background image

 

- 8 - 

Remote Models  

The remote models are designed to use 449 refrigerant and are shipped from the factory with the evaporator 
coil, expansion valve, sight glass and refrigerant solenoid valve. A thermostat senses evaporator 
temperature and opens and closes the refrigerant solenoid valve. The solenoid valve closes and shuts off the 
refrigeration flow to the unit and initiates a pump down cycle. This will allow the remote low pressure 
switch to open and shut off remote compressor. The temperature control may require some adjustment by 
the installer for proper operation of unit.  This unit also has a defrost timer that will shut the refrigeration 
solenoid off a set number of times per day (set at the factory to 3 times per day) to insure a full defrost 
occurs. The solenoid will remain off until either the off time is reached or until the temperature sensor on 
the coil reaches a set temperature, whichever happens first

 

 
The condensing unit is optionally supplied from the factory for remote location installation. The 
condensing unit supplied from the factory will require a high low pressure switch that must be mounted and 
wired by the installer. The high low pressure switch must be wired in series with the compressor power 
supply as shown in diagram below. A drier/filter must also be installed by installer. 
 
1.

 

Mount condensing unit indoors as close to the remote display case as practical.  The refrigeration line 
should be as short as possible and must not exceed 30 feet. 

2.

 

All refrigeration and/or electrical materials between the condensing unit and display case are to be 
supplied by installing contractor. 

3.

 

Route properly sized and designed refrigeration lines from the condensing unit to the cabinet.           
Horizontal suction lines should be pitched downward towards the condensing unit at least ½” per 10’ 
run to aid the oil drainage.  A “P” trap must be installed in the suction line at the foot of every riser to 
insure oil return. Dry nitrogen must be used to flow through tubing while brazing refrigeration lines. 

4.

 

The suction line must be insulated the entire length with Armaflex (or equivalent). Do not run liquid 
line inside insulation with suction line. 

5.

 

The remote high/low-pressure control must be mounted, wired and set pressures by the installer.  

6.

 

Leak check the condensing unit, cabinet, and all connecting tubing. The cabinet and condensing unit 
tubing should be checked to insure no leaks occurred during shipping or from rough handling.  
Make certain all refrigeration valves are opened and evacuate system to 500 microns. Charge the 
system with the refrigerant type specified on the data plates. 

 

REMOTE
HIGH LOW
PRESSURE
CONTROL

LIQUID LINE

SUCTION LINE (INSULATED)

REMOTE
CONDENSING
UNIT

EVAPORATOR COIL

DISPLAY CASE

EXPANSION
VALVE

HIGH

LOW

LIQUID LINE 
SOLENOID VALVE

SIGHT GLASS

DRIER/FILTER

FIELD CONNECTION

HOT

FUSED
POWER
SUPPLY

DEFROST
TIMER

HOT

DEFROST
TERMINATE

TEMPERATURE
CONTROL

NEUT.

TEMP. CONTROL PROBE

 

 
 
 

Summary of Contents for SSRSP Series

Page 1: ...RIGERATED SSRSP SANDWICH PREP CASE MODELS KEEP THIS MANUAL FOR FUTURE REFERENCE Engineering and technical data are subject to change without notice FEDERAL INDUSTRIES 215 FEDERAL AVE BELLEVILLE WI 535...

Page 2: ...utton and Display Overview 17 Powering on Control 17 Adjusting the Set Point 17 Entering Manual Defrost Mode 18 Error Codes 18 Electronic Control Operation 19 Control Parameters 20 Initial Startup 20...

Page 3: ...ded only for persons qualified to perform electrical work DANGER Improper or faulty hookup of electrical components in the case can result in severe injury or death All electrical wiring hookups must...

Page 4: ...r death will occur if you ignore the message WARNING Severe injury or death can occur if you ignore the message CAUTION Minor injury or damage to your case can occur if you ignore the message NOTICE T...

Page 5: ...trical wiring hookups must be done in accordance with all applicable local regional or national electrical standards A separate circuit for each display case is required to prevent other appliances on...

Page 6: ...l against the top end glass or door frames and do not pull on end panels when removing the case from the skid or moving the case Case damage or glass breakage will result 1 Remove crate top and sides...

Page 7: ...ure side is a safety to protect the compressor in the case of refrigerant loss The high pressure side is a safety to protect from system failure causing too high of system pressure The high side of th...

Page 8: ...remote display case as practical The refrigeration line should be as short as possible and must not exceed 30 feet 2 All refrigeration and or electrical materials between the condensing unit and displ...

Page 9: ...rant is used Note Check your State and Local regulations for approved refrigerants for your install location Federal Industries is not liable for any alternate refrigerants used The control is located...

Page 10: ...bracket bottom tab to clear shelf standard slot 3 Swing shelf bracketbottom tab into shelf standard slot 4 Place the desired shelf bracket notch of 0 6 or 12 degrees onto bottom of shelf standard slot...

Page 11: ...orts as outlined in the appropriate Shelf Installation section of this manual 10 Removal of shelving is performed by following steps in reverse order 11 The shelf standards are removable from case by...

Page 12: ...ner clip Position the glass shelf retainer clips in the 2 far corners of glass as indicated in the above illustration Repeat for each glass shelf 2 Also for first time installation it will be necessar...

Page 13: ...and down out of upper track 2 Remove the outer inside door using the same procedure 3 The inner door set can then be removed using the same procedure starting with the inner outside door followed by t...

Page 14: ...ng the night curtain down and around sandwich prep area Hook the edge of night curtain over the front edge of sandwich prep area under the front glass 2 Move around to the front of the case Lift the f...

Page 15: ...lector There also may be a U retainer clip in the center of the case that must also engage the security night cover flange 3 Set the top flange of the security cover down against the top glass handle...

Page 16: ...ONTROLS OVERVIEW TEMPERATURE CONTROL POWER SWITCH LIGHT SWITCH Power Switch The unit has a power switch that turns off power to the entire unit including the condensate evaporator and the lights Light...

Page 17: ...control may already be in the on mode when shipped from factory To turn refrigeration control power to off press and hold for approx three seconds The display will read Off while the button is depres...

Page 18: ...control will return to normal operation and will automatically clear the codes from the display Carel Control EO Air sensing probe Open or shorted E1 Evap coil probe Open or shorted Error codes may be...

Page 19: ...p control cuts out at 26 F 3 3 C at the coldest setting 9 and 36 F 2 2 C at the warmest setting 1 See Error Reference source not found on page Error Bookmark not defined for more details on using the...

Page 20: ...Common Resistance Chart Probe Temp Maximum Resistance Normal Resistance Minimum Resistance 32 F 0 C 27 83 27 28 26 74 77 F 25 C 10 1 10 9 9 212 F 100 C 1 0 97 0 94 INITIAL STARTUP After all the checks...

Page 21: ...e used provided sufficient adapters are used SSRSP5052 4 HALF PANS SSRSP5952 5 HALF PANS SSRSP7752 7 HALF PANS A set of divider bars are supplied with each case If required additional adapters can be...

Page 22: ...THE FRONT SHELF SUPPORT 4 Remove the remaining double sided tape from the Front Shelf Support 5 Apply a new layer of double sided tape to the new LED and adhere to the front shelf support Locate new L...

Page 23: ...er lower areas of case using a damp cloth 3 To allow easier access to clean upper section interior tilt the upper front glass open Tilt the front glass up by standing in front of the case and grabbing...

Page 24: ...ufficient time for the unit to reach room temperature before proceeding with cleaning NOTICE Remove all product and food pans from case before proceeding with cleaning procedure NOTICE Acrylic front a...

Page 25: ...ove the fan shroud assembly There are either 2 retainer latches or 2 thumbscrews located at each end at the front of the fan shroud Lift the black tab up on each retainer latch or remove the 2 front t...

Page 26: ...scratches 14 Slide the tray catch out from under wrap board and wash with warm soapy water 15 Remove the wrap board assembly by lifting assembly up out of key slots on support brackets Clean the Wrap...

Page 27: ...Phone 800 356 4206 and choose the Tech Support Warranty Option Email Service federalind com For Warranty Compressors please contact the Parts Department Phone 800 356 4206 and choose the Warranty Par...

Page 28: ...ntered situations that can cause unsatisfactory case performance CAUTION Before servicing case turn off power at the main breaker of fuse box Case Does Not Operate Check for disconnected power supply...

Page 29: ...customer service department at Federal Industries at 800 356 4206 The customer service department at Federal Industries should be contacted at the time of sale or disposal of your case so records may...

Page 30: ...30 MAIN WIRING DIAGRAMS SELF CONTAINED SSRSP5052 SSRSP5952 SSRSP7752 Mfg d Before 12 15 18 REMOTE SSRSP5052 SSRSP5952 SSRSP7752 Mfg d Before 12 15 18...

Page 31: ...31 SELF CONTAINED SSRSP5052 SSRSP5952 SSRSP7752 Mfg d After 12 15 18 until 12 1 19 REMOTE SSRSP5052 SSRSP5952 SSRSP7752 Mfg d After 12 15 18 until 12 1 19...

Page 32: ...K BLK BLK RIB BLK BLK BLK EVAP FAN BLK RIB BLK RIB BLK BLK BLK M PLUG CONDENSATE PUMP OR EVAPORATOR G FAN 4 5 RELAY M REMOTE COMPRESSOR HI LO PRESS SW Y Y OPTIONAL REMOTE MOUNTED WIRED COMPONENTS ALL...

Page 33: ...wer Supply Cases mfg after 12 15 18 LED Light Assembly Cases Prior to 12 15 18 SA5307 2 SA5307 3 SA5307 4 LED Light Strip Cases Prior to 12 15 18 42 19038 42 19038 5 42 19038 3 LED Strip Light Cases A...

Page 34: ...SP7752 Rear Door Bottom Track Btm Opt 57 18519 2 57 18519 3 57 18519 4 Rear Door Jamb Btm Section Optional Rear Door Inner Solid Btm Section Opt 53 18211 2 53 18211 3 53 18211 4 Rear Door Outer Solid...

Page 35: ...Only WARNING This product can expose you to chemicals including chromium which is known to the State of California to cause cancer and birth defects or other reproductive harm For more information go...

Page 36: ...36 REV CHANGE RECORD APP D DATE ECN B REVISED CONTROL PARTS LIST SES 5 14 19 C ADDED DUAL PRESSURE CONTROL INFO ADC 8 6 19 3506...

Reviews: