FeatureComforts MD100TBE Installation & Operation Instructions Download Page 9

9

 WARNING

: If the area in which the heater may be operated is smaller than that defined as 

     an unconfined space or if the building is of unusually tight construction, provide adequate  

     combustion and ventilation air by one of the methods described in the National Fuel Gas   

     Code, ANS Z223.1, Section 5.3 or applicable local codes.

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation

grills or duct. You must provide two 

 

permanent openings: one within 12 inches 

of the ceiling and one within 12 inches of 

the floor. Connect these items directly to the 

outdoors or spaces open to the outdoors. 

These spaces include attics and crawl 

spaces. Follow the National Fuel Gas Code 

NFPA 54/ANS Z223.1. Air for Combustion 

and Ventilation for required size

of ventilation grills or ducts.

Ventilation Air From Inside Building

This fresh air would come from adjoining

unconfined space. When ventilating to an

adjoining unconfined space, you must

provide two permanent openings: one

within 12 inches of the wall connecting

the two spaces (see options 1 and 2,

Fig. 1). You can also remove door into

adjoining room (see option 3, Fig. 1). 

Follow the National Fuel Gas Code 

 

NFPA 54/ANS Z223.1. Air for Combustion 

and Ventilation for required size of 

 

ventilation grills or ducts.

IMPORTANT

: Do not provide openings for

inlet or outlet air into attic if attic has a

thermostat-controlled power vent. Heated

air entering the attic will activate the

power vent. Rework worksheet, adding the

space of the adjoining unconfined space. 

The combined spaces must have enough 

fresh air to supply all appliances in both 

spaces.

Fig. 1 - Ventilation Air from 

Inside Building

Fig. 2 - Ventilation Air from 

Outdoors

 WARNING

: If the area in which the heater may be operated does not meet the required

     volume for indoor combustion air, combustion and ventilation air shall be provided by one

     of the methods described in the NATIONAL FUEL GAS CODE, ANSI Z223.1/NFPA 54, the

     INTERNATIONAL FUEL GAS CODE, or applicable local codes.

Ventilation

Grills

Into Adjoining

Room, 

Option 1

Or

Remove

Door

Into

Adjoining

Room,

Option 3

Ventilation Grills

Into adjoining Room,

Option 2

12 in.

12 in.

Outlet 

Air

Ventilated 

Attic

To Attic

To Crawl 

Space

Outlet 

Air

Inlet 

Air

Inlet Air

Ventilated 

Crawl Space

Summary of Contents for MD100TBE

Page 1: ...y local codes This appliance is for use with the type of gas indicated on the rating plate only This appliance is not convertible for use with other gases This is an unvented gas fired heater It uses...

Page 2: ...0 000 NG 28 000 LP Gas Type Using Natural Gas Using Natural Gas Using Natural Gas Pressure Regulator Setting 4 in W C 4 in W C 4 in W C Inlet Gas Pressure inches of water For purposes of input adjustm...

Page 3: ...LP gases are odorless An odor making agent is added to the gas The odor helps you detect a gas leak However the odor added to the gas can fade Gas may be present even though no odor exists Make certa...

Page 4: ...furniture 8 Always run heater with control knob at 1 2 3 4 5 locked positions Never set control knob between locked positions Poor combustion and higher levels of carbon monoxide may result 9 Do not u...

Page 5: ...d plumber or gas fitter in the Commonwealth of Massachusetts Sellers of unvented propane or natural gas fired supplemental room heaters shall provide to each purchaser a copy of 527 CMR 30 upon sale o...

Page 6: ...se an unvented room heater as the primary heat source PREPARING FOR INSTALLATION Before beginning assembly or operation of the product make sure all parts are present Compare parts with package conten...

Page 7: ...gate input rating of all appliances installed in that space Rooms connecting directly with the space in which the appliances are installed through openings not furnished with doors are considered a pa...

Page 8: ...logs BTU hr Gas water heater 30 000 BTU hr Other gas appliances BTU hr Vent free heater 26 000 BTU hr Total BTU hr Total 56 000 BTU hr Do not include direct vent gas appliances Direct vent draws comb...

Page 9: ...the two spaces see options 1 and 2 Fig 1 You can also remove door into adjoining room see option 3 Fig 1 Follow the National Fuel Gas Code NFPA 54 ANS Z223 1 Air for Combustion and Ventilation for req...

Page 10: ...ties such as tobacco smoke aromatic candles cleaning fluids oil or kerosene lamps etc next to vinyl or cloth wall coverings WARNING Maintain the minimum clearances If you can provide greater clearance...

Page 11: ...bracket from back panel Removing Front Panel of Heater 1 Remove 4 screws 2 screws on each side of the front panel 2 Pull front panel forward 3 Replace front panel when completed using the screws remo...

Page 12: ...ake sure mounting bracket is level WARNING Maintain minimum clearances shown in Fig 3 If you can provide greater clearances from floor and joining wall 2 Mark screw locations on wall see Fig 6 Note Ma...

Page 13: ...g Heater On Mounting Bracket 1 Locate two horizontal slots on back panel of heater see Fig 9 2 Place heater onto mounting bracket Slide horizontal slots onto stand out tabs on mounting bracket Install...

Page 14: ...egulator damage could occur PROPANE MODELS CAUTION Never connect heater directly to the gas supply This heater requires an external regulator not supplied Install the external regulator between the he...

Page 15: ...aps moisture and contaminants This keeps them from going into heater controls If sediment trap is not installed or is installed wrong heater may not run properly Installation of Base Feet Before insta...

Page 16: ...e heater between locked positions 3 Rotate and close cover over gas selection valve and reinstall screw 4 Remove hex plug with wrench provided from natural gas inlet of regulator and install into LP i...

Page 17: ...leaks immediately 6 Reconnect heater and equipment shutoff valve to gas supply Check reconnected fittings for leaks Test Pressures Equal To or Less Than 1 2 PSIG 3 5 kPa 1 Close equipment shutoff valv...

Page 18: ...DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas...

Page 19: ...hooting pages 23 through 25 Also contact a qualified service technician or gas supplier for repairs Until repairs are made light pilot with match If control knob does not pop up when released contact...

Page 20: ...er senses the room temperature At times the room may exceed the set temperature If so the burner will shut off The burner will cycle back on when room temperature drops below the set temperature The c...

Page 21: ...me Pattern with Control Knob Set to High Flame 5 Fig 20 Correct Pilot Flame Pattern Fig 21 Incorrect Pilot Flame Pattern WARNING If yellow tipping occurs your heater could produce increased levels of...

Page 22: ...um cleaner in the blow position If using compressed air in a can please follow the direc tions on the can If you don t follow directions on the can you could damage the pilot assembly 1 Shut off the u...

Page 23: ...ark at ODS pilot 1 Ignitor electrode is positioned wrong Ignitor electrode is broken 2 Ignitor electrode is not connected to ignitor cable 3 Ignitor cable is pinched or wet 4 Broken ignitor cable 5 Ba...

Page 24: ...vice 3 Contact your gas supplier Delayed ignition of burner s 1 Manifold pressure is too low 2 Burner orifice is clogged 1 Contact your gas supplier 2 Clean burner see Care and Maintenance page 22 or...

Page 25: ...r furniture 1 When heated the vapors from furniture polish wax carpet cleaners etc turn into white powder residue 1 Turn heater off when using furniture polish wax carpet cleaner or similar products H...

Page 26: ...r Service or your dealer have ready Your name Your address Model and serial number of your heater How heater was malfunctioning Type of gas used Propane LP or Natural gas NG Purchase date Usually we w...

Page 27: ...100 1 2 ODS Pilot Assembly NDD0308X600 MEDI 1 2 1 Thermocouple ND0803 6 1 2 2 Ignitor Electrode ND0807 1 3 Pressure Regulator RV83FI L S 4 9 1 4 Valve LHY 00 100 1 5 Plug PF120820 2 6 Grill Guard MEL2...

Page 28: ...B3100 1 2 ODS Pilot Assembly NDD0308X800 MED 1 2 1 Thermocouple ND0803 8 1 2 2 Ignitor Electrode ND0807 1 3 Pressure Regulator RV83FI L S 4 9 1 4 Valve LHY 00 1 5 Plug PF120820 2 6 Grill Guard MEL3133...

Page 29: ...EB5100 1 2 ODS Pilot Assembly NDD0308X800 MED 1 2 1 Thermocouple ND0803 8 1 2 2 Ignitor Electrode ND0807 1 3 Pressure Regulator RV83FI L S 4 9 1 4 Valve LHY 00 1 5 Plug PF120820 2 6 Grill Guard MEL513...

Page 30: ...reinstallation are the expressed responsibility of the purchaser Any damage to the product by accident misuse improper installation or by affixing accessories not produced by the manufacturer are the...

Reviews: