FE PETRO EcoVFC Installation And Owner'S Manual Download Page 16

16

Troubleshooting Guide

To help field service personnel, the EcoVFC can diagnose abnormal operating conditions, and communicate them via the 

display on the front panel. The display indicates the operating status of the controller and, if an alarm is present, displays 

the alarm condition. The following tables show the alarm codes, as well as provide suggested troubleshooting steps.
The EcoVFC is also equipped with a Reset Button to clear faults and a Silence Audible Alarm Button that turns off the 

audible alarm when depressed. Depressing the silence audible alarm button does not clear the fault; it only silences the 

alarm. Pushing and holding the Silence Button will put the Pump Status Display in fault readout mode, showing the last 

3 fault conditions encountered by the EcoVFC, ie. F0 is followed by the code of the last fault encountered, F1 is second 

to last fault encountered, F2 is third to last fault encountered (sequence through the codes by briefly pushing the Silence 

Button after each code is displayed until the Pump Status Display returns to normal status).

Code

Condition

Potential 

Causes

Proposed Action

UL

Under-load, 

Tank Empty 

Incorrect 

horsepower 

setting

Low fuel level in 

the storage tank 
Obstruction on 

intake of PMA  
SW3 Pole 6 set 

incorrectly for 

pump connected

1.   Push reset button on the EcoVFC. 
2.   If condition is corrected, check for proper operation of system; if 

operating correctly do not continue to next step. If condition is still 

present continue to next step. 

3.  Check SW3 Pole 6 setting and verify that it matches the 

horsepower of the pump connected. Connecting VS2 motor with 

a SW3 Pole 6 ON (4hp) setting, may cause this false indication 

when operating in SW1 positions 0 - 6. 

4.  Check fuel level in storage tank; if product level is low schedule 

fuel delivery, when delivery is complete and fuel level is above 

PMA end bell, push reset button on EcoVFC  Check for correct 

system operation.

5.   If condition is not corrected, it is possible that there is an 

obstruction (rag or absorbent pad) on the inlet of the PMA.

LI

Low 

Incoming 

Voltage

Voltage 

fluctuations or 

low input voltage.

1.   Push reset button on the EcoVFC. 
2.   If condition is corrected, check for proper operation of system; if 

operating correctly do not continue to next step. If condition is still 

present continue to next step. 

3.   Use AC voltmeter to verify incoming voltage is within the 360-

440VAC acceptable range. If voltage is not within this range, 

contact an electrician to correct problem. 

LU

Locked Rotor 

fault at PMA 

startup

Foreign material 

in PMA or 

defective PMA.

1.  Push reset button on the EcoVFC. 
2.   If condition is corrected, check for proper operation of system; if 

operating correctly do not continue to next step. If condition is still 

present continue to next step. 

PMA Inspection

3.   Disconnect input voltage at load center, lock and tag circuit 

breakers. 

4.   Remove two 9/16” bolts from extractable portion of the manifold. 

Disengage the 3/4” securing bolt of the electrical connector and 

swing out of the way. 

5.   Pull extractable part of the pump. 

Note:   Pump Motor Assembly shell can be damaged by blows from hard 

surfaces; use care in removing it.

6.   Remove black end cap from PMA and attempt to spin rotor with a 

3/16" Allen wrench to determine if there is any binding. If binding 

or physical damage, continue with next step. If no binding or 

physical damage to the PMA, and it is a new installation, reinstall 

extractable. 

(Continued on next page)

Summary of Contents for EcoVFC

Page 1: ...on and Owner s Manual Eco VARIABLE FREQUENCY CONTROLLER Franklin Fueling Systems 3760 Marsh Rd Madison WI 53718 USA Tel 1 608 838 8786 800 225 9787 Fax 1 608 838 6433 www franklinfueling com 2016 FFS...

Page 2: ...ult in serious fire or explosion Before entering a containment sump check for the presence of hydrocarbon vapors If hydrocarbon vapors are at unsafe levels ventilate the sump with fresh air re check t...

Page 3: ...compatible with competitive makes of variable speed models The EcoVFC is compatible with the IST VFC for communication in Master Slave configurations only if the EcoVFC has software revision 1 18 or...

Page 4: ...nd hold button and the Pump status display will show the last 3 fault conditions the EcoVFC encountered Reset Button Resets controller of any fault condition Communications LED Used in Master Slave ty...

Page 5: ...08mm2 14 AWG 75 meters 250 feet 4 Replace the cover of the pump junction box and securely tighten in place The compression seal is not a replacement for the vapor explosion seals required by the NEC...

Page 6: ...phase power only If 200 250V 50 Hz Single Phase power supply is only available the EcoVFC must be replaced with the FE Petro MagVFC which will olny be capable of driving a PMA VS2 in this application...

Page 7: ...le EcoVFC controllers working together See Alternating Circuit Control section for details default is OFF Note Not functional in IST VFC Compatibility Mode set with SW2 Pole 5 per Table 1A SW6 Pole 1...

Page 8: ...ther EcoVFC s Because of enhanced communication protocols the EcoVFC is not capable of communication with the IST VFC unless SW6 Pole 3 IST VFC Compatibility Mode is switched ON IST VFC Compatibility...

Page 9: ...laves s SW3 pole 3 OFF and set SW2 switches per Table 1A Line leak detection performance can be affected when using multiple EcoVFCs FE Petro does not recommend using the Alternating Circuit feature i...

Page 10: ...set connect the signal from the dispenser hook to the terminals of the Master EcoVFC only The Master controller will energize the Slave s when needed without a signal from the dispenser 19 When all co...

Page 11: ...le 2 Summary of Master Slave 30 minute Alternating Setup Software version 1 24 or higher Below is a table summarizing the SW3 and SW6 settings to enable the EcoVFC to alternate active pumps every 30 m...

Page 12: ...ch locations Example For a Master controller with a 20 000 gallon tank when set to address 20 the pump will run for 30 minutes For a Slave controller with a 12 000 gallon tank when set to address 12 t...

Page 13: ...SW3 3 O N 1 2 6 4 5 7 SW6 O N 1 6 2 4 3 5 8 7 SW3 6 SW6 O N 2 1 3 4 5 7 8 6 O N 2 1 3 4 5 7 8 SW2 SW6 position 5 ON SW6 position 4 ON SW3 position 8 ON Set according to Table 3 Each controller address...

Page 14: ...sition Pressure 0 1 7 bar 24 psi 1 1 8 bar 26 psi 2 1 9 bar 28 psi 3 2 1 bar 30 psi 4 2 2 bar 32 psi 5 2 3 bar 34 psi 6 2 5 bar 36 psi 7 2 8 bar 38 psi 8 2 9 bar 40 psi 9 42 psi Table 4 SW1 Settings T...

Page 15: ...the revision xx yy Note If the display stops on yy there may be an issue of low incoming voltage or loose input power connections Immediately after the EcoVFC has been reset or turned ON Pr NN Pressur...

Page 16: ...Pole 6 ON 4hp setting may cause this false indication when operating in SW1 positions 0 6 4 Check fuel level in storage tank if product level is low schedule fuel delivery when delivery is complete a...

Page 17: ...or submersible wiring in the beginning of this manual Code Condition Potential Causes Proposed Action Er Extended Run Continuous hook signal applied for greater than 60 minutes without change in pumpi...

Page 18: ...results e g Black to red 2 ohms Readings between any of the three motor control wires and ground should be an open circuit If readings in this step are incorrect go to Step 7 if readings are correct c...

Page 19: ...lacement in 3 flashes section if readings are correct there is problem with the wiring between the EcoVFC and this point 7 Remove the junction box cover and do conductivity test on wires from junction...

Page 20: ...llasted in water 8 Remove four 5 16 cap screws that connect the PMA with Allen wrench and remove the PMA from the motor discharge head Note Prior to mounting a new PMA check lead assembly wires inside...

Page 21: ...ly TO MOTOR TO LINE GND ORG RED BLK GND L1 L2 L3 N 1 9 0 Switches located on user interface panel SW1 3 4 2 SW2 5 6 7 8 2 1 5 4 3 SW3 3 2 1 6 5 4 8 7 SW6 1 4 3 2 7 6 5 8 Switch Handle Dispenser RETURN...

Page 22: ...e only TO MOTOR TO LINE L3 N L2 L1 GND BLK RED ORG GND 5 SW1 0 3 2 7 4 6 1 9 8 O N SW2 1 2 3 5 4 0 1 2 3 4 5 6 7 8 9 SW3 SW2 1 J23 1 2 3 4 TO LINE USER INTERFACE PANEL 8 O N SW3 3 2 1 5 4 7 6 O N SW6...

Page 23: ...ion instructions for further details Wiring must conform to all federal state and local codes Control panels are for non hazardous indoor use only TO MOTOR TO LINE L3 L2 L1 GND BLK RED ORG GND 5 SW1 0...

Page 24: ...uctions for further details Wiring must conform to all federal state and local codes Control panels are for non hazardous indoor use only TO MOTOR TO LINE L3 L2 L1 GND BLK RED ORG GND 5 SW1 0 3 2 7 4...

Page 25: ...de 2 1 1 2 3 4 5 6 7 5 4 3 SW3 O N 1 9 0 SW1 3 4 2 SW2 5 6 7 8 2 1 5 4 3 SW3 3 2 1 6 5 4 8 7 SW6 1 4 3 2 7 6 5 8 O N O N O N On IST VFC Mode Off 2HP Motor Not used Not used in IST VFC mode Not used in...

Page 26: ...2016FFS 228001102 Rev 10...

Reviews: