FE PETRO EcoVFC Installation And Owner'S Manual Download Page 14

14

EcoVFC SITE SET UP 

 20.  Verify rotary switch on 

Eco

VFC is set to 

position 4. This will provide approximately 2.2 bar 

(32 psi) output from the IST or STP units with VS2 

or VS4 suffix, and serves as a good starting point 

for 

Eco

VFC calibration.

 21.  Using a 19 liter (5 gallon) capacity minimum 

approved container, go to the dispenser closest 

to the storage tank and perform a Flow Rate Test. 

If the product being pumped is gasoline, consider 

following the U.S. EPA Fuel Dispenser Flow Rate 

Test Procedure for 38 LPM (10 GPM) maximum 

flow rate standard, where applicable. 

Note:

  It is necessary to perform a Flow Rate Test for each 

product available at the dispenser. This will confirm 

that all product outputs, including products blended 

at the dispenser, do not exceed the U.S. EPA 38 

LPM (10 GPM) maximum, where applicable.

Note

:  Use of “flow restrictors” to control a maximum flow 

rate of 38 LPM (10 gpm) per nozzle (as required 

by the U.S. EPA) are not required if the variable 

frequency controller is properly calibrated as 

defined in “

Eco

VFC Site set up Section” section.

 22.  If output is above or below the desired range (i.e. 

30 -38 LPM or 8-10 GPM), turn off the pump at the 

power supply, (wait one minute after LED display 

blanks before opening the cover) remove the 

Eco

VFC cover, and adjust the rotary switch (SW1), 

see Figure 2. This switch will increase or decrease 

the system operating pressure according to Table 

4. An increase in pressure will normally yield an 

increase in flow rate; a decrease in pressure will 

reduce flow rate. Replace the 

Eco

VFC cover and 

re-apply input voltage. Return to Step 21 above 

and check LPM (GPM) with the new settings. 

Repeat until the output obtained is within the 

desired range in LPM (GPM).

Switch 

Position

Pressure

0

1.7 bar (24 psi)

1

1.8 bar (26 psi)

2

1.9 bar (28 psi)

3

2.1 bar (30 psi)

4

2.2 bar (32 psi)

5

2.3 bar (34 psi)

6

2.5 bar (36 psi)

7

2.8 bar (38 psi)

8

2.9 bar (40 psi)

9

42 psi

 

Table 4: SW1 Settings

To avoid the risk of potentially lethal 

electrical shock, explosion or fire, 

always tag and lock circuit breakers 

in the off position before removing the 

cover of the EcoVFC.
After disconnecting power to the 

EcoVFC, wait one minute after LED 

display blanks before opening the 

cover for servicing. Voltage stored 

in the capacitor bank of the EcoVFC 

presents a risk of potentially lethal 

electrical shock even after power is 

disconnected.

Note:  Additives in gasoline can change the specific 

gravity of gasoline, which may cause the pressures 

stated in the above Table 4 to vary.

 23.  Optimize Pipe Compensation settings by doing 

another Flow Rate Test; this time with two other 

nozzles from the same product open at the same 

time as your test nozzle. If the flow rate at the 

test nozzle falls from the desired range with three 

nozzles open, increase SW3 pole 4 and pole 5 to 

the next highest compensation setting (0 to 1 or 

1 to 2 for example). If output exceeds the desired 

range, decrease to the next lowest compensation 

setting (2 to 1 or 1 to 0 for example). Repeat this 

step until compensation setting is optimal for your 

installation. Factory setting is zero.

SW3 pole 4 and pole 5

Compensation

SW 3 

Pole 4

SW3 

Pole 5

Piping 

Configuration

0

on

on

least restrictive

1

on

off

...

2

off

on

...

3

off

off

most restrictive

 

Table 5

Note

:  An example of a small restriction piping system 

would be 2" fiberglass running less than 45m 

(150'). An example of a restrictive piping system 

would be 1 ½" convoluted flexible piping greater 

than 23m (75') in length.

Note

:  When working with a Master-Slave or Master-

Slave/Alternating Circuit configuration, the piping 

compensation must be identical in all controllers.

Factory Setting

>

Warning

Warning

Summary of Contents for EcoVFC

Page 1: ...on and Owner s Manual Eco VARIABLE FREQUENCY CONTROLLER Franklin Fueling Systems 3760 Marsh Rd Madison WI 53718 USA Tel 1 608 838 8786 800 225 9787 Fax 1 608 838 6433 www franklinfueling com 2016 FFS...

Page 2: ...ult in serious fire or explosion Before entering a containment sump check for the presence of hydrocarbon vapors If hydrocarbon vapors are at unsafe levels ventilate the sump with fresh air re check t...

Page 3: ...compatible with competitive makes of variable speed models The EcoVFC is compatible with the IST VFC for communication in Master Slave configurations only if the EcoVFC has software revision 1 18 or...

Page 4: ...nd hold button and the Pump status display will show the last 3 fault conditions the EcoVFC encountered Reset Button Resets controller of any fault condition Communications LED Used in Master Slave ty...

Page 5: ...08mm2 14 AWG 75 meters 250 feet 4 Replace the cover of the pump junction box and securely tighten in place The compression seal is not a replacement for the vapor explosion seals required by the NEC...

Page 6: ...phase power only If 200 250V 50 Hz Single Phase power supply is only available the EcoVFC must be replaced with the FE Petro MagVFC which will olny be capable of driving a PMA VS2 in this application...

Page 7: ...le EcoVFC controllers working together See Alternating Circuit Control section for details default is OFF Note Not functional in IST VFC Compatibility Mode set with SW2 Pole 5 per Table 1A SW6 Pole 1...

Page 8: ...ther EcoVFC s Because of enhanced communication protocols the EcoVFC is not capable of communication with the IST VFC unless SW6 Pole 3 IST VFC Compatibility Mode is switched ON IST VFC Compatibility...

Page 9: ...laves s SW3 pole 3 OFF and set SW2 switches per Table 1A Line leak detection performance can be affected when using multiple EcoVFCs FE Petro does not recommend using the Alternating Circuit feature i...

Page 10: ...set connect the signal from the dispenser hook to the terminals of the Master EcoVFC only The Master controller will energize the Slave s when needed without a signal from the dispenser 19 When all co...

Page 11: ...le 2 Summary of Master Slave 30 minute Alternating Setup Software version 1 24 or higher Below is a table summarizing the SW3 and SW6 settings to enable the EcoVFC to alternate active pumps every 30 m...

Page 12: ...ch locations Example For a Master controller with a 20 000 gallon tank when set to address 20 the pump will run for 30 minutes For a Slave controller with a 12 000 gallon tank when set to address 12 t...

Page 13: ...SW3 3 O N 1 2 6 4 5 7 SW6 O N 1 6 2 4 3 5 8 7 SW3 6 SW6 O N 2 1 3 4 5 7 8 6 O N 2 1 3 4 5 7 8 SW2 SW6 position 5 ON SW6 position 4 ON SW3 position 8 ON Set according to Table 3 Each controller address...

Page 14: ...sition Pressure 0 1 7 bar 24 psi 1 1 8 bar 26 psi 2 1 9 bar 28 psi 3 2 1 bar 30 psi 4 2 2 bar 32 psi 5 2 3 bar 34 psi 6 2 5 bar 36 psi 7 2 8 bar 38 psi 8 2 9 bar 40 psi 9 42 psi Table 4 SW1 Settings T...

Page 15: ...the revision xx yy Note If the display stops on yy there may be an issue of low incoming voltage or loose input power connections Immediately after the EcoVFC has been reset or turned ON Pr NN Pressur...

Page 16: ...Pole 6 ON 4hp setting may cause this false indication when operating in SW1 positions 0 6 4 Check fuel level in storage tank if product level is low schedule fuel delivery when delivery is complete a...

Page 17: ...or submersible wiring in the beginning of this manual Code Condition Potential Causes Proposed Action Er Extended Run Continuous hook signal applied for greater than 60 minutes without change in pumpi...

Page 18: ...results e g Black to red 2 ohms Readings between any of the three motor control wires and ground should be an open circuit If readings in this step are incorrect go to Step 7 if readings are correct c...

Page 19: ...lacement in 3 flashes section if readings are correct there is problem with the wiring between the EcoVFC and this point 7 Remove the junction box cover and do conductivity test on wires from junction...

Page 20: ...llasted in water 8 Remove four 5 16 cap screws that connect the PMA with Allen wrench and remove the PMA from the motor discharge head Note Prior to mounting a new PMA check lead assembly wires inside...

Page 21: ...ly TO MOTOR TO LINE GND ORG RED BLK GND L1 L2 L3 N 1 9 0 Switches located on user interface panel SW1 3 4 2 SW2 5 6 7 8 2 1 5 4 3 SW3 3 2 1 6 5 4 8 7 SW6 1 4 3 2 7 6 5 8 Switch Handle Dispenser RETURN...

Page 22: ...e only TO MOTOR TO LINE L3 N L2 L1 GND BLK RED ORG GND 5 SW1 0 3 2 7 4 6 1 9 8 O N SW2 1 2 3 5 4 0 1 2 3 4 5 6 7 8 9 SW3 SW2 1 J23 1 2 3 4 TO LINE USER INTERFACE PANEL 8 O N SW3 3 2 1 5 4 7 6 O N SW6...

Page 23: ...ion instructions for further details Wiring must conform to all federal state and local codes Control panels are for non hazardous indoor use only TO MOTOR TO LINE L3 L2 L1 GND BLK RED ORG GND 5 SW1 0...

Page 24: ...uctions for further details Wiring must conform to all federal state and local codes Control panels are for non hazardous indoor use only TO MOTOR TO LINE L3 L2 L1 GND BLK RED ORG GND 5 SW1 0 3 2 7 4...

Page 25: ...de 2 1 1 2 3 4 5 6 7 5 4 3 SW3 O N 1 9 0 SW1 3 4 2 SW2 5 6 7 8 2 1 5 4 3 SW3 3 2 1 6 5 4 8 7 SW6 1 4 3 2 7 6 5 8 O N O N O N On IST VFC Mode Off 2HP Motor Not used Not used in IST VFC mode Not used in...

Page 26: ...2016FFS 228001102 Rev 10...

Reviews: