Fenwal Controls 35-9 Series Operation And Installation Instructions Manual Download Page 5

Effective: October 2018

F-35-2000

5 of 12

3. The control attempts two additional ignition trials 

before going into lockout and the gas valve relay(s) are 
de-energized immediately. 

4. The LED indicates the fault code for ignition lockout.

Lockout Reset

Volatile Reset Models

Recovery from lockout requires either pressing manual reset, 
recycling the call for heat, or removing 24 volts for a period of 5 
seconds. On models with automatic reset, if the call for heat is 
still present after the configured reset time, the control will 
automatically reset and attempt to start a new heating cycle. 

Manual Reset Models

Recovery from lockout requires activation of the manual reset 
switch or remote reset input.

High Limit Fault Reset

If the High Limit sensor detects a temperature above the High 
Limit setpoint, the PIM will enter lockout. Recovery from a High 
Limit fault requires activation of the manual reset switch or 
remote reset input.

FLAME FAILURE RESPONSE

Recycle Mode 

With "recycle after loss of flame", upon loss of flame, the gas 
valve is de-energized within 0.8 seconds. After the flame recycle 
delay, the control attempts to relight the burner. Multi-try 
models allow three tries for ignition including inter-purges. If the 
pilot burner relights, normal operation resumes. If the burner 
does not relight, the control will go into lockout as described in 
“Failure to Light - Lockout”.

Re-ignition Mode (Spark Models Only)

If the established flame signal is lost while the burner is 
operating, the control responds within 0.8 seconds by energizing 
the HV spark for the TFI period in an attempt to relight the 
burner. If the flame is re-established, normal operation resumes. 
If the burner does not light within the TFI, the gas valve is de-
energized immediately and on multi-try models a new TFI 
sequence begins. Multi-try models will make 2 more attempts to 
light the burner.

If the burner does not relight, the control will lockout as 
previously described in “Failure to Light - Lockout”.

OEM FACTORY WIRING

Supplying Power

The PIM requires 24 VAC on Connector J11 to operate its 
microprocessor circuits, the safety switch connections, and the 
field demand inputs. An onboard fuse protects the 24 VAC 
circuits and if configured for direct gas valve power, the 24 VAC 
relay outputs to the gas valves.

Sensor Inputs

The PIM requires an outlet thermistor sensor for burner control 
and a high-limit thermistor sensor for the integrated UL353 high-
limit function. These two thermistors must be independent but 
co-located so they provide similar readings. The vent sensor and 
inlet sensor are optional and if used should be enabled by the 
parameter table settings.

Isolated Valve Contacts

If the optional isolated valve configuration is used, the valve 
power and return must be separately supplied to J12 and the 
valve outputs are not protected.

Combustion Blower Connections

The blower motor is connected to J13 operating off the power 
supplied to L1, which can be 120VAC or 240VAC. If a modulating 
blower is used, PWM or 4-20 mA signals are provided by 
connection to J10. The blower motor tachometer signal is 
required when configured for closed-loop fan speed control.

High-Current Blower Option

If provided, the relay contacts of K5 must be used to connect the 
blower. The QC dry-contact terminals on top of the relay are 
used for the blower output and supply voltage, which may be 
120VAC or 240VAC. The maximum current rating is 15.0A.

Pump Outputs

The pump circuits are operated off the power supplied to L1 and 
L1-S, which can be 120VAC or 240VAC. The boiler pump and 
DHW pump are sourced from L1, while the supply pump (if 
used) must be powered by L1-S.

Ignition Outputs

The PIM is capable of DSI, IP, or HSI ignition depending on 
configuration. For spark ignition (DSI or IP) the electrode is 
connected to the T3 ignition coil. For HSI the igniter element 
connects to P1 and is driven off the L1 supply voltage.

If configured, an external spark ignition transformer can be used 
by connecting it to P1. It is powered by L1 and the spark output 
on T3 will be disabled.

SYSTEM CONNECTIONS (FIELD WIRING)

If used, the Host Controller must be connected to J4. The RJ-45 
style 8-pin jack provides power, communications, and sensor 
information to the Host Controller.

The PIM also acts as the central wiring point of a hydronic 
system. Field wiring terminals on J1 and J2 allow connection of 
optional DHW, outdoor, and system sensors, Host Controller, 
EMS analog demand signal, LWCO, remote reset, water flow 
switch, and the space thermostat and DHW demand inputs.

Summary of Contents for 35-9 Series

Page 1: ...ssion testing to be verified after incorporation into end use appliance CSA Design certified to ANSI Z21 20 CAN CSA C22 2 No 199 M99 and ANSI Z21 20 2014 CAN CSA C22 2 No 60730 2 5 14 CE Approved to EN 298 20122 WARNING Installing or operating the product inconsistent with these instructions or specifications could cause serious property damage injury or death Specification Value Input Power Contr...

Page 2: ...sensor types as outlined in the specific appliance manuals Optional 12k Ohm thermistor are available consult factory for details The Inlet Outlet Hi Limit and Vent exhaust stack sensors are directly processed by the PIM The optional System Outdoor and DHW tank sensors are also connected to the PIM but passed through to the tekmar Host Controller which is required to provide those additional featur...

Page 3: ...by the presence of any one or more of the four sources below A heat demand contact closure on the TH field wiring terminals A voltage greater than 0 5Vdc on the analog 0 10Vdc EMS signal input A heat demand present on the DHW field wiring terminals A heat demand from the Host Controller based on the DHW sensor temperature 4 The PIM initializes the Trial for Ignition TFI counter to the programmed n...

Page 4: ...ed number of trials 2 The High Limit sensor is confirmed to read below the High Limit Set Point 3 The blower light off RPM speed is verified modulating type only 4 The gas valve relay contacts are verified open except isolated valve models 5 The Combustion Blower is set to the Ignition light off speed if modulating 6 The Pilot gas valve output is enabled for the trial for ignition time 7 The HV sp...

Page 5: ...d fuse protects the 24 VAC circuits and if configured for direct gas valve power the 24 VAC relay outputs to the gas valves Sensor Inputs The PIM requires an outlet thermistor sensor for burner control and a high limit thermistor sensor for the integrated UL353 high limit function These two thermistors must be independent but co located so they provide similar readings The vent sensor and inlet se...

Page 6: ...eck the cable between the Host Controller and J1 Safety 2 Fault 15 flashes Check gas pressure Verify proper safety switch operation MOUNTING AND WIRING The PIM enclosure is designed to facilitate mounting within a control box by the appliance OEM The PIM is not position sensitive and can be mounted vertically or horizontally The case may be mounted on any surface using four standard 8 sheet metal ...

Page 7: ...te Reset Flow Swit ch DHW TH Thermos t at Host Controller FT Bus B FT Bus A PIM Slave V Boiler Identity Card V in GN D High Limit Sensor Outlet Sensor Air Flow Safety 2 Safety 1 Inlet Sensor Vent Sensor 4 to 20 MA Fan Power 18 VDC Fan GND Flow SEN GND Flow SEN PW 12 VDC PWM Out Flow Sens or Tac homet er To J10 P in 3 To J10 P in 4 24 VAC L1 L2 2 STG MV MV PV RTN Hot Dry Contact Blower System Pump ...

Page 8: ...set Flow Swit ch DHW TH Thermos t at FT Bus B FT Bus A PIM Slave V Boiler Identity Card V in GN D High Limit Sensor Outlet Sensor Air Flow Safety 2 Safety 1 Inlet Sensor Vent Sensor 4 to 20 MA Fan Power 18 VDC Fan GND Flow SEN GND Flow SEN PW 12 VDC PWM Out Flow Sens or Tac homet er To J10 P in 3 To J10 P in 4 24 VAC L1 L2 2 STG MV MV PV RTN Hot Dry Contact Blower System Pump Boiler Pump DHW Pump ...

Page 9: ...Safety 1 return Molex Micro Fit 20 30AWG 2 0A J8 4 Airflow return Molex Micro Fit 20 30AWG 2 0A J8 5 Safety 2 switch Molex Micro Fit 20 30AWG 2 0A J8 6 Safety 2 return Molex Micro Fit 20 30AWG 2 0A J9 1 Inlet Sensor Molex Micro Fit 10K Thermistor J curve J9 2 Vent Sensor Molex Micro Fit 10K Thermistor J curve J9 3 Sensor Common Molex Micro Fit 10K Thermistor J curve J9 4 Sensor Common Molex Micro ...

Page 10: ...Jr 120 240VAC 8A J13 4 L1 supply input Molex Mini Fit Jr 120 240VAC 8A K5 Relay F1 and F2 terminals 250 QC terminals 120 240VAC 15A J14 1 DHW Pump Molex Mini Fit Jr 120 240VAC 5A J14 2 Boiler Pump Molex Mini Fit Jr 120 240VAC 5A J14 3 L1s System Pump Supply Molex Mini Fit Jr 120 240VAC 8A J14 4 System Pump Molex Mini Fit Jr 120 240VAC 5A J14 5 L1 Supply power Molex Mini Fit Jr 120 240VAC 8A J14 6 ...

Page 11: ...DHW Sensor Common 10K Thermistor J curve J2 3 System Supply Sensor 10K Thermistor J curve J2 4 System Sensor Common 10K Thermistor J curve J2 5 Outdoor Sensor 10K Thermistor J curve J2 6 Outdoor Sensor Common 10K Thermistor J curve J2 7 tN4 Communications Network Signal J2 8 0 10Vdc Analog EMS Input 0 10 VDC or 4 20mA J2 9 Common GND J1 1 Alarm Contacts 0 30VAC 2 0A Max Dry contact J1 2 Alarm Cont...

Page 12: ...aning of the various digits in the part number Use this information to order the correct board 35 9 X X X X X X X X IGNITION TYPE 1 Direct Spark 2 Direct Spark with External Relay 6 Hot Surface Ignition 7 Proven Hot Surface Ignition VALVE FAN CONFIGURATION 0 Modulating 1 stage 1 One Stage 2 Two Stage 3 Intermittent Pilot PV MV 4 One Stage with Auxiliary 5 Isolated Modulating 1 stage 6 Isolated One...

Page 13: ...3 SERIES 35 60 61 63 608 SERIES 35 65 66 SERIES 35 9X The object of the declaration described above is in conformity within the relevant union harmonization legislation Gas Appliance Regulation EU 2016 426 Low Voltage Directive 2014 35 EC EMC Directive 2014 30 EC Rohs 2011 65 EU The following harmonized standards and technical specifications have been applied EN298 2012 Automatic Burner Control sy...

Reviews: