Detection / Activation
No manual adjustments are required for most settings. Default beam’s effective range is
65 – 70 cm.
The factory setting should be satisfactory for most installations.
Range Adjustment
If the range is too short or too long, it can be adjusted.
1. Using a phillips screw driver remove the stainless steel cover plate by
unscrewing the screw from the bottom of the plate.
2. Ensure both cables are connected.
3. Press the black push button three time (x3) unitl the sensor red LED flashes.
4. Place a target sensor view at a desired distance for 30 seconds. The LED will
stay on for 5 seconds before flashing twice indicating distance set.
Water Flow Time Adjustment
Default water flow delivery is 8 seconds.
1. Press te black push button 5 times (x5) unit the red LED stays on. The valve will
open, flushing once to indicate ready for timing adjustment.
2. Within 10 seconds, press the black push once for 6 seconds delivery, push twice
for 8 seconds, 3 times for 10 seconds delivery, 4 times for 12 seonds delivery.
Solenoid Valve Maintenance