15
GENII-RC Remote Controller
Description, Installation, and User Manual
Federal Signal
www.fedsig.com
Fault
Description
Pcp Node Type
Mismatch
An I/O board reports its type as different from the type in the
controller configuration.
Pilot Tone Fail
An audio input pilot-tone signal has fallen below the configured
threshold.
Pilot Tone Stale
An audio input pilot-tone signal has not been measured within the
configured period.
Psu Fault
The controller power supply has encountered a fault.
Spi Bus Failure
An I/O board or amplifier has a SPI bus failure.
Spi Transaction Failed An amplifier has encountered a problem with its SPI bus.
Speaker Short Circuit
An amplifier speaker circuit has a short circuit.
Spkr Mon Uncalibrated An amplifier is unable to perform impedance monitoring because
it is uncalibrated.
Stack Overflow
The controller, an I/O board, or an amplifier has encountered a
stack overflow.
Statistics Reset
A beacon-monitor or fan-monitor I/O board has reset its statistics.
Sys State Healthy
There are no reported major or minor faults.
Sys State Major Fault
There is at least one reported major fault.
Sys State Minor Fault
There are no reported major faults, but there is at least one
reported minor fault.
Under Temp
A fan-monitor I/O board is reporting the rack is under-
temperature.
Unexpected Reset
An I/O board or amplifier has reset unexpectedly.
Unexpected Uptime
An I/O board or amplifier has reported less uptime than expected.
Unknown Fault
An I/O board or amplifier has encountered an unknown fault.
User Fault
A user-defined fault has occurred on the controller.
3 4 GENII-RC Installation and Setup
For specific configuration information, see the PAGASYS GEN II SYSTEM MANAGER
Software (Model P-SYSMGR-G) manual document number 25500459.
To install the GENII-RC Remote Controller, connect the wiring as follows, and then
configure the Remote Controller using the PAGASYS GEN II System Manager.
Remote Controller wiring:
• Connect AC power cable to the AC Power In port on the rear of the Remote
Controller. AC Power connection uses a standard IEC C13 terminated power cable.
The wall plug should be of a type used in the location the chassis is deployed.
Federal Signal offers cables compatible with the Remote Controller with UK, EU, or
US wall plugs. This cable is not included with the Remote Controller, as it differs on
which wall plug is needed.
• Connect digital relay outputs as needed on the rear panel of the Remote Controller.
Eight digital outputs use three pins for each relay output, NC (normally closed), C
(common), and NO (normally open), and are dry relay contact only (circuit is only open
or closed to pass current). Wire gauge used to connect to the digital outputs should
support current and voltage in “Table 5 GENII-RC Inputs and Outputs” on page 12.