![Federal Signal Corporation 782979229384 Installation And Maintenance Manual Download Page 10](http://html1.mh-extra.com/html/federal-signal-corporation/782979229384/782979229384_installation-and-maintenance-manual_548161010.webp)
10
Installation and Maintenance Instructions
Model 371LED-120 Rotating Light
2.
If you are using conduit side-entries, attach a Myers®
STTTB-2 or a T&B
®
H075TBH 3/4-inch NPT conduit hub
with a 3/4-inch NPT close nipple (both installer-supplied)
to the housing and securely tighten the hub. When side
entries are used, the bottom 1-inch NPT conduit entry must
be plugged with a threaded plug (installer-supplied). (See
“Table 4 Accessories” on page 14.)
3.
Route the supply wires (10 AWG to 16 AWG) into the light
housing.
4.
Strip a maximum of 0.28 inch (7 mm) of insulation from
the ends of the power leads. Connect the wires to the
terminal block by inserting the stripped ends of the wires
into the connectors as far as they can travel.
5.
Tighten the clamping screw. The maximum tightening
torque is 7.0 in-lb (0.8 N
•
m).
6.
Connect the earth ground to the terminal block.
7.