400.5 NCC DT-10 (Determinator) Automatic Timer Controller
The DT-10 (Determinator) Automatic Timer Controller uses a differential pressure transmitter connected
to a solid state timer control to initiate the cleaning cycle at user input differential pressure points. When
the differential pressure across the filter elements reaches the high set point, the control will begin the
cleaning sequence until the low differential pressure set point is obtained. The control will then end the
cleaning cycle until the high set point is reached again. At this point, the control will re-initiate cleaning
beginning with the next to last row cleaned.
37
PROCESS (IN H O)
TIME OFF (SEC)
TIME ON (MSEC)
HIGH LIMIT
LOW LIMIT
HIGH ALARM
LOW ALARM
CYCLE DELAY (MIN)
DOWN TIME CYCLES
(MIN)
AUTO ALARM RESET
(SEC)
LAST OUTPUT
RUN
ALARM
RESET
MANUAL
OVERRIDE
UP
DOWN
SELECT
SETUP
STATUS
DA
IS
Y C
H
AI
N
IN
OUT
DWYER INSTRUMENTS
MICHIGAN CITY, IN
HIGH
LIMIT
COM LOW
LIMIT
ALARM
MODE
MAN
OVR
DT
CLN
ALARM
RESET COM
COM
TB
3
TB
2
4-20 MA
OUTPUT
l+
l-
NC
l+
l-
NC
4-20
M
A
S
O
U
RCE
EXTER
N
AL
IN
TE
RNA
L
ALAR
M
CONTA
C
T
S
PO
W
E
R
ON
TB4
TB5
DO NOT USE
SLOW BLOW FUSES
LINE VOLTAGE
85V MIN TO 270 V MAX
50/60 HZ
L1 L2
SOL.
COM.
1
OUTPUTS (300 VA MAX)
2
3
4
5
6
7
8
9
10 11 12 13 14 15 16 17 18 19 20 21 22
L1
X
BLACK B
X
L1
HAND
NOT USED
AUTO
1
X
BLACK A
WHITE B
X
X
WHITE A
3
2
L1
L2
3 POSITION SELECTOR
SWITCH
ALLEN BRADLEY
PN-800T-J2-KU7-B
PN-800T-X625
W/NAMEPLATE
120/1/50-60 VAC
200 VA TO SOLENOIDS
16 AWG WIRE MIN.
EXTERNAL
SOLENOID
CONNECTIONS
1
PLUG-IN
PRESSURE
MODULE
Figure 400.4.2
Dwyer DCT1000
Timer wiring diagram
2