Hysteresis range for ON/OFF control (Setting range: 0 to 50%FS)
[Description]
• To select the ON/OFF control (two-position control), set
to 0.0. It is not necessary to set and .
• When the hysteresis range (Range of ON/OFF control) is
too small, the output may switch the ON/OFF frequently.
(This may affect the life of the device to be controlled,
especially when contact output is selected.)
• The unit of the set value of this parameter is
°
C or
°
F
(engineering unit). The setting range varies according to
the measured range of input.
[Setting example] Changing the hysteresis range from 1˚C to 35˚C
Press and hold the
SEL
key for three seconds.
will be displayed on the PV display.
Press the
key to display
.
Press the
SEL
key once.
The current setting ( ) flashes on the SV display.
Press the
or
keys to display
.
Press the
SEL
key once.
will stop flashing and will be registered for
. After that, the
controller will operate with the hysteresis range being 35˚C.
If you want to display the operation status, press and hold the
SEL
key for two seconds.
Operating procedure
Display
1.
2.
3.
4.
5.
6.
[Ex] Input Thermocouple K
: At measured range of 0
to 400
°
C, the setting
range is 0 to 200
°
C.
Resistance bulb
: At measured range of 0
to 150
°
C, the setting
range is 0 to 75
°
C.
Related parameters:
(page 24)
(page 36)