8
Model G-SND Sounder
Federal Signal
signaling.fedsig.com
For 24 Vdc operation (remote switching of tones with remote power)
a.
Set the tone selector switch to 0.
b.
Connect the negative (–) power source wire to the terminal block position marked L2 on the PCB.
c.
Connect the positive (+) power source/select wires to the terminal block positions marked T1, T2, T3, and
T4.
d.
Connect the ground wire to the terminal block position marked EARTH.
6.
Insert the PCB into the enclosure and fully tighten the PCB captive screw.
7.
Place the cover on the housing and tighten it by turning it clockwise.
8.
To ensure O-ring compression, the cover must be fully seated against the housing when the threads are tightened.
Turn the M3 set screw on the side of the housing until the screw contacts the housing.
9.
Ensure that the unused wire entry is sealed with the provided brass M20-1.5 x 6 g stopping plug (equipment-
certified).
Table 1 Tone chart
Tone
(Position)
Description
Frequency
Duration
0 (0)
Off
1 (1)
Two Tone
588 Hz
714 Hz
0.25 s
0.25 s
2 (2)
Swept
600 Hz to 700 Hz 0.5 s
3 (3)
Warble
1000 Hz/1400 Hz
Silence
Warble
Silence
0.4 s
0.25 s
0.4 s
0.2 s
4 (4)
Constant
700 Hz 700 Hz
5 (5)
Simulated Bell ~ 3 rings per s
6 (6)
Swept 1
.6 kHz to 1.2 kHz
1.2 kHz to 2.6 kHz
6 cycles per s
7 (7)
Two Tone
1 kHz
700 Hz
0.4 s
0.4 s
8 (8)
700 Hz
700 Hz
Silence
0.25 s
0.25 s
9 (9)
Swept
400 Hz to 1.6 kHz
Constant 1.2 kHz
1.2 kHz to 400 kHz
Silence
1 s
2 s
1 s
0.5 s
10 (A) Swept
500 Hz to 770 Hz 0.5 s
11 (B)
1 KHz
1 KHz
Silence
1 s
1 s
*12 (C) Constant 1 kHz 1 kHz
13 (D) Two Tone
700 Hz
500 Hz
0.5 s
0.5 s
14 (E)
Warble
1 kHz to 1.4 kHz 10 cycles per s
15 (F)
Swept
1.2 kHz 400 Hz
1 s
*Factory setting