Room classification 

Number of rooms 

CFM (L/s) 

CFM Required

Master bedroom 

 

x 20 cfm (10 l/s) 

=

Basement 

yes or no 

 

=

Bedrooms 

 

x 10 cfm  (5 l/s) 

=

Living room 

 

x 10 cfm  (5 l/s) 

=

Others 

 

x 10 cfm  (5 l/s) 

=

Kitchen 

 

x 10 cfm  (5 l/s) 

=

Bathroom 

 

x 10 cfm  (5 l/s) 

=

Laundry room 

 

x 10 cfm  (5 l/s) 

=

Utility room 

 

x 10 cfm  (5 l/s) 

=

 

Total Ventilation Requirements

 (add last column ) 

=

if yes add 20 cfm / 10 l/s 

if no = 0

Alternate Method

2

TABLE OF CONTENTS

TECHNICAL DATA
 

VHR 704R . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

INSTALLATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
 

Mounting the Unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 

 

Location & Ducting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  6

 

Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

 

Air Flow Balancing  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  10

OPERATION  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Modes Of Operation  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
 

Optional Remote Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  12

MAINTENANCE   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  13

TROUBLESHOOTING  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

ELECTRICAL CONNECTIONS  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...  15

  The Best  

Limited Warranty  

in the Business

•  The heat recovery aluminum core has a 

limited lifetime warranty.

•  The motors found in all Fantech HRV’s 

require no lubrication, and are factory 
balanced to prevent vibration and promote 
silent operation.

•  The limited warranty covers normal use. 

It does not apply to any defects, 
malfunctions or failures resulting from 
improper installation, abuse, mishandling,  
misapplication, fortuitous occurrence or 
any other circumstances outside 
Fantech’s control.

•  Inappropriate installation or  

maintenance may result in the 
cancellation of the warranty.

•  Any unauthorized work will result in  

the cancellation of the warranty.

•  Fantech is not responsible for any  

incidental or consequential damages 
incurred in the use of the ventilation 
system.

•  Fantech is not responsible for providing 

an authorized service center near the 
purchaser or in the general area.

•  Fantech reserves the right to supply 

refurbished parts as replacements.

•  Transportation, removal and installation 

fees are the responsibility of the purchaser.

•  The purchaser is responsible for ensuring 

that applicable local and national codes 
are observed.

•  The warranty is limited to 5 years on parts 

and 7 years on the motor from the date of 
purchase, including parts replaced during 
this time period. If there is no proof of 
purchase available, the date associated 
with the serial number will be used for the 
beginning of the warranty period.

* This warranty is the exclusive and only 

warranty in effect relative to the ventilation 
system and all other warranties either 
expressed or implied are invalid.

Sizing (Example) for maximum airflow normally required.

HRVs are typically sized to ventilate the whole house at a minimum of 0.35 air changes per 
hour. To calculate, simply take the square footage of the house (including basement) and multi-
ply by the height of the ceiling to get cubic volume. Then, divide by 60 and multiply by 0.35.
Example: 

SQFT of House 

1100

 

Basement 

1100

 

Total SQFT 

2200

 

Height of ceiling 

x   8

 

Cubic volume 

17600

 

 

/  60

 

Maximum airflow required (CFM) 

293

 

 

x  0.35

 

 

103

* Always consult your local code for sizing requirements in your area.

1 cfm = 0.47189 l/s 
1 l/s = 3.6 m

3

/hr

***Illustrations & 

images in this  

manual may not be 

exactly like unit  

purchased, these 

illustrations & imag-

es are for examples 

only.***

Summary of Contents for VHR704R

Page 1: ...asuring the airflow of the Heat Recovery or Energy Recovery Ventilators It is always important to assess how the operation of any HRV ERV may interact with vented combustion equipment i e Gas Furnaces...

Page 2: ...ncurred in the use of the ventilation system Fantech is not responsible for providing an authorized service center near the purchaser or in the general area Fantech reserves the right to supply refurb...

Page 3: ...e UL 94HF MOTORS Two 2 German manufactured factory balanced ebm motors with backward curved blades Motors come with permanently lubricated sealed ball bearings to guarantee long life and maintenance f...

Page 4: ...ps Watts 115V 60Hz 0 40A 40W 3 plug in power cord w 3 prong plug Continuous ventilation mode of supply and exhaust airstreams 10 254mm of clear ance is recommended for removal of core Pa in wg L s cfm...

Page 5: ...p should be made in the drain line This will prevent odors from being drawn back up into the unit MOUNTING EASY WALL MOUNT LOCATION The HRV must be located in a heated space where it will be possible...

Page 6: ...ropriate port on the HRV The insulation should remain full and not be compressed The outer liner which acts as a vapor bar rier must be completely sealed to outer wall and the HRV using tape and or ca...

Page 7: ...recommended Galvanized ducting from the HRV ERV to the living areas in the house is recommended whenever possible although flexible duct can be used in moderation when necessary Warning The VHR 704R s...

Page 8: ...n an enclosed room with spillage susceptible combustion appliances Partially Dedicated System Stale air drawn from key areas of home bathroom Fresh air supplied to main living areas via the forced air...

Page 9: ...rap is full of water In cold weather check that HRV is defrosted and not in defrost mode Turn HRV fans on high speed Step 3 Taking measurements Ensure measuring gauge is level and secure Magnehelic or...

Page 10: ...ring the winter months Clean Core and Filters Every 3 6 Months Unplug unit before doing any repairs or maintenance a Open access door b Carefully grip handle of core and pull out Core will slide out o...

Page 11: ...tire line of SHR VHR series Heat Recovery Ventilators comes equipped with Fantech s new electronic uni control board which offers a wide variety of features making it the ultimate ventilation control...

Page 12: ...you Adjust the control when needed PRACTICAL TIPS All controls are low voltage 18 to 24 gauge wire is recommended OPTIONAL REMOTE CONTROLS OPERATION CONT D NOTE A dehumidistat is ideal for use in ene...

Page 13: ...Locate the grilles high on the walls or under the baseboards install ceiling mounted diffuser or grilles so as not to directly spill the supply air on the occupant eg Over a sofa Turn down the HRV sup...

Page 14: ...2 wires Dehumidistat On Off 4 wires Mechanical Crank Timer 2 wires and or and or 1 only Air Quality Sensor CUR SW DEHUM N C N O TIMER EDF COM FURNACE INTERLOCK IN COM EDF5 or EDF2 not shown EDF1 RTS3...

Page 15: ...TIMER RED FURNACE INTERLOCK COM PC SW3 COM NO ON J7 J5 J6 J4 J3 ON OFF ON ON ORANGE ORANGE GREEN STAND BY MED BROWN BROWN GREY TR1 RED YELLOW BLACK WHITE BLUE SW1 BLACK T P DAMPER MOTOR LOW RED BROWN...

Page 16: ...rgizing the R and G termi nals at the furnace has the effect of energizing Y at the thermostat and thereby turning on the cooling system If you identify this type of thermostat you must use the Altern...