7 Power
factor
correct or
(PFC)
fault
(a
fault of outdoor
unit) (AP1
hereinafter
refers to the control board of the outdoor unit)
Mainly detect:
Check if the reactor (L) of the outdoor unit and the PFC capacitor are broken
The failure diagnosis process is as follows:
Start
Check wiring of the
reactor (L) of the
outdoor unit and the
PFC capacitor
Whether there is any
damage or
short-circuit?
Replace it as per the
wiring diagram and
reconnect the wires
If the fault is eliminated?
Remove the PFC capacitor
and measure resistance
between the two terminals.
Is the resistance around zero?
The capacitor is
short circuited and
the capacitor
should be replaced
Restart the unit
If the fault is eliminated?
Disconnect the terminals for the
reactor and measure the resistance
between the two terminals of the
reactor by an ohmmeter
Whether there is any damage
or short-circuit?
Replace the reactor
Restart the unit
If the fault is eliminated?
Replace the control
panel AP1
End
Troubleshooting
Summary of Contents for GWH18MC-D3DNA1A/O
Page 17: ...15 5 2 Printed Circuit Board TOP VIEW BOTTOM VIEW Schematic Diagram ...
Page 18: ...16 TOP VIEW BOTTOM VIEW Schematic Diagram ...
Page 34: ...38 8 Exploded Views and Parts List 230V 18K R410A Indoor Unit Exploded Views and Parts list ...
Page 36: ...40 230V 24K R410A Indoor Unit Exploded Views and Parts list ...
Page 38: ...44 Exploded Views and Parts list 230V 18K R410A Outdoor Unit ...
Page 40: ...48 Exploded Views and Parts list 230V 24K R410A Outdoor Unit ...