Fcontrol FXDM series Quick Start Manual Download Page 4

2.3

Work on the device

Information

Mounting, electrical connection, and start-up operation may only be carried out by an electrical 
specialist in accordance with electrotechnical regulations (e.g. EN 50110 or EN 60204)!

Danger due to electric current

It is generally forbidden to carry out work on electrical live parts. Protection class of the device when 
open is IP00! It is possible to touch hazardous voltages directly.

The safe isolation from the supply must be checked using a 

two-pole

 voltage detector. 

Even after disconnecting the mains voltage, life-threatening charges can appear between the 
protective ground 

PE

 and the mains connection. 

The protective earth is conducting high discharge currents (dependent on the switching frequency, 
current-source voltage and motor capacity). Earthing in compliance with EN speci

cations shall 

therefore be observed even for testing and trial conditions (EN 50 178, Art. 5.2.11). Without 
earthing, dangerous voltages can be present on the motor housing. 

Waiting period at least 3 minutes!

Through use of capacitors, danger of death exists even after switching off the device through 
directly touching the energized parts or due to parts that have become energized due to faults.

It is only permitted to remove the housing cover after waiting for 3 minutes once the line supply 
cable has been shut down. Should measurement or adjustment work be unavoidable on the opened 
unit while still powered, then this may only be performed by quali

ed personnel acquainted with the 

thereby associated hazards.

Attention!

Even after switching off, dangerous temperatures can still occur in and on the device.

Attention!

Automatically restart after a power failure or mains disconnection!

3

Product overview

3.1

Application

The frequency inverter is designed for a stepless control of fans without additional (electromagnetic) 
motor noise.   
Only suitable for drives with low set-off torque (e.g.: fans or pumps).

3.2

Functional description

The frequency inverters of these series generate their 3~ output with variable voltage and frequency 
from the three-phase mains on the input.
The devices are constructed in accordance with the general requirement in EN 61800-2 for adjustable 
speed electrical power systems and is intended for one-quadrantdrives.

Information

By using the integrated all-pole effective Sine 

lter (phase to phase and phase to ground), an absolute 

parallel control of fans without risk of damage for motors is possible. Screened motor cables are not 
required!

Quick Start Guide 

Fcontrol

 

 model series FXDM

Product overview

L-BAL-E223-GB 1623 Index 003

Part.-No. 00153236

4/22

Summary of Contents for FXDM series

Page 1: ...egrated sine lter for 3 fans Quick Start Guide Detailed Description on www ziehl abegg com Software version D1333A from Version 2 37 L BAL E223 GB 1623 Index 003 Part No 00153236 english CZ D DK E F F...

Page 2: ...up 12 6 1 Jumper for the input signal 12 6 1 1 External Setpoint External speed setting in manual operation 12 6 2 Select operation mode 13 7 Start up 14 7 1 Prerequisites for commissioning 14 7 2 Pro...

Page 3: ...ety instructions 2 1 Intended use The equipment is to be used solely for the purposes speci ed and con rmed in the order Any other use above and beyond this is considered not for the intended purpose...

Page 4: ...ue to faults It is only permitted to remove the housing cover after waiting for 3 minutes once the line supply cable has been shut down Should measurement or adjustment work be unavoidable on the open...

Page 5: ...ssible shipping damage Start up is not allowed in the case of transport damage At a weight greater than 25 kg for men 10 kg for women the device should be lifted out by two persons according to REFA T...

Page 6: ...ondingly larger clear ance or thermal shielding is required 4 3 Fastening the device The type of fastening and the number of fastening points are dependent on the housing design All the fastening poin...

Page 7: ...ning at 8 points GM00002A_M 15 12 2015 1 7 2 3 4 5 6 8 Drill 8 fastening points Screw in fastening point screws 1 4 up to a distance of approx 5 mm and mount the device Tighten fastening point screws...

Page 8: ...cable inlet for cable glands Metal sheet housings are supplied with stoppers Any cable ducts openings not used must be sealed Strip and insert the cables properly Attach cover for terminal compartment...

Page 9: ...ective ground must be made double in accordance with EN 50178 Point 5 2 11and 5 3 2 1 up to a cross section of at least 10 mm For an installation of r c d protection it shall be observed that this mus...

Page 10: ...erminals TB TP have to be bridged Motor fault Motor fault When a connected thermostat or thermistor responds interruption between the two terminals TB TP the device switches off and does not switch ba...

Page 11: ...selection Mode GND A D B D RS 485 MODBUS Interface for networking via MODBUS RTU A D must always be connected to A D of the next devices the same applies to B D In addition a GND connection must be e...

Page 12: ...guration in base setup For Potentiometer Analog Out1 terminal A program to function 1A 10 V like factory setting see IO Setup If a second sensor is connected at input 2 external Setpoint or speed sett...

Page 13: ...02 Sensor TF E2 Temperature control depending on outdoor temperature preset set point 5 0 C P band 20 0 K 2 03 Sensor TF E1 Temperature control with additional functions shutter and heating 2 04 1x S...

Page 14: ...5 Menu group Start Set the menu language if necessary factory setting English Language GB 6 Menu group Base setup Setting the desired operation Mode factory setting 1 01 Speed controller see Selectio...

Page 15: ...MotorRa tedVolt OTM 00010 56 11 GB Lan guage 8 W Input power 0 0 Hz Min Speed 2 ext Fault OFF E2 Func tion OFF Save User Setup 10 0 V A max Level max 48 5 Hz Edgefre quency 585 V DC Voltage OFF Reset...

Page 16: ...3 gures display unit etc 12 Text line 16 gures display text menu P Program key and open menu Menu selection reduce value Menu selection increase value ESC key combination Escape leave menu 8 2 Menu op...

Page 17: ...In order to simplify the initial start up operation the service level is enabled at rst I e not protected by the PIN 0010 see Controller Setup PIN protection OFF If PIN protection is activated ON the...

Page 18: ...6 8 7 54 FXDM14M 308143 14 13 5 12 3 40 16 310 54 6 8 5 54 FXDM18AM 308174 18 16 7 15 5 40 20 400 9 1 54 FXDM18M 308173 18 16 7 15 5 40 20 400 8 9 54 FXDM22AM 308108 22 19 2 17 7 40 25 520 14 5 54 FX...

Page 19: ...for 4 20 mA input Ri 100 Voltage supply e g for sensors 24 V 20 Imax 120 mA for connection to an external AXG terminal minus approx 50 mA Output 0 10 V Imax 10 mA short circuit proof Digital inputs D...

Page 20: ...issible temperature for the rated current at rated voltage is speci ed as rated temperature Since the dissipation of the power loss heat development in the device is decisively dependent on the ambien...

Page 21: ...Normal 7 M 3 U V W PE TB Y q 3 Motor mit eingebauten Thermostatschaltern with internal thermostats 3 TB C 24V GND MODBUS RS 485 GND 24 V A D B D A D GND Terminal AXG 1A E B D 1 Line 3 208 480 V 50 60...

Page 22: ...technical support for control systems ventilation technology phone 49 0 7940 16 800 Email fan controls service ziehl abegg de Our worldwide contacts are available in our subsidiaries for deliveries ou...

Reviews: