background image

2    

Safety Messages to Installation and Service Personnel  

of Federal Signal Products

Peoples lives depend on your proper installation of our products. It is important to follow all instructions 

shipped with the products. The selection of the mounting location for the device, its controls and routing of the 

wiring is to be accomplished under the direction of the Facilities Engineer and the Safety Engineer. In addition, 

listed below are some other important safety instructions and precautions you should follow:

• 

This unit must be installed by a qualified electrician in accordance with the National Electrical Code/

NFPA 70/NFPA 72/ANSI and with all local codes and authorities having jurisdiction.

• 

Read and understand all instructions before installing or operating this equipment.

• 

Consult the authority having jurisdiction in your area regarding the proper use and installation of this 

product.

• 

Do not connect this product to the system when power is on.

• 

After installation and completion of the initial system test, a program for periodic testing of this product 

must be established. Refer to NFPA 72G, local Fire Codes and the authority having jurisdiction for this 

information.

• 

Show these instructions to your Safety Engineer and then file them in a safe place and refer to them 

when maintaining and/or reinstalling the unit.

Failure to follow all safety precautions and instructions may result in property damage, serious injury, or death.

Summary of Contents for PS1000

Page 1: ...2562563A REV A 1212 Printed in U S A Installation and Maintenance Manual Model PS1000 Power Supply Charger...

Page 2: ...nd controllers manufactured by Federal Warning Systems are warranteed for two years on parts and one year on labor No agent employee representative or distributor of Seller has any authority to bind t...

Page 3: ...uct Specifications 3 Installing and Maintaining the Model PS1000 5 Mounting the Model PS1000 Enclosure 5 Wiring the Model PS1000 5 Maintaining the Model PS1000 9 Obtaining Service Parts and Support 10...

Page 4: ...70 NFPA 72 ANSI and with all local codes and authorities having jurisdiction Read and understand all instructions before installing or operating this equipment Consult the authority having jurisdicti...

Page 5: ...sealed lead acid or gel batteries Automatic switchover to stand by battery when AC fails 3 6 A maximum charge current Zero voltage drop when switched over to battery backup Supervision AC fail superv...

Page 6: ...A Alarm 10 A Standby 200 mA Alarm 10 A Standby 100 mA Alarm 10 A 24 Vdc 65 Ah Battery NA Standby 8 A Alarm 10 A Standby 1 5 A Alarm 10 A Standby 500 mA Alarm 10 A 1 285 ENCLOSURE DIMENSIONS 15 5 H x 1...

Page 7: ...rill the lower holes and install the three fasteners Place the upper keyholes of the enclosure over the two upper screws Install the two lower screws and make sure to tighten all screws Secure the enc...

Page 8: ...onnected to an annunciator alarm panel The relays are normally energized when AC power is present The contact rating is 1 A at 28 Vdc AC or brownout fail is reported within 1 minute of event To delay...

Page 9: ...ISTRIBUTION MODULE S 115 Vac POWER MAINS NON POWER LIMITED CLASS I BATTERY AND AC SUPERVISION CIRCUIT POWER LIMITED NON POWER LIMITED KEEP POWER LIMITED WIRING SEPARATED FROM NON POWER LIMITED USE 0 2...

Page 10: ...alarm A G Alarm duration hours 15 min 0 2 hour alarm H H Battery capacity required for alarm E F G Ah I Total calculated battery capacity D H Ah J Battery capacity required I 1 8 safety factor Ah Note...

Page 11: ...Under normal load conditions the DC output voltage should be checked for proper voltage level Battery Test Under normal load conditions check that the battery is fully charged check the specified vol...

Page 12: ...eturn authorization from your local distributor prior to returning the product to Federal Signal Please contact your distributor for assistance A product is qualified to be returned for credit when th...