Federal Signal Corporation Informer100 Speaker Manual Download Page 45

45

Programming

Signaling Standalone Manual 

Federal Signal 

www.fedsig.com

To upload a certificate file:

1. 

Click Certificates.

The Certificates page displays.

Fields

Description

Choose File

Choose the new ca-cert.pem, cert.pem or key.pem file.

Upload

Upload the new file.

2. 

Click Browse to select the new ca-cert.pem, cert.pem, or key.pem file.

3. 

Click Upload to upload the new file.

4. 

Reboot the device for the changes to take effect.

7. Uploading Firmware

Use the Upload Firmware page to load a new operating system into the Digi

®

 Ethernet 

module. The Home page displays the current version of the firmware.
To upload new firmware:

1. 

Click Upload Firmware. 

The Upload Firmware page displays.

Summary of Contents for Informer100 Speaker

Page 1: ...Manual 25500845 Rev A0 0323 Printed in U S A Copyright 2023 Federal Signal Corporation Informer100 Speaker Models IS I IP100ACX and IS I IP100DCX High Powered Indoor Outdoor Audible Speaker For use in...

Page 2: ...l 1 708 534 3400 This limited warranty is in lieu of all other warranties express or implied contractual or statutory including but not limited to the warranty of merchantability warranty of fitness f...

Page 3: ...meter pole 17 Mounting without Bracket 18 Opening the Housing 18 Wiring Power to the Control Board 19 Wiring to the Relay Outputs 21 Wiring to the Alarm Initiation Input Connections 21 Using Optional...

Page 4: ...Table 11 Standard DV Messages 51 Table 12 UTM Tones 58 Figures Figure 1 Informer100 Speaker with 255XL light 9 Figure 2 Bracket attached to speaker 13 Figure 3 Width and height of bracket 13 Figure 4...

Page 5: ...to be accomplished under the direction of the Facilities Engineer and the Safety Engineer Listed below are some other important safety instructions and precautions you should follow Electrocution or...

Page 6: ...st the system regularly to confirm that it will be operational in an emergency If future service and operating personnel do not have these instructions to refer to the system may not provide the inten...

Page 7: ...edsig com Symbol Definition _A _V Indicates to reduce the risk of fire replace fuse as marked Pay careful attention to the notice located on the equipment Read and understand the information contained...

Page 8: ...es two relay outputs for controlling strobes or other devices The Informer100 has a 1 2 inch NPT opening on the top of the speaker for simple installation of pipe mount devices The bottom of the speak...

Page 9: ...local alarm initiation inputs to activate unit locally or standalone operation Momentary mode contact closure sounds alarm for programmed duration Continuous mode sounds alarm for duration of closure...

Page 10: ...ry contacts Ethernet Port IEEE 802 3 10 100 Base T connection Alarm Initiating Inputs Four optically Isolated Inputs Dry Contact closure 1 kilohm NOTE The four optically isolated Alarm Initiation Inpu...

Page 11: ...Red LED turns on when Activation input 1 is being activated D12 ACTIVATION INPUT 2 Red LED turns on when Activation input 2 is being activated D14 ACTIVATION INPUT 3 Red LED turns on when Activation...

Page 12: ...tallation Determine a Suitable Location The Informer100 can be mounted on any relatively flat surface with the supplied mounting brackets The mounting surface must be capable of supporting the weight...

Page 13: ...rientation of the curved slots on the L shaped brackets this orientation is important to allow the speaker to be pivoted downward 2 Tighten the 1 4 20 by 5 8 inch screws to approximately 80 in lb 3 At...

Page 14: ...rmer100 Speaker Models IS I IP100ACX and IS I IP100DCX Federal Signal www fedsig com Figure 4 Depth and height with bracket 6 68 in 2 53 in 12 87 in 2 00 in 10 09 in Figure 5 Top view of speaker 10 09...

Page 15: ...t 1 Find a suitable location to mount the speaker Use industry or company preferred practices when mounting hardware to poles or other structures 2 Attach the IS I IP100 PMW bracket to the pole using...

Page 16: ...e location to mount the speaker Use industry or company preferred practices when mounting hardware to poles or other structures 2 Remove the speaker U shaped bracket store the pivot lock bolts 3 Selec...

Page 17: ...peaker The speaker is mounted as described in the Small Pole Mount section with the omni bracket mounted at a distance of 2 0 inches from the speaker Use the following procedure if mounting the speake...

Page 18: ...10 Surface mount hole center dimensions 5 20 in 2 60 in 3 00 6 00 7 39 C L C L 6 1 4 20 0 5 in THREAD DEPTH Opening the Housing Tools required 3 8 inch socket 6 inch extension To open the housing loos...

Page 19: ...d it is recommended to leave the connector on the PCB With I IP100ACX units JP9 is wired from the factory to the power supply PCB With the I IP100DCX units JP9 is wired to the amplifier PCB Use JP6 an...

Page 20: ...al 1 Inter board communications Factory wiring Factory wiring JP6 24 V L2 NUE 24 Vdc GND 24 V 24 Vdc GND 24 V Serial Port 1 2 3 4 JP5 100 W Amp To Driver To Temperature Sense Fuse JP3 Pins 1 2 IS I IP...

Page 21: ...actory wiring Factory wiring JP6 L2 NUE L2 NUE L1 Hot L2 NUE L1 Hot Serial Port 1 2 3 4 Fuse Fuse JP5 JP3 Pins 1 2 Wiring to the Relay Outputs JP4 Relay Outputs 1 2 Normally Open 3 4 Normally Open Wir...

Page 22: ...nd 7 below are common Federal Signal strobes and LED indicators that you can use with the IS I IP100ACX and IS I IP100DCX units Figure 14 on page 23 illustrates the optional visual indicators to use w...

Page 23: ...om Figure 14 225XST I 225XL Strobe with Informer100 Speaker Side View Front View Pipe Nipple 1 2 NPT 3 overall length Recommended customer supplied For a 225XST I 225XL Strobe the following is recomme...

Page 24: ...ker Models IS I IP100ACX and IS I IP100DCX Federal Signal www fedsig com The following figures illustrate the electrical connections with the resistor The programming is for Relay 2 Figure 15 DC Contr...

Page 25: ...a conduit carrying high voltage The wired Ethernet port auto negotiates a 10 100 full or half duplex connection Putting the Informer100 Speaker into Standalone Mode Standalone mode allows the Informe...

Page 26: ...outputs to open close and cycle based on a pre programmed sequence Closing the Housing To close the housing do the following 1 Verify that the cover gasket is in the groove around the perimeter of the...

Page 27: ...ssociated with each input will activate in sequence Lower priority inputs are ignored while higher priority inputs are active If an equal or greater priority momentary input is activated while a conti...

Page 28: ...configured to control audio volume activate relay outputs play tones and play WAV files Functions configured with Commander can also include delays and repeat loops The input functions can be configur...

Page 29: ...Control Station Informer and siren devices Do not duplicate IP addresses or site ID numbers on the network at any time or network errors occur Informer and Siren Site ID numbers start at number 001 an...

Page 30: ...name 5 Enter the Password fedsig or preconfigured Password NOTE The password is case sensitive 6 Click OK The Home page displays The Home page displays a summary of the current configuration settings...

Page 31: ...rmware Version The firmware version of the DIGI Connect ME 9210 module RTU Firmware Version The firmware version of the RTU Up Time The elapsed time since power up or reboot 7 Record the MAC and IP ad...

Page 32: ...ses IP Address or Domain Name The RTU s assigned IPV4 address or its domain name in the IP address field Subnet Mask The RTU s assigned subnet mask Default Gateway The RTU s network gateway for routin...

Page 33: ...ment but MAC address discovery tools may not traverse routers and maintenance may be more difficult 2 Configuring the RTU Settings When the RTU is used with Commander the device s RTU Number and Descr...

Page 34: ...gramming Informer100 Speaker Models IS I IP100ACX and IS I IP100DCX Federal Signal www fedsig com To change the configure the RTU Settings of the Informer 1 Click RTU Settings The RTU Settings page di...

Page 35: ...acter text field to describe the RTU This can be the physical address of the site or any other text string The description field has a 255 character limit and can be scrolled to view additional charac...

Page 36: ...a failover server leave this field blank Address Extension The RTU s assigned Address or Extension number This field is required Registration User ID Username for registration If this field is blank t...

Page 37: ...c address audio will be buffered and play out after the Pretone message It is good practice to limit the duration of Pretone messages to 3 5 seconds To enable Pretone select a digital voice message fr...

Page 38: ...n the Power Attenuation box type or select a the default volume level 5 In the Ambient Attenuation box type or select the ambient attenuation threshold 6 Click Enable SmartMsg to enable the SmartMsg i...

Page 39: ...l Signal www fedsig com NOTE Multicast Transmit Zone microphone audio is only available in Informer15 and Informer100 speakers To configure a multicast zone to receive public address messages 1 Click...

Page 40: ...rrupt multicast pages Multicast Transmit Zone siren audio All audio sources except incoming Multicast Receive Zones are routed to the Multicast TX Zone Configure only one RTU per Zone with a Multicast...

Page 41: ...or if two zones are configured with the same priority the RTU listens to audio only from the first source that started multicasting until the RTU detects the original source has stopped sending RTP au...

Page 42: ...curity page displays Field Description SIP IP Filter Start IP Address Starting IP Address in dotted decimal format End IP Address Ending IP Address in dotted decimal format The ending IP address must...

Page 43: ...Admin privileged users to create users create passwords and assign security privileges You cannot delete the Admin user or change the security privilege for the Admin user You can change the Admin use...

Page 44: ...an disable this user Apply Saves your settings You must reboot for changes to take effect 2 For the Admin fields enter the default Username admin This is the default username 3 For the Admin fields en...

Page 45: ...Upload Upload the new file 2 Click Browse to select the new ca cert pem cert pem or key pem file 3 Click Upload to upload the new file 4 Reboot the device for the changes to take effect 7 Uploading Fi...

Page 46: ...ackup bin ROM image rom bin spi_rom bin or romzip bin 3 Click the Upload button to upload the new image bin file IMPORTANT To prevent operating system corruption power must not be interrupted during t...

Page 47: ...10 10 10 10 Primary Secondary DNS 0 0 0 0 0 0 0 0 Admin user name admin Admin user password fedsig User 1 User 4 username password blank Factory Support User Enabled To restore configuration to factor...

Page 48: ...tton 1 Remove power from the Informer 2 Press and hold down the RESET button 3 Apply power while holding down the RESET button until the Power and Test LEDs begin to blink confirming that the default...

Page 49: ...local configuration settings before placing the Informer into service 10 Logging Out of the Web Interface Use the Log Out page to log out before the five minute session timer expires To log out of the...

Page 50: ...IP100AC Service Kit IP100 DC Model Includes Assembled front housing driver and amplifier Q IP100DC Service Part Fuse 2 per AC unit Bussman part GDC 3 15A Littlefuse part p 2183 15HXP K148186A 01 Serv...

Page 51: ...er Chime Musical Tone 13 FWS 13967 TM13 5 sec Evac Amplitude Modulated Siren 479 Hz 14 FWS 13968 TM14 5 sec Air Horn Steady Horn 400 Hz and 800 Hz 15 FWS 13969 TM15 5 sec Chime Single Strike Chime Mus...

Page 52: ...c 1 kHz_30 sec 44 FWS 13998 5 sec Alt Steady 5 sec Alt Steady 45 FWS 13999 5 sec Alt Wail 5 sec Alt Wail 46 FWS 14000 5 sec Pulsed Steady 5 sec Pulsed Steady 47 FWS 14001 5 sec Pulsed Wail 5 sec Pulse...

Page 53: ...al Weather Service has issued a high wind warning High winds are approaching Take shelter immediately Repeat the National Weather Service has issued a high wind warning High winds are approaching Take...

Page 54: ...l release take shelter indoors Repeat Chemical release take shelter indoors 79 FWS 14033 Chemical Release Seek Shelter Attention There has been a chemical release in the area Go inside close all windo...

Page 55: ...ing open flames or candles during this outage Public Address 94 FWS 14048 Pre Announcement for Live Broadcast PA Attention Attention Stand by for an emergency announcement Stand by for emergency infor...

Page 56: ...Navy Song Anchors Aweigh 111 FWS 14065 Air Force The Air Force Song 112 FWS 14066 Marine Corp The Marines Hymn 113 FWS 14067 Coast Guard Semper Paratus 114 FWS 14068 Army Song The Army Goes Rolling Al...

Page 57: ...Cover 149 FWS 14103 Emergency Shutdown Emergency Shutdown 150 FWS 14104 Gas Detected Gas Detected 151 FWS 14105 General Alarm 7 short 1 long 30 sec 1 khz General Alarm 7 short 1 long 30 sec 1 khz 152...

Page 58: ...M12 9 sec Westminster Chime Westminster Chime Musical Tone 177 FWS 19253 TM13 180 sec Evac Amplitude Modulated Siren 479Hz 178 FWS 19254 TM14 180 sec Air Horn Steady Horn 400Hz and 800Hz 179 FWS 19255...

Page 59: ...g com FWS Name Customers name for DV Description Notes 194 FWS 19270 TM30 180 sec Attention Extremely Rapid Siren Multiple Frequency 195 FWS 19271 TM31 180 sec Multi Tone Extremely Rapid Siren Multipl...

Page 60: ...2645 Federal Signal Drive University Park Illinois 60484 www fedsig com Customer Support 1 800 344 4634 1 708 534 4756 Technical Support 1 800 755 7621 1 708 587 3587...

Reviews: