F-35-2000
October 2018
1 of 12
Series 35-9X Modulating
Platform Ignition Module (PIM
®
)
OPERATION AND INSTALLATION INSTRUCTIONS
DESCRIPTION
The Fenwal Controls Platform Ignition Module (PIM
®
) integrates
the functions of Automatic Ignition Control with temperature
regulating and control functions. The PIM is designed for a range
of hydronic boilers including both staged systems and
modulating types. The PIM can be configured as a direct spark
ignition (DSI), intermittent pilot (IP) or Hot Surface Ignition
(HSI) to provide safe lighting and supervision of the burners in
an appliance. The PIM is also designed to connect to and receive
commands from the tekmar
®1
Host Controller. When connected
to a Host Controller, the PIM offers expanded control
functionality including Domestic Hot Water, outdoor reset,
diagnostic messages, and other system capabilities.
APPLICATIONS
The PIM and Host Controller system is suited to a wide variety
of gas-fired hydronic heating systems including:
•
High-efficiency Modulating Condensing Boilers
•
Fan-assisted single and multi-staged Boilers
•
Multiple Boiler Installations using intelligent sequencing
•
Intermittent Pilot based Hydronic appliances
•
Water Heaters
•
Pool and Spa Heaters
AGENCY APPROVALS
SPECIFICATIONS
1.The tekmar BTCII Boiler Controller is fully compatible with
the Fenwal PIM and provides complete hydronic boiler
operation. For more information, contact tekmar controls at
(250) 545-7749.
2. EMC Emission testing to be verified after incorporation into
end use appliance.
CSA Design certified to ANSI Z21.20,
CAN/CSA C22.2 No. 199-M99 and ANSI
Z21.20-2014 CAN/CSA C22.2 No.
60730-2-5-14
CE Approved to EN 298-2012
2
WARNING
Installing or operating the product inconsistent
with these instructions or specifications could
cause serious property damage, injury or death.
Specification
Value
Input Power
Control: 18-30 VAC 50/60 Hz
(Class 2 Transformer)
Input Current Drain
400 mA @ 24 VAC with gas and
blower relays energized (Control
only)
Gas Valve Relays
5.0A max (continuous)
Combustion Blower
5.0 A max for standard (J2)
connection
15.0 A max for heavy-duty (K5
relay) terminals
Hot Surface Igniter
5.0 A max, 120/240 VAC
Pump Relays
5.0 A max (continuous)
Alarm Relay
2.0 A, 30 VDC or 30 VAC max
Operating Temperature
-40°F to + 165°F (-40°C to +74°C)
Storage Temperature
-40°F to + 185°F (-40°C to +85°C)
Sensor Temperature Range
-22°F to + 260°F (-30°C to
+126°C)
Flame Sensitivity
0.7
μ
A minimum
Flame Failure Response or
Reignition Time
0.8 seconds maximum
Flame Detector Self-check Rate Once per second minimum
Flame Failure Lockout Time
Varies by model
Types of Gas
Natural, LP, or manufactured
Spark Rate
Remote sense (50/60 Hz)
Local sense (25/30 Hz)
Size (LxWxH)
8.50 x 6.50 x 2.50 inches
(21.59 x 16.51 x 6.35 cm)
Ingress Protection
Not rated, protection provided by
appliance in which it is installed.
Moisture Resistance
Conformal coated to operate non-
condensing to 95% R.H.
Tries for Ignition
One or three try versions available
Trial for Ignition Period
1 to 30 seconds, up to 300 seconds
(IP)
Pre-purge Timings
1 to 255 seconds
Inter-purge Timings
1 to 255 seconds