Effective: January 2023
2
F-05-50
PROVISIONING
Installation and Configuration with Mobile App
During initial power-up, LED2 (Green) flashes to notify user it is
in provisioning mode. The mobile application walks user through
the process of provisioning the appliance. The mobile application
connects to the connectivity module via Bluetooth. Once
securely connected, LED1 (Red) flashes while searching for
available Wi-Fi networks. The user then selects the network they
want to use and enter its password. The connection is then
verified through the cloud and back to the mobile phone via the
Internet. LED2 (Green) changes to a solid on after successfully
connecting to the Internet and authenticating.
OPERATION
Power Up
On powerup, the connectivity module runs diagnostics. After a
successful power up, LED2 (Green) stays solid to indicate secure
connection to the internet. LED4 (Green) stays solid to indicate
successful communication with gas ignition control.
If there is any data in memory of the connectivity module that
has not been previously uploaded to the cloud, that data is
uploaded at this time.
Normal Operation
The connectivity module constantly monitors the gas ignition
control activity and the three proving switches. All data is stored
in the module’s memory during normal operation. At the
completion of a burn cycle, the data is sent to the cloud and then
available in the Fenwal ConnectedControls application.
Alert Conditions
In the event of a gas ignition control alert, such as a lockout, the
connectivity module will immediately send all data in memory
including the alert condition to the cloud. The Fenwal
ConnectedControls application can be configured to notify end-
users of the alert condition.
Refresh Command
Using the Fenwal ConnectedControls mobile application, a
refresh command can be sent to the connectivity module. Upon
receiving this command all available data in memory of the
connectivity module, including the current state, is sent to the
cloud.
Reset Command
Using the Fenwal ConnectedControls application, a reset
command can be sent to the connectivity module during certain
alert conditions. Upon receiving this command, the TH relay is
momentarily opened and then re-closed to cycle the TH signal
to the gas ignition control. The software contains limits
controlling when and how often this reset can be done.
Loss of Power
On a loss of power, any data that has not been sent to the cloud
is written to non-volatile memory for transmission on the next
power up cycle.
MOUNTING AND WIRING
The 05-50 with internal antenna option is position sensitive. The
internal antenna is placed on the right side of the module (as
noted on the label) and must be kept a minimum of 15mm (.6")
away from any metal surface, including below the module. As
such, the connectivity module should not be mounted to a metal
surface without the appropriate spacing.
The 05-50 with external antenna option is not position sensitive
and can be mounted vertically or horizontally. The module may
be mounted on any surface and fastened with #6 sheet metal
screws. Consideration should be taken for mounting the external
antenna to reduce signal blockage by metal surfaces. The Wi-Fi
signal radiates perpendicular to the antenna.
Secure the module in an area that will experience minimum
vibration and remain below the maximum ambient operational
temperature of 176°F (80°C).
All connections should be made with UL approved, 105°C rated,
18 gauge stranded wire with .054" minimum insulation thick-
ness. Refer to the appropriate wiring diagram when connecting
the 05-50 to other components in the system.
CAUTION
Label all wires prior to disconnection when
servicing or replacing controls. Wiring errors can
cause improper and dangerous operation. A
functional checkout of a replacement control
should always be performed.
CAUTION
The control must be mounted and located in a
manner which protects components from
exposure to water (dripping, condensate,
spraying, rain). Any control that has been
exposed to water must be replaced.
WARNING
All wiring must be done in accordance with both
local and national electrical code, and by a
trained service technician. Wiring must be at
least #18 AWG /AWM rated for 105°C or higher.
WARNING
The 05-50 uses voltages of shock hazard
potential. Wiring and initial operation must be
done by qualified service technician.
WARNING
Operation outside specifications could result in
failure of the Fenwal Controls product and other
equipment with injury to people and property.
WARNING
Do not disconnect any electrical loads while the
automatic gas ignition control is powered.
Disconnect power prior to installation or
replacement of the control with the end use
appliance.