Fantech VHR704R Installation Manual Download Page 9

9

AIRFLOW BALANCING

1

  For this flow measuring 

station, cut the duct and 
place the flow measuring 
station between each section 
of duct. Make sure that the 
flow measuring station’s air 
direction arrow points in the 
direction of the airflow. 
Secure the flow measuring 
station with duct tape.

2

  Before taking the 

reading, make sure 
that the magnehelic 
gauge is level and at 
0. Refer to the flow 
measuring station’s 
chart to determine 
your unit’s airflow 
velocity.

3

  Adjust the “Supply Air 

Out” damper until you 
reach the desired 
velocity. Follow the 
previous steps to adjust 
the “Exhaust Air Out” 
damper, if needed.

B

Measure 

here

Measure 

here

12”

(300 mm)

12”

(300 mm)

•  To avoid airflow 

turbulence and 
incorrect readings, the 
airflow velocity should 
be measured on steel 
ducting a minimum of 
12” (300 mm) from 
the unit or elbow and 
before any transition.

The following procedure is designed for measuring airflow and balancing 
an HRV based ventilation system.                                                    

Step 1:

 Prepare the house

•  Air/vapor barriers must be complete.
•  Fireplace dampers, windows and doors closed.
•  Clothes dryers and other large exhaust devices must be off.

Step 2:

 Prepare the system

•  Ventilation system must be complete, including grilles and registers.
•  Check that filters are installed and clean.
•  All system dampers set to operating positions (fully open for 

new installations.

•  Check that intake and exhaust hoods are clear. 
•  Check that the HRV drain trap is full of water.
•  In cold weather, check that HRV is defrosted and not in defrost mode.
•  Turn HRV (fans) on high speed.

Step 3

: Taking measurements

•  Ensure measuring gauge is level and secure. Magnehelic or slope 

manometer cannot be hand held.

•  “Zero” gauge as required.
•  Connect hoses to high and low ports of gauge and MBS. High to 

high and low to low.

•  Read pressure from gauge and convert it to cfm using the chart for 

the unit’s MBS. Record reading.

•  This process must be done twice, once for the supply duct system 

and once for the exhaust duct system.

Step 4:

 Balancing the airflow

Both the supply and exhaust measurements taken in step 3 must be 
greater  than  or  equal  to  the  Total  Ventilation  Capacity.  An  HRV  is 
deemed balanced if the supply and exhaust flow are or- 10% of 
each other.

•  From the chart on 
the MBS, determine the 
pressure reading which 
corresponds to the 
ventilation rate required 
(TVC). With the 
measuring gauge 
attached to the MBS, 
slowly close volume 
damper until gauge reads 
the correct pressure.

•  Lock volume damper in position.

•  Repeat the above procedure for the second duct system. It does 

not matter whether the supply or exhaust is adjusted first. 

AIRFLOW STATION (GRID) METHOD

Fantech’s  superior  design  and  use  of  EBM  motors  results  in  a  steep  fan  curve  that  usually  does  not  require  balancing. 

Commissioning the system after installation is recommended which includes confirming the proper operation of the system and 
how it interacts with other components within the home.

HIGH

LOW

LOW

HIGH

SUPPLY

EXHAUST

Measuring and Balancing Airflow with a Measurement and Balancing System

Summary of Contents for VHR704R

Page 1: ...asuring the airflow of the Heat Recovery or Energy Recovery Ventilators It is always important to assess how the operation of any HRV ERV may interact with vented combustion equipment i e Gas Furnaces...

Page 2: ...ncurred in the use of the ventilation system Fantech is not responsible for providing an authorized service center near the purchaser or in the general area Fantech reserves the right to supply refurb...

Page 3: ...e UL 94HF MOTORS Two 2 German manufactured factory balanced ebm motors with backward curved blades Motors come with permanently lubricated sealed ball bearings to guarantee long life and maintenance f...

Page 4: ...ps Watts 115V 60Hz 0 40A 40W 3 plug in power cord w 3 prong plug Continuous ventilation mode of supply and exhaust airstreams 10 254mm of clear ance is recommended for removal of core Pa in wg L s cfm...

Page 5: ...p should be made in the drain line This will prevent odors from being drawn back up into the unit MOUNTING EASY WALL MOUNT LOCATION The HRV must be located in a heated space where it will be possible...

Page 6: ...ropriate port on the HRV The insulation should remain full and not be compressed The outer liner which acts as a vapor bar rier must be completely sealed to outer wall and the HRV using tape and or ca...

Page 7: ...recommended Galvanized ducting from the HRV ERV to the living areas in the house is recommended whenever possible although flexible duct can be used in moderation when necessary Warning The VHR 704R s...

Page 8: ...n an enclosed room with spillage susceptible combustion appliances Partially Dedicated System Stale air drawn from key areas of home bathroom Fresh air supplied to main living areas via the forced air...

Page 9: ...rap is full of water In cold weather check that HRV is defrosted and not in defrost mode Turn HRV fans on high speed Step 3 Taking measurements Ensure measuring gauge is level and secure Magnehelic or...

Page 10: ...ring the winter months Clean Core and Filters Every 3 6 Months Unplug unit before doing any repairs or maintenance a Open access door b Carefully grip handle of core and pull out Core will slide out o...

Page 11: ...tire line of SHR VHR series Heat Recovery Ventilators comes equipped with Fantech s new electronic uni control board which offers a wide variety of features making it the ultimate ventilation control...

Page 12: ...you Adjust the control when needed PRACTICAL TIPS All controls are low voltage 18 to 24 gauge wire is recommended OPTIONAL REMOTE CONTROLS OPERATION CONT D NOTE A dehumidistat is ideal for use in ene...

Page 13: ...Locate the grilles high on the walls or under the baseboards install ceiling mounted diffuser or grilles so as not to directly spill the supply air on the occupant eg Over a sofa Turn down the HRV sup...

Page 14: ...2 wires Dehumidistat On Off 4 wires Mechanical Crank Timer 2 wires and or and or 1 only Air Quality Sensor CUR SW DEHUM N C N O TIMER EDF COM FURNACE INTERLOCK IN COM EDF5 or EDF2 not shown EDF1 RTS3...

Page 15: ...TIMER RED FURNACE INTERLOCK COM PC SW3 COM NO ON J7 J5 J6 J4 J3 ON OFF ON ON ORANGE ORANGE GREEN STAND BY MED BROWN BROWN GREY TR1 RED YELLOW BLACK WHITE BLUE SW1 BLACK T P DAMPER MOTOR LOW RED BROWN...

Page 16: ...rgizing the R and G termi nals at the furnace has the effect of energizing Y at the thermostat and thereby turning on the cooling system If you identify this type of thermostat you must use the Altern...

Reviews: