Farris Engineering 1890 Series Maintenance Manual Download Page 8

WATER - Before starting the seat tightness test, the outlet
body bowl shall be filled with water, and the valve shall be
allowed to stabilize with no visible flow from the valve out-
let. The valve shall be observed for 1 minute at the test
pressure. There shall be no visible leakage at the valve
outlet.

Soft Seated Valves:

Soft seated valves shall be tested at 95% of set pressure
when set above 100 psig; they shall be tested at 5 psig
below set pressure when the set pressure is less than or
equal to 100 psig.

AIR - There shall be no leakage (zero bubbles) using the
test method outlined above.

STEAM and WATER - There shall be no visible leakage at
the valve outlet.

2. If any valve fails to meet leakage requirements, it shall

be reworked.

3. Assemble appropriate cap construction after leak tight-

ness has been verified. If valve type is open lever, no
back pressure test is required. Plain cap and packed
lever valves must be back pressure tested as outlined
in the next section.

BACK PRESSURE TEST

1. This test applies to all valves designed for discharge to

a closed system (plain or packed lever cap construc-
tion) with inlet sizes larger than 1 nps.

2. The secondary pressure zone of the valve shall be test-

ed with air or other suitable gas at a pressure of at least
30 psi. The valve should be pressurized at the outlet
with shop air or other means. A soap solution or other
suitable solution shall be applied to all connections
which are potential leakage paths (i.e., body/bonnet
connection, cap/bonnet connection, packed lever
assembly/cap connection). No leakage is acceptable.

3. If leakage is detected at any location, the valve shall be

reworked.

6. Setting & Testing

TESTING AND SETTING PROCEDURE

1. Mount the valve on the test stand. Use air as the test

medium for air, gas and vapor or flashing service appli-
cations. Set valves for saturated steam service on satu-
rated steam. Valves for steam service set with air
should include temperature compensation. The name-
plate provides “Cold Differential Test Pressure.” Set
valves for liquid service on water.

2. Hold the stem tightly and tighten (turn clockwise) the

spring adjusting screw to increase the spring force.
Make sure the stem does not rotate while loading the
spring.

3. Slowly raise the test drum pressure and observe the

opening point. The set pressure on air or steam is the
“pop point” while on water it is the first continuous flow.

4. If necessary reduce the test drum pressure and adjust

the spring adjusting screw. Repeat this until the valve
opens at the required pressure, designated as “Cold
Differential Test Pressure.” At the desired setting, torque
the jam nut to 25 ft. lbs. and assemble cap and gasket
for tightness testing. Check set point once more after
locking jam nut.

Never adjust the spring setting when the pressure
under the valve is near its popping point, as the body
seat and disc seat might score and/or gall. Always
lower the pressure in the valve at least 25 percent
below popping pressure before making adjustments.
This will put a loading on the seat surfaces, and pre-
vent rotation and damage.

SEAT TIGHTNESS TESTING

WARNING:

The valve must be checked for seat leak-

age after the set pressure has been checked. Excessive
leakage could lead to fouled or inoperable valves, serious
product loss and could be hazardous to personnel and
equipment.

1. The valve can be tested for tightness on the test stand

by increasing vessel pressure to the required test pres-
sure and observing the valve outlet for evidence of
leakage. The following is an overview of the test proce-
dures used.

Metal Seated Valves:

Metal seated valves shall be tested at 90% of set pressure
when the set pressure is greater than 50 psig; they shall
be tested at 5 psig below set pressure when the set pres-
sure is less than or equal to 50 psig.

AIR - A 5/16 O.D. x 0.035 wall thickness copper tube or
equivalent immersed no more than 1/2 deep in water shall
be connected to the valve outlet. See Figure 6.1. Seal all
other potential leakage paths with suitable fixtures (i.e.,
cap, plugs) so that seat leakage can be detected at the
outlet. Before starting the bubble count, test pressure shall
be applied for a minimum of 1 minute. The valve shall then
be observed for leakage for at least 1 minute. The leakage
rate shall not exceed 40 bubbles per minute.

STEAM - Test pressure shall be applied for 3 minutes
before the seat tightness test. The valve shall be observed
for leakage for at least 1 minute. There shall be no visible
or audible leakage at the valve outlet.

7

!

Visit www.boighill.com to request a quote.

Visit www.boighill.com to request a quote.

Summary of Contents for 1890 Series

Page 1: ...cal Manual 296T Series 1890 2850 Maintenance Manual Farris Engineering Division of Curtiss Wright Flow Control Corporation Visit www boighill com to request a quote Visit www boighill com to request a...

Page 2: ...w trained maintenance personnel to properly repair types 1890 1892 2850 and 2852 pressure relief valves All of the assembly and disassembly instructions refer to types with plain screwed caps When rep...

Page 3: ...during disassembly split rings may fall free Current valves do not use a stem shoulder and split ring The stem shoulder is an integral part of the stem 10 Lift the stem with the disc attached If desi...

Page 4: ...s Engineering Division of Curtiss Wright Flow Control Corporation Bill of Materials Item Part Name Material 1890 1892 1890 S4 1892 S4 SA 479 Type 316 SA 479 Type 316 1 Body St St St St SA 216 Gr SA 35...

Page 5: ...jam nut and stem test washer 4 Reassemble in reverse order making sure the camshaft lobe is pointing down The stem test washer should be adjusted to ensure the cam will make contact with the stem tes...

Page 6: ...ATES PART NO MAT CODE SIZE THICKNESS 7688 164 1 1 2 l 4 7689 164 2 1 4 3 8 2 Use Farris 1200 lapping compound When lapping the disc operate with a light figure eight motion over entire block surface I...

Page 7: ...blowdown ring notches without jamming the ring in its tightened posi tion 15 The valve is now ready to be removed for testing 6 Series 1890 and 1892 1 Refer to Figure 2 2 for construction details 2 V...

Page 8: ...while loading the spring 3 Slowly raise the test drum pressure and observe the opening point The set pressure on air or steam is the pop point while on water it is the first continuous flow 4 If neces...

Page 9: ...Curtiss Wright Flow Control Corporation SERIES SIZE A A1 B C C1 D E F G H J K L 2850 3 4 X 1 7501 7852 8103 1254 1254 0151 284 700 894 459 1 X 1 1 2 1 0001 1 0372 1 0603 1254 1254 0151 331 950 1 125 6...

Page 10: ...contained herein is to be construed as a warranty or guarantee expressed or implied regarding the performance merchantability fitness or any other matter with respect to the products nor as a recommen...

Reviews: