background image

 

 

 

e.  A series of DIN rail mount terminal blocks are pro-

vided for field wiring. See Figure 2 for the wiring diagram. These 
terminals are rated as follows:

  (1).  Relay Output: 18-12 AWG (0.75 – 4 mm2), tightening torque 

3.4 in-lb (0.4 N

m), 240VAC, 3.0A max.

  (2).  Aux. Power: 18-12 AWG (0.75 – 4mm2), 240VAC, 20A max.

  (3).  Audio/ISDN: 26-12 AWG (0.25 – 4mm2), Cu conductors only

 

 

 

f.  Upon completion of field wiring, re-fit the cover. 

Secure the M8 screws to ensure weather/dust tightness and hazardous 
location ratings.

Figure 2

  Wiring diagram

290A6743

DATA/POWER LINES
FROM ECHO 
CENTRAL CONTROL 
(ISDN)

LINE VOLTAGE WIRING

(240VAC, 20A MAX.)

(N)

(L)

(N)

(N)

(L)

(L)

RELAY OUTPUT
(240V, 3A MAX.)

AUX. POWER FOR SPEAKER
(240V, 20A MAX.)

AUDIO LINES TO
CONNECTOR CARD T-300CK
ON FS POWERED SPEAKER

-4-