FATEK P5043S Installation Manual Download Page 4

3. Specifications 

Model 

P5043S 

P5043N 

UL 61010-1 

Technical 

Considera on

 

Type of item tested   

Control 

Product Descrip on Operator 

Panel 

Connec ons to mains 

supply  

Permanent 

Overvoltage category   

II 

Pollu on degree   

Means of Protec on  

Class III 

Environmental condi ons  

Opera ng Temp. 0~50°C 

Storage Temp. -20 ~ 60°C 

For use in wet loca ons  

No 

Equipment mobility   

Built in 

Opera ng condi ons  

Con nuous 

Overall size 

128.0 x 102.0 x 38.1 (mm) 

Weight 

215 (g) 

235 (g) 

Marked degree of 

protec on 

Front panel: IP65 / Rear Case: IP20 to IEC 60529 

Type 1 to UL 50E  

Equipment classi

fi

ca on 

Industrial, Professional, Commercial 

Equipment class 

Class III 

Equipment type 

Permanently connected, Fixed 

I/O Port 

Serial 1 

Connector: D-Sub 9-Pin 

COM1: RS-232 (TXD, RXD) 

COM2: RS-422/485 

COM3: RS-485 

Serial 2 

--- 

LAN 

--- 

10M/100M

 

USB 

USB2.0 Type-A (Host)x1 

USB2.0 Type mini-B (Device)x1 

Micro SD 

--- 

Audio

 

--- 

PLC Extension

 

---

 

Termina on 

Switch 

Yes (For RS-422/485) 

Power 

Power Input 

24VDC

±

20% 

Consump on 350mA@24VDC 

Insula on 50M

Ω

 at 500VDC 

Environment 

Rela ve Humidity 

10%~90%@ 40°C (non-condensing) 

Withstand Voltage

 

AC500V/20mA/1 Min. (between charger & FG terminals) 

Vibra on

 

5 to 9Hz Half-amplitude: 3.5mm 

9 to 150 Hz Constant accelera on: 19.6m/s2 (2G) 

3 direc ons of X, Y, Z: 10 mes (IEC61131-2 complaints) 

Noise Suppression

 

1000Vp-p, width 1us, rising  me 1ns 

Grounding Resistance

 

Below 100

Ω

 

Dimension 

Cut-out 118.5 

92.5 

(mm) 

Summary of Contents for P5043S

Page 1: ...is damaged avoid contact with the leaked liquid crystal If the liquid crystal spills on clothing or skin use soap and wash off thoroughly In case of eye contact the liquid hold the eye open flush with...

Page 2: ...ase contact our sales department Do not use the output signal of the device as any safety function or system emergency stop It may result in personal injury or equipment damage if a malfunction of the...

Page 3: ...es and Dimensions Power Indicator Light Mounting Hole Power Connector COM2 COM3 Termination Switch COM1 COM2 COM3 DB 9 Male Connector USB Connector Mini USB Connector Ethernet RJ45 Connector for N mod...

Page 4: ...al Professional Commercial Equipment class Class III Equipment type Permanently connected Fixed I O Port Serial 1 Connector D Sub 9 Pin COM1 RS 232 TXD RXD COM2 RS 422 485 COM3 RS 485 Serial 2 LAN 10M...

Page 5: ...ut until the waterproof ring contacts the plate Insert a hook into each mounting hole on the HMI and then tighten the screws evenly with a moderate torque Failure to tighten the screws may cause the H...

Page 6: ...sistor switch To enable or disable the termination resistor please follow the configuration shown in the table below The termination switch is for COM2 RS 422 RS 485 and COM3 RS 485 Configuration of T...

Page 7: ...TX NC NC NC 4 NC RX NC NC 5 GND GND GND GND 6 NC TX DATA NC 7 NC NC NC DATA 8 NC NC NC DATA 9 NC RX NC NC 1 NC No Connection 26FL NO 29 SEC 2 JUNGJENG E RD DANSHUEI DIST NEW TAIPEI CITY 25170 TAIWAN...