background image

UNDERVOLTAGE ATTACHMENT (Figure 15)

SCREW

The 

 attachment is a continuous duty device,

which can be provided with or without a time delay, and
which mechanically trips the breaker if the voltage drops

 30% to 60% of normal voltage. It is mechanically 

set and has no auxiliary contact in its circuit. The 
voltage time delay mechanism is of the pneumatic delay
type. The time 

 is controlled by the 

 adjusting

screw.

To 

 the 

 attachment, hold the move-

able 

 by hand, close breaker and slowly release

 

 the 

 is fully opened, the spring

loaded plunger will be released, strike the 

 lever and

trip the breaker. Check for missing retaining rings and
loose 

 missing 

 and bolts. Check condition of coil.

If 

 attachment is noisy while being energized,

clean faces of 

 and 

AUXILIARY SWITCH (Figure 16)

 max. 6 stage, 

12 contact 

 is available. It 

mounted on top of the 

 energy mechanism on the

right hand 

 of the breaker and is 

 by the main

 contacts. All contacts are operated by 

 and 

 factory adjusted 

 provide “a” (normally

open) and 

“b" (normally 

closed) contacts.

The position and the condition of all contacts can be see”

and inspected through the transparent dust 

 The

contacts may be changed from a 

 b 

 b to   by

removing the 

 and inverting the contact bridge.

INTERRUPTING CAPACITY

 

 

 

 IN 

 

 

 

SINGLE CONTACT

24

20

15

10

7.5 

230

250

 

 CONTACT

230

250

BELL 

ALARM SWITCH (Figure 

Figure 17

bell 

 switch attachment is mounted on the 

hand side of the breaker and will function only when
breaker is tripped by the 

 trip units. It 

 be

manually and/or electrically reset. Closing of breaker also
resets the 

 switch.

To check the alarm switch attachment, hip breaker with

trip button, the” with shunt trip. In both cases the switch
should not be actuated. Trip breaker by moving the series

trip coil magnet 

 the switch should operate.

Courtesy of NationalSwitchgear.com

Summary of Contents for FUSEMATIC FP25-600

Page 1: ...CIRCUIT BREAKER FM 25400 P A C I F I C E L E C T R I C C O M P A N Y POWER EQUIPMENT SYSTEMS DIVISION INSTRUCTION MANUAL for FUSEMATIC FP25 600 FP501600 FM25 600 FM50 1600 N FP 25 600 FUSEMATIC EDERA...

Page 2: ...1600 I N D E X PAGE G e n e r a l 3 Shipment Receiving Handling Storage _______________ 3 Inspection Installation 3 Maintenance 6 Accessories 7 Overcurrent Trip Devices 9 Wiring Diagram 11 Recommende...

Page 3: ...he Company in aiding the filing of the damage claim When unpacking make all items are removed from the box including packing list instruction book main tenance parts and hardware Report any shortage i...

Page 4: ...touch any of the breaker when the stored energy mechanism is charged close button on front Breaker will close Depress red trip button located in charging handle Breaker will open Recharge stored ener...

Page 5: ...ion rails should be free to in and check rail stops for tightness 4 Rail rollers should be free and well lubricated 5 Main stabs should be tight free of dust and dirt Lubricate with contact grease 6 C...

Page 6: ...re frequent inspections should be made for dirty corrosive or high use applications Reassemble following the reverse of operations and adjust per Figs 10 and 11 In most it is not to replace contacts b...

Page 7: ...mechanism when stored energy mech anism is slowly and that the trip shaft is free It should take no more than 22 inches of torque to trip the breaker GENERAL Make that current carrying parts secured...

Page 8: ...of all contacts can be see and inspected through the transparent dust The contacts may be changed from a b b to by removing the and inverting the contact bridge INTERRUPTING CAPACITY IN SINGLE CONTAC...

Page 9: ...E Open position The plunger s which has been released indicates which fuse s have blown They are reset manually after replacing the blown fuses by pulling the plunger s out as far as they will go and...

Page 10: ...he circuit breaker and be lubricated again It is possible to remove and replace a trip device in the field To Remove a Trip Device The trip units which contained in transparent plastic cases should be...

Page 11: ...rmitting the breaker to be tripped electrically when control power is switched to auxiliary stabs and 6B Motor cut off switch contact bb closes when spring discharges and when spring is fully charged...

Page 12: ...1151 9354 1152 9354 1151 0632 Mounting Ref 1100 6034 Mounting Ref Drawing 1100 6035 Mounting Ref Drawing Mounting Ref Description Moving arcing contacts Upper stud assembly Main Stationary contact as...

Reviews: