63
[Description]
• This parameter sets whether or not to maintain the value
within the limit when the output value increases up to the
limit set value.
Output limit types (Setting range: 0 to 15)
[Setting example] Selecting the operation that outputs 1 and 2 are maintained within the upper and lower limits
Press and hold the
SEL
key for five seconds.
will be displayed on the PV display.
Press the
key to display
.
Press the
SEL
key once.
The current setting ( ) flashes on the SV display.
Press the
or
keys to display .
Press the
SEL
key once. will stop flashing and will be registered for
. After that, the
controller will operate with outputs 1 and 2 maintained within the upper and lower limits.
If you want to display the operation status, press and hold the
SEL
key for two seconds.
Operating procedure
Display
1.
2.
3.
4.
5.
6.
PCUT
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
103%
103%
Limit
Limit
103%
103%
Limit
Limit
103%
103%
Limit
Limit
103%
103%
Limit
Limit
-3%
Limit
-3%
Limit
-3%
Limit
-3%
Limit
-3%
Limit
-3%
Limit
-
3%
Limit
-3%
Limit
103%
103%
103%
103%
103%
103%
103%
103%
Limit
Limit
Limit
Limit
Limit
Limit
Limit
Limit
-3%
-3%
-3%
-3%
Limit
Limit
Limit
Limit
-3%
-3%
-3%
-3%
Limit
Limit
Limit
Limit
Output 1
Output 2
Upper limit
Upper limit
Lower limit
Lower limit
PHC
PLC
103%
Output value
(under the limit)
PHC
PLC
Limit
Breaking the limit
Limit
Breaking the limit
-3%
Output value
(beyond the limit)
www.
.com
1.800.561.8187