Installation
40
Wiring with several Motion Control Systems in RS232 network operation
Fig. 28: Wiring with several Motion Control Systems in RS232 network operation
Connection to the CANopen network
Fig. 29: Connection to the CANopen network
Depending on the number of networked controllers a smaller value may be necessary
for the pull-down resistor.
If the CAN wiring is not laid in a straight line it may be necessary to individually opti-
mise the amount and location of the terminating resistors. For instance in a star net-
work a central 60 Ohm terminating resistor may be more suitable. When the optimum
arrangement of terminating resistors is fitted, no accumulation of error frames should
be evident.
P
C
or
High Level
C
ontrol
4,7k
Node 1
Node n
TxD
TxD
RxD
RxD
RxD
TxD
GND
GND
GND
(D-
S
ub9 Pin 2)
(D-
S
ub9 Pin 3)
(D-
S
ub9 Pin 5)
Node 1
C
AN Bus Line
Node n
GND
C
AN_H
C
AN_L
120
120