background image

PART 6

OVERCURRENT TRIP DEVICES

GENERAL DESCRIPTION

The 

direct acting series coils and magnet assemblies pro-

vide the energy to operate the over-current time delay
device and to trip the circuit breaker, interrupting sustain-

ed 

 and faults. There 

 

 (7) different

coils covering the range from 15 to 1600 amperes.

Each 

 is 

 and calibrated in the factory at the

desired continuous current rating. Any one of the seven
series coils 

 be used in any of the 

 circuit breakers

and FM Fusematic circuit breakers 

 the 

rating dues not exceed the maximum continuous current
rating of the circuit breaker frame. [IE., 

 

 

Dual Magnetic 

Overcurrent Trip Device 

(Figure 18)

The dual magnetic 

 

 device, in combination

with the series coil and magnet, provides inverse long de-
layed tripping for 

 

 below the instantaneous

pickup setting, and adjustable instantaneous tripping. 
devices are factory calibrated and 

 be field adjusted.

Selective Overcurrent Trip Device 

 (Fig. 18)

The selective 

 trip device, in combination with

the series coil and dual 

 magnet, provides inverse

long delayed tripping for all 

 below the short

delay pickup setting, and short delayed tripping for all

 and faults above the short delay pickup set-

ting. 

 devices 

 factory calibrated and can be field

adjusted.

 Phasing Protection (Fig. 

19) 

When fuses are used to protect circuits feeding three phase

motors 

 similar reactive apparatus there is always the

possibility, upon the blowing of 

 fuse only, that the

apparatus, single phased, will bum out. To eliminate this
danger, Fusematic Air Circuit Breakers incorporate three
single phase trip coils, one in parallel with each of the three

main fuses.

The voltage drop 

 a blown fuse energizes the single

phase trip coil in parallel with it.

The trip coils will operate from 630 volts down to 24 volts.
Each coil, when energized, releases a spring loaded plunger
which trips and locks the circuit breaker in the “TRIP
FREE,” (Open) position. The plunger(s) which has been

released indicates which fuse(s) have blown. They are
reset manually, after replacing the blown fuses, by pulling
the plunger(s) out as far as they will go and releasing

them. The reset plunger will remain latched in the “OUT”
position. The circuit breaker should be thoroughly in-
spected after every “Blown Fuse” operation and returned
to service only after the conditions in part 3 Section 1

 II “Inspection and Installation” have been satisfied.

 

 OF OPERATION

A.

Series Coil and Magnet

The current through the series coil provides the 
motive force to energize the magnet assembly. The clapper
type 

 exerts   force on the push rod which

operates the trip unit and trips the circuit breaker. The
current rating of the 

 and magnet may he changed by

moving the pole 

 assembly up 

 down. The trip

system must 

 recalibrated after adjusting the magnet

 face.

B. Dual Magnetic Overcurrent Trip Device 

(TD-1)

(Long Time Delay and Instantaneous Trip)

The 

 delay 

 trip device 

 of 

 dash

 which 

 by the positive displacement of   liquid

   

 

 and 

 adjustable tension coupling

spring which permits the push md to 

 rapidly when

the force 

 the magnet exceeds   predetermined value.

The lever ratio between the push 

 and the dash pot is

adjustable permitting the time delay to be varied. There

 three adjustment bands, identified 

 minimum, inter.

mediate and maximum. In addition to the long delay band

adjustment there is a” adjustable tension spring which

prevents motion of the push rod for currents below the
maximum desired continuous current. This is the long
delay pickup. It is adjustable from 80 percent to 160

percent with calibrated points at 

 

 

 

and 160%.

Courtesy of NationalSwitchgear.com

Summary of Contents for FUSEMATIC FM25-600

Page 1: ...CIRCUIT BREAKER FM 25400 P A C I F I C E L E C T R I C C O M P A N Y POWER EQUIPMENT SYSTEMS DIVISION INSTRUCTION MANUAL for FUSEMATIC FP25 600 FP501600 FM25 600 FM50 1600 N FP 25 600 FUSEMATIC EDERA...

Page 2: ...1600 I N D E X PAGE G e n e r a l 3 Shipment Receiving Handling Storage _______________ 3 Inspection Installation 3 Maintenance 6 Accessories 7 Overcurrent Trip Devices 9 Wiring Diagram 11 Recommende...

Page 3: ...he Company in aiding the filing of the damage claim When unpacking make all items are removed from the box including packing list instruction book main tenance parts and hardware Report any shortage i...

Page 4: ...touch any of the breaker when the stored energy mechanism is charged close button on front Breaker will close Depress red trip button located in charging handle Breaker will open Recharge stored ener...

Page 5: ...ion rails should be free to in and check rail stops for tightness 4 Rail rollers should be free and well lubricated 5 Main stabs should be tight free of dust and dirt Lubricate with contact grease 6 C...

Page 6: ...re frequent inspections should be made for dirty corrosive or high use applications Reassemble following the reverse of operations and adjust per Figs 10 and 11 In most it is not to replace contacts b...

Page 7: ...mechanism when stored energy mech anism is slowly and that the trip shaft is free It should take no more than 22 inches of torque to trip the breaker GENERAL Make that current carrying parts secured...

Page 8: ...of all contacts can be see and inspected through the transparent dust The contacts may be changed from a b b to by removing the and inverting the contact bridge INTERRUPTING CAPACITY IN SINGLE CONTAC...

Page 9: ...E Open position The plunger s which has been released indicates which fuse s have blown They are reset manually after replacing the blown fuses by pulling the plunger s out as far as they will go and...

Page 10: ...he circuit breaker and be lubricated again It is possible to remove and replace a trip device in the field To Remove a Trip Device The trip units which contained in transparent plastic cases should be...

Page 11: ...rmitting the breaker to be tripped electrically when control power is switched to auxiliary stabs and 6B Motor cut off switch contact bb closes when spring discharges and when spring is fully charged...

Page 12: ...1151 9354 1152 9354 1151 0632 Mounting Ref 1100 6034 Mounting Ref Drawing 1100 6035 Mounting Ref Drawing Mounting Ref Description Moving arcing contacts Upper stud assembly Main Stationary contact as...

Reviews: