Fenwal 35-70 Series Manual Download Page 3

Effective: November 2015

F-35-70

3

MOUNTING AND WIRING

The Series 35-70 control is not position sensitive and can be 
mounted vertically or horizontally. The control may be mounted 
on any surface and fastened with #6 sheet metal screws. Secure 
the control in an area that will experience a minimum of 
vibration and remain below the maximum ambient temperature 
of 80°C (175°F).

All connections should be made with UL Approved, 105°C rated, 
18 gauge, stranded, .054” thick insulated wire. Refer to the 
appropriate wiring diagram when connecting the 35-70 to other 
components in the system.

Wiring Diagrams - 35-70

Figure 1. Local Sense

Figure 2. Remote Sense

Figure 3. Multi-Pin Layout

CAUTION

All wiring must be performed in accordance with
both local and national electrical codes.

CAUTION

Label all wires prior to disconnection when
servicing controls. Wiring errors may cause
improper and dangerous operation. A functional
checkout of a replacement control should always
be performed.

WARNING

This product uses voltages of shock hazard
potential. Wiring and initial operation must be
performed by a qualified service technician.

WARNING

Operation outside specifications could result in
failure of the Fenwal product and other
equipment with potential for injury to people and
property.

Terminal Designations

Terminal

Description

Multi-Pin 
Connector

P/N: TE 1-644615-1

Quick 
Connect 
(inch)

NC

Alarm

11

1/4”

V1

Valve Power

10

3/16” 

L2

120 VAC (Neutral)

8

3/16”

V2

Valve Neutral

7

3/16”

L1

120 VAC Input (Hot) 6

1/4”

B. GND

Burner Ground

2

3/16”

S1

Remote Flame 
Sensor

1

1/4”

FC+, FC-

Flame Sense 
Test Points

2 Pin Header

(TE P/N: 640383-2, 

Molex P/N: 26-60-2020)