Fenwal 35-70 Series Manual Download Page 2

Effective: November 2015

2

F-35-70

SEQUENCE OF OPERATION / FLAME 

RECOVERY / SAFETY LOCKOUT

Start Up - Heat Mode

When a call for heat is received from the thermostat supplying 
120VAC to L1, the control will reset, perform a self-check 
routine, flash the diagnostic LED and begin a pre-purge delay. 
Following the pre-purge period, the gas valve is energized and 
sparking commences for the Trial For Ignition (TFI) period.

When flame is detected during the TFI, the sparking process is 
terminated and the gas valve remains energized. The thermostat 
and burner flame are constantly monitored to assure proper 
system operation. When the thermostat is satisfied and the 
demand for heat ends, the gas valve is immediately de-
energized.

Failure to Light - Lockout

SINGLE TRIAL MODEL
Should the burner fail to light, or a flame is not detected during 
the TFI period, the gas valve will de-energize and the control will 
go into lockout. The LED will indicate the fault code for ignition 
lockout.

MULTI TRIAL MODEL
Should the burner fail to light or the flame is not detected during 
the TFI period, the gas valve will de-energize. The control will 
then go through an inter-purge delay before an additional 
ignition attempt. The control attempts two additional ignition 
trials before de-energizing the gas valve and entering lockout. 
The LED will indicate the fault code for ignition lockout.

FLAME FAILURE - RE-IGNITION MODE
If the established flame signal is lost while the burner is 
operating, the control will respond within 0.8 seconds by 
immediately energizing the H.V. spark for the TFI period in an 
attempt to relight the flame. If the burner does not light within 
the TFI, the gas valve will immediately de-energize and single try 
models will enter lockout. On multi-try models, a new TFI 
sequence will begin after an inter-purge delay. Multi-try models 
perform two additional attempts to light the burner before de-
energizing the gas valve and entering lockout. If the burner 
relights, normal operation resumes.

FLAME FAILURE-RECYCLE MODE

With the “Recycle After Loss of Flame" option, upon loss of 
flame, the gas valve is de-energized and the control proceeds to 
inter-purge before attempting to relight the flame. Multi-try 
models permit three tries for ignition including inter-purges. If 
the burner relights, normal operation resumes. If the burner 
does not relight, the control will enter lockout.

Lockout Recovery

Recovery from lockout requires a manual reset by either 
resetting the thermostat, or removing 120 VAC for a period of 5 
seconds. On models with automatic reset, if the thermostat is 
still calling for heat after one hour, then the control will 
automatically reset and attempt to ignite the burner.