2 ...

Page 5: ...it exceeds environmental specification It causes trouble Do not install wrong location The smoke detector cannot detect a smoke Be sure to install the detector away from sources of electrical noise such as high voltage and high current switches Isolation from electric noise source such as power line The signal conductor which is connected to the detector please wires over 20cm separating from the ...

Page 6: ...e a malfunction failure or drop Tighten the screw in the specified torque range torque 0 5N m Reference value Under tightening can cause a drop short circuit or malfunction Over tightening can cause a drop short circuit or malfunction due to damage to the screw or he equipments and malfunction and fire Put Insert guides Detector Terminal and Attachment together correctly It causes trouble Do not t...

Page 7: ... between Relay and Relay Relay and Power supply Do not place obstacle as wiring etc near the slit of the detector It will disturb inflow of smoke Please provide a dedicated power supply as much as possible This Detector does not have over voltage protection device Before using Please add an external over current circuit breaker Smoke detectors are detecting light scattered by smoke particles in th...

Page 8: ...nsitivity Depend on Type of Product 5 m Nominal 4 State Indication LED RED LED State of LED Normal mode 10 seconds interval Alarm mode 1 seconds interval Trouble mode Off not blinking Alarm will override trouble 5 Output Alarm Trouble Relay Output Capacity of Relay DC24V 0 5A Resistance loading State depends on Type of relay Type Contact Normal mode Alarm mode Trouble mode Power OFF AA Alarm Open ...

Page 9: ...mental and annual deterioration The detector becomes trouble condition before exceeding correctable limit 4 2 Mechanical Specification 1 External Φ28 H57mm Installation Base 10mm is contained 2 Mass Approx 25g Installation Base is contained 3 Main Material ABS resins 4 3 Environmental Specification 1 Operating Temperature Range 10 60 2 Storage Temperature Range 20 75 3 Operating Humidity Range 30 ...

Page 10: ...Move the wire to check Connectors must not be loose Change the connector cable 4 Behavior Normal supervision Detector State Indication LED Check Visually Blink 10 seconds interval Check the State Indication LED behavior Please do not touch the terminal while the unit is energized It may get an electric shock Please do the cleaning and the increase tightening of the screw after the power supply off...

Page 11: ...0mVp p Meets the specification 6 Installation Common Securely locked Move the detector to check The detector must be installed securely Retighten the screws on the base with proper torque Obstacle near the inlet of detector Check Visually Obstacle must not be present Removed 7 Appearance Common Adhesion of dirt and foreign matter Check Visually Dirt and foreign matter must not be present Removed a...

Page 12: ...unction Please use the dry cloth or wring the water out tightly cloth for the cleaning After Cleaning Do not leave a foreign substance such as sawdust or wiring debris on a detector Such debris could cause erroneous operation Do not clean with a solvent such as a ph balanced detergent Bleach Benzene Thinner Alcohol It causes the detector surface is damaged Caution ...

Page 13: ...al methods are specific criteria depending on each municipality 7 Support Please inquire about this product to Fenwal Controls of Japan Co Ltd Tokyo headquarters Fenwal Controls of Japan Co Ltd 1 5 10 Iidabashi Chiyoda Tokyo 102 0072 Japan Tokyo headquarters 81 3 3237 3565 警告 注意 警告 警告 警告 警告 注意 警告 ...

Reviews: