Fema Electronica M Series User Manual Download Page 16

FEMA ELECTRÓNICA . Series M . M50-P

16

Type 

of relay 

 

3 contact relay (NC, NO, common)

Current 

maximum 

8A per relay (resistive load)

Voltage 

maximum* 

250 Vac continuous

Isolation

 

 

3500 Veff

Type 

of terminal   

plug-in screw terminal, pitch 5.08 mm

Slots

 allowed 

 

‘Opt.1’, ‘Opt.2’, ‘Opt.3’ 

(see section 1.13)

Output

 ranges 

4/20 mA active, 4/20 mA passive 0/10 Vdc

Accuracy

 (at 25 ºC) 

<0.1% FS

Isolation

 

1000 Vdc

Slots

 allowed 

‘Opt.1’, ‘Opt.2’, ‘Opt.3’ 

(see section 1.13)

The R1 module provides 1 relay output to Series M panel meters. 

Up to a maximum of 3 R1 modules can be installed in a single instru

-

ment  (3 relays). 

Note : for more than three relays per instrument or larger relay den-

sity per module, see special modules R2, R4 and R6 at section 2.6

.

Relays  with  3  contacts  each  (common,  normally  closed,  normally 

open), with switching capability up to 250V @ 8A.
Modules R1 are configured from the ‘ALr1’, ‘ALr2’ and ‘ALr3’ alarm 

menus of the panel meter. The ‘ALrX’ menus provide configuration 

for main setpoint, hysteresis, independent activation and deactiva

-

tion delays, and a second setpoint to create windowed alarms.
Modules R1 are installed on slot ‘

Opt.1

’, ‘

Opt.2

’ or ‘

Opt.3

’ 

(see sec-

tion 1.13)

 and are configured from instruments front keypad.

The R1 module can be ordered pre-installed into a Series M panel 

meter, or standalone for delayed installation, as they do not require 

soldering or special configuration.

2. Output and control modules

2.1 Module R1

2.2 Module AO

Terminal A 

Common

Terminal B 

NO - Normally Open

Terminal C 

NC - Normally Closed

Opt.2

Opt.1

Op

t.3

Power

A B C

A B C

A B C

Signal

The AO module provides 1 analog output with 4/20 mA or 0/10 Vdc 

configurable output range. Output current loop configurable as ac

-

tive (the instrument provides the excitation for the loop) or passive 

(the loop is externally powered). Signal output proportional to the 

instruments  reading.  Fully  configurable  scaling,  in  direct  (positive 

slope) or inverse (negative slope) scaling.
Up to a maximum of 3 analog output modules can be installed in a 

single instrument, all outputs isolated between them and isolated 

from the power and input signal circuits.
Configuration from instrument front keypad, through menu entries 

‘Opt.1’, ‘Opt.2’ or ‘Opt.3’, depending on the position the module is 

installed 

(see section 1.13)

.

The RTU module can be ordered pre-installed into a Series M panel 

meter, or standalone for delayed installation, as it does not require 

soldering or special configuration.

Terminal A 

Vexc

 

Terminal B 

Signal in mA or Vdc

 

Terminal C 

GND

Jumper M 

closed for mA 

 

Jumper V 

closed for Vdc

M V A B C

M V A B C

M V

A B C

Opt.2

Opt.1

Op

t.3

Power

Signal

For  more  information  see  document  3510_MODULE-M_R1_

manual_i.pdf

For  more  information  see  document  2654_MODULE-M_AO_

manual_i.pdf

Summary of Contents for M Series

Page 1: ...riza tion fast access to alarm setpoints tare function on power up function measure function configu rable reading brightness Universal AC and DC power Up to 3 optional modules for output and control...

Page 2: ...reading password protection 5 brightness levels 1 1 How to order M50 P Model Power Option 1 Others H Option 2 Option 3 R1 1 relay AO analog output RTU Modbus RTU S4 RS 485 S2 RS 232 empty H 85 265 Vac...

Page 3: ...Panel cut out 16 8 75 Passive voltage signal 0 10 Vdc 10 Vdc Active voltage signal 0 10 Vdc 10 Vdc Common Signal Active current loop 4 20 mA 20 mA Passive current loop 4 20 mA 20 mA Vexc Signal Commo...

Page 4: ...s analog outputs serial communi cations see section 2 1 7 Technical specifications Ranges Accuracy Zin Max signal overload Offset drift span drift includes offset drift 4 20 mA 0 03 FS 11 Ohm 100 mA p...

Page 5: ...E 3 inside the menus the LE 3 key functions as the ES CAPE key It leaves the selected menu and eventually will leave the whole menu When leaving the configuration menu with the LE 3 key the changed pa...

Page 6: ...instru ment scaling parameters when the instrument is being installed on the field providing a fast and easy way to compensate offset signals To operate the Field correction F cor function for the of...

Page 7: ...s due to fluctuating input signals around the set point at Activation delay dEL 0 configure the delay to apply before alarm activation The activation delay starts counting when the set point value is...

Page 8: ...ory of maximum MAX function displays the maximum reading value stored in memory It also provides a way to reset the value This parameter is eligible for configuration through the Fast access menu see...

Page 9: ...the front of the instrument gives access to a list of functions configurable by the operator See section 1 8 for an ex planation on how to operate the fast access menu The Key UP Fast access K uP menu...

Page 10: ...rE menu allows to operate the instrument for load cell and weight applications The tare function assigns the actual input signal value to a reading of 0 Kilos by adding an inter nal offset It does not...

Page 11: ...access the configuration menu key SQ The fast access menu is not password pro tected 1 10 12 Function Password At the Brightness LIGh menu select the light intensity for the front leds With this funct...

Page 12: ...0 for a description of each menu entry Scaling Input low Display low Input high Display high Alarm 1 Setpoint Hysteresis Setpoint 2 Active Alarm type Activation delay Deactivation delay Left zeros Ste...

Page 13: ...f segments Value 2 to 20 Input 0 Display 0 Input 1 Display 1 On power up Delay Tare Seconds Option 1 Configuration menu for the module installed at Opt 1 Option 2 Configuration menu for the module ins...

Page 14: ...tion for the position of each module You may need to access the inside of the instrument to add or re place internal modules Use a flat screwdriver to unlock the upper clips marked with A Then unlock...

Page 15: ...sword off Brightness 3 strument must be assured Do not expose the instrument to excess of humidity Maintain clean by using a humid rag and do NOT use abrasive products such as alcohols solvents etc Ge...

Page 16: ...ter or standalone for delayed installation as they do not require soldering or special configuration 2 Output and control modules 2 1 Module R1 2 2 Module AO Terminal A Common Terminal B NO Normally O...

Page 17: ...module for Series M of panel meters ASCII protocol with Master Slave architec ture Addressable with up to 31 modules Frames codified in rep resentable ASCII characters codes 32 to 255 directly visibl...

Page 18: ...SCII characters codes 32 to 255 directly visible using hyperterminal or similar programs Access to display values alarm status memory of maximum and minimum alarm setpoints Configuration from instrume...

Page 19: ...FEMA ELECTR NICA Series M M50 P 19 T h i s p a g e b l a n k...

Page 20: ...the panel and remove the front filter Inter nal press buttons for configuration are accessible Optionally request the instrument preconfigured from factory Without front keypad Front IP65 protection...

Page 21: ...lder 4 1 THM benchtop housing Adapter96 x 96 mmfor96 x 48 mm instruments Adapter for DIN rail mount for Series M and Series K of panel meters Front IP65 protector for Series M and Series K of panel me...

Page 22: ...FEMA ELECTR NICA Series M M50 P 22 Notes...

Page 23: ...FEMA ELECTR NICA Series M M50 P 23 Notes...

Page 24: ...info fema es www fema es Panel meters Standard 96x48mm Panel meters Compact 72x36mm Panel meters Miniature 48x24mm Large format meters Signal converters Isolators Bar meters Low cost Customized instr...

Reviews: