Fema Electronica M Series User Manual Download Page 10

FEMA ELECTRÓNICA . Series M . M50-P

10

On power-up

Delay

Tare

Seconds

Tools

1.10 Configuration menu (cont.)

The ‘

On Power Up

’ (‘

on.Pu

’) menu configures functions to apply at 

start-up. It applies only to instrument restart after power loss. It does 

not apply to instrument restart due to change in configuration.
• parameter ‘

Delay

’ (‘

dLAy

’) assigns a waiting time in seconds. The 

instrument waits the configured time before starting normal func

-

tion. During this waiting time, the display shows all decimal points 

on in flash mode, all alarms are in ‘oFF’ state, there is no signal acqui

-

sition and there is no communications or control being performed. 

After  the  configured  time  is  over,  the  instrument  starts  in  normal 

function. Delay value between 0 and 200 seconds.

Application - the start-up process for an automation system implies 

that different parts of the system (engines, actuators, controllers, ...) 

have different start-up times. The ‘Delay’ function gives time to the 

instrument to wait until the slowest part of the system is fully func-

tional before executing actions on the system (signal reading, relay 

activation, ...)

• the ‘

Tare

’ (‘

tArE

’) functions allow to activate an automatic tare of 

the reading each time the instrument is restarted. See section 

1.10.9

 

for more information on the ‘tare’ function.

1.10.8 Menu ‘On Power Up’

The ‘

Tare function

’ (‘

tArE

’) menu allows to operate the instrument 

for load-cell and weight applications. The tare function assigns the 

actual input signal value to a reading of ‘0’ Kilos, by adding an inter

-

nal offset. It does not modify the scaling parameters of the instru

-

ment.

The ‘Tare’ function can be applied pressing button ‘LE’ (

3

) at the 

front keypad 

(see section 1.10.10)

. The offset value is eligible for visu

-

alization through the ‘

Fast access

’ menu 

(see section 1.10.6).

To work with load-cell applications it is important to first adjust the 

scaling of the instrument to the load-cell used.

Application - A load cell with 2 mV/V parameter, powered at 10 Vdc, 

with nominal weight of 500 Kilos, together with a signal converter 

that provides 4/20 mA signals for a 0/20 mV signal from the load-cell. 

The scaling to configure at the meter is 4/20 mA = 0/500.0 Kilos. Once 

the meter is scaled, the tare function can be used to ‘tare’ the reading 

to 0 Kilos.

• at the ‘

Reset

’ (‘

rSt

’) menu select ‘

yES

’ to reset the tare offset value 

in memory.

1.10.9 Menu ‘Tare function’

Tare function

Reset

Key LE

Tare

Alarm unlock

No function

1.10.10 Menu ‘Key LE’

The ‘LE’ (

3

) key at the front of the instrument can be configured to 

activate several functions. Only one function can be assigned to the 

‘LE’ (

3

) key

• the ‘

No function

’ (‘

nonE

’)

 

value assigns no function.

• the ‘

Tare

’ (‘

Tare

’) value assigns a tare function 

(see section 1.10.9).

• the ‘

Alarm unlock

’ (‘

A.Lck

’)

 

value assigns the manual unlock of the 

alarms function, for instruments with the ‘

Locked alarms

’ (‘

A.Lck

’) 

function activated 

(see section 1.10.3)

Summary of Contents for M Series

Page 1: ...riza tion fast access to alarm setpoints tare function on power up function measure function configu rable reading brightness Universal AC and DC power Up to 3 optional modules for output and control...

Page 2: ...reading password protection 5 brightness levels 1 1 How to order M50 P Model Power Option 1 Others H Option 2 Option 3 R1 1 relay AO analog output RTU Modbus RTU S4 RS 485 S2 RS 232 empty H 85 265 Vac...

Page 3: ...Panel cut out 16 8 75 Passive voltage signal 0 10 Vdc 10 Vdc Active voltage signal 0 10 Vdc 10 Vdc Common Signal Active current loop 4 20 mA 20 mA Passive current loop 4 20 mA 20 mA Vexc Signal Commo...

Page 4: ...s analog outputs serial communi cations see section 2 1 7 Technical specifications Ranges Accuracy Zin Max signal overload Offset drift span drift includes offset drift 4 20 mA 0 03 FS 11 Ohm 100 mA p...

Page 5: ...E 3 inside the menus the LE 3 key functions as the ES CAPE key It leaves the selected menu and eventually will leave the whole menu When leaving the configuration menu with the LE 3 key the changed pa...

Page 6: ...instru ment scaling parameters when the instrument is being installed on the field providing a fast and easy way to compensate offset signals To operate the Field correction F cor function for the of...

Page 7: ...s due to fluctuating input signals around the set point at Activation delay dEL 0 configure the delay to apply before alarm activation The activation delay starts counting when the set point value is...

Page 8: ...ory of maximum MAX function displays the maximum reading value stored in memory It also provides a way to reset the value This parameter is eligible for configuration through the Fast access menu see...

Page 9: ...the front of the instrument gives access to a list of functions configurable by the operator See section 1 8 for an ex planation on how to operate the fast access menu The Key UP Fast access K uP menu...

Page 10: ...rE menu allows to operate the instrument for load cell and weight applications The tare function assigns the actual input signal value to a reading of 0 Kilos by adding an inter nal offset It does not...

Page 11: ...access the configuration menu key SQ The fast access menu is not password pro tected 1 10 12 Function Password At the Brightness LIGh menu select the light intensity for the front leds With this funct...

Page 12: ...0 for a description of each menu entry Scaling Input low Display low Input high Display high Alarm 1 Setpoint Hysteresis Setpoint 2 Active Alarm type Activation delay Deactivation delay Left zeros Ste...

Page 13: ...f segments Value 2 to 20 Input 0 Display 0 Input 1 Display 1 On power up Delay Tare Seconds Option 1 Configuration menu for the module installed at Opt 1 Option 2 Configuration menu for the module ins...

Page 14: ...tion for the position of each module You may need to access the inside of the instrument to add or re place internal modules Use a flat screwdriver to unlock the upper clips marked with A Then unlock...

Page 15: ...sword off Brightness 3 strument must be assured Do not expose the instrument to excess of humidity Maintain clean by using a humid rag and do NOT use abrasive products such as alcohols solvents etc Ge...

Page 16: ...ter or standalone for delayed installation as they do not require soldering or special configuration 2 Output and control modules 2 1 Module R1 2 2 Module AO Terminal A Common Terminal B NO Normally O...

Page 17: ...module for Series M of panel meters ASCII protocol with Master Slave architec ture Addressable with up to 31 modules Frames codified in rep resentable ASCII characters codes 32 to 255 directly visibl...

Page 18: ...SCII characters codes 32 to 255 directly visible using hyperterminal or similar programs Access to display values alarm status memory of maximum and minimum alarm setpoints Configuration from instrume...

Page 19: ...FEMA ELECTR NICA Series M M50 P 19 T h i s p a g e b l a n k...

Page 20: ...the panel and remove the front filter Inter nal press buttons for configuration are accessible Optionally request the instrument preconfigured from factory Without front keypad Front IP65 protection...

Page 21: ...lder 4 1 THM benchtop housing Adapter96 x 96 mmfor96 x 48 mm instruments Adapter for DIN rail mount for Series M and Series K of panel meters Front IP65 protector for Series M and Series K of panel me...

Page 22: ...FEMA ELECTR NICA Series M M50 P 22 Notes...

Page 23: ...FEMA ELECTR NICA Series M M50 P 23 Notes...

Page 24: ...info fema es www fema es Panel meters Standard 96x48mm Panel meters Compact 72x36mm Panel meters Miniature 48x24mm Large format meters Signal converters Isolators Bar meters Low cost Customized instr...

Reviews: