11

Start up procedure

The Switch on the side of the unit is used to toggle between STANDBY, REDUCED speed and NORMAL speed modes.

Place the unit in NORMAL speed to perform the balancing.

Airflow balancing

IF THE UNIT'S AIR FLOWS ARE NOT PROPERLY BALANCED...

•  THE UNIT'S EFFICIENCY MAY BE REDUCED.
•  THE UNIT'S CORE MAY BECOME DAMAGED.
•  NORMAL OPERATION OF THE UNIT COULD CAUSE THE PRESSURIZATION OR DEPRESSURIZATION OF YOUR 

HOME, WHICH CAN LEAD TO AIR LEAKS OR BACKDRAFTING OF ANY COMBUSTION APPLIANCES.

The balancing procedure consists of measuring the supply air flow and the return air flow to ensure that they are equal. A difference of up to 10% is 
considered acceptable. In the cases where the air flow is not exactly the same, it is recommended to have a higher return air flow to ensure that the 
temperature of the supply air flow coming from outside is as close to room temperature as possible.

 

       • 

For optimal performance, ERV unit should be re-balanced after a major renovation or after the  

 

 

 

 

installation of extra grilles or registers.

 

 

 

 Remove the nutsert. 

INSTALLING DRAIN LINE

Through normal operation and during its defrost mode, the ERV may produce some condensation. This water should flow into a nearby drain, or be taken 
away by a condensate pump. The ERV and all condensate lines must be installed in a space where the temperature is maintained above the freezing point. 
A “P” trap should be made in the drain line. This will prevent odors from being drawn back up into the unit.

2  

Invert the drain nipple. Make 

sure to place gasket between 
the unit and the drain nipple 
inside the unit.

3  

Secure the drain nipple using 

the nutsert.

4  

Install the drain hose making a 

"P" trap, secure the 
condensate line drain 
connection using the tube 
clamp provided.

  Fill the condensate line with 

water.

The drain nipple is placed upside down in the unit to prevent it being damaged during shipping or the installation of the unit.

Summary of Contents for SER150

Page 1: ...ode and or ASHRAE s Good Engineering Practices Fantech reserves the right to modify at any time and without notice any or all of its products features designs components and specifications to maintain their technological leadership position Please visit our website www fantech net for more detailed technical information United States 10048 Industrial Blvd Lenexa KS 66215 Tel 800 747 1762 Fax 800 4...

Page 2: ...nted combustion equipment i e Gas Furnaces Oil Furnaces Wood Stoves etc Products are designed and manufactured to provide reliable performance but they are not guaranteed to be 100 free of defects Even reliable products will experience occasional failures and this possibility should be recognized by the user If these products are used in a life support ventilation system where failure could result...

Page 3: ...rhood Location 8 Installing the ducting to the weatherhood 8 INTERIOR DUCTING INSTALLATION General Tips 9 Installing duct to ERV 9 Supply Exhaust Air Grilles Location 9 ERV INSTALLATION 10 AIRFLOW ADJUSTMENT BALANCING Start up procedure 11 Airflow balancing 11 LOW VOLTAGE CONTROL SYSTEMS 13 WIRING DIAGRAM 14 TROUBLESHOOTING 16 ERV MAINTENANCE CHART 17 ERV CORE WASHING INSTRUCTION 18 PARTS LIST 19 ...

Page 4: ... area Bedrooms 0 1 2 3 4 5 6 7 7 Ft2 m2 CFM L s CFM L s CFM L s CFM L s CFM L s 1500 139 30 14 45 21 60 28 75 35 90 42 1501 3000 139 1 279 45 21 60 28 75 35 90 42 105 50 3001 4500 279 1 418 60 28 75 35 90 45 105 50 120 57 4501 6000 418 1 557 75 35 90 42 105 50 120 57 135 64 6001 7500 557 1 697 90 42 105 50 120 57 135 64 150 71 7500 697 105 50 120 57 135 64 150 71 165 78 ASHRAE 62 2 2010 Table 4 1 ...

Page 5: ...The ERV s airflow must be balanced after installation using the procedure found in the section AIRFLOW BALANCING Suggested installation for Hydronic baseboard Infloor heating Electric baseboard Mini split heat pump Benefits Provides the best fresh air distribution in the house lowest operation cost since the furnace air handler unit is not needed Air from inside Unit air flow should be balanced wh...

Page 6: ... 2 Stale air is drawn from key areas of the home bathroom kitchen laundry room 3 Fresh air is supplied to the return air plenum of the furnace 4 Due to the difference in pressure between the ERV and the equipment it is being connected to the ERV s airflow must be balanced on site using the procedure found in the section AIRFLOW BALANCING In the case of a multi zone system please contact Fantech cu...

Page 7: ...fresh air the ERV s exhaust air connection should be upstream of the ERV s supply air connection when ducting to the furnace s cold air return 4 Due to the difference in pressure between the ERV and the equipment it is being connected to the ERV s airflow must be balanced on site using the procedure found in the section AIRFLOW BALANCING In the case of a multi zone system please contact Fantech cu...

Page 8: ...arrier must be completely sealed to the outer wall and the ERV using tape and or caulking A good bead of high quality caulking preferably acoustical sealant will seal the inner flexible duct to both the ERV duct connection and the weatherhood prior to securing them To minimize airflow restriction the flexible insulated duct that connects the two outside weatherhoods to the ERV should be stretched ...

Page 9: ...exible duct to prevent leakage between the ducting and the duct connection In the case of solid ducting slide duct over duct connection screw in place and seal Supply air grilles location In homes without a forced air furnace fresh air should be supplied to all habitable rooms including bedrooms and living areas It should be supplied from high wall or ceiling locations Grilles that diffuse the air...

Page 10: ...p fan Central vacuum system Bathroom exhaust fans unless they are specifically designed for this purpose These appliances may cause lint dust or grease to collect in the ERV damaging the unit Connecting any of these types of appliances to the ERV will void your warranty Mounting Chain mount Have a nearby power supply 120 volts 60Hz Choose a location which allows the possibility of mounting the uni...

Page 11: ...s close to room temperature as possible For optimal performance ERV unit should be re balanced after a major renovation or after the installation of extra grilles or registers 1 Remove the nutsert INSTALLING DRAIN LINE Through normal operation and during its defrost mode the ERV may produce some condensation This water should flow into a nearby drain or be taken away by a condensate pump The ERV a...

Page 12: ...o be made prior to any transition in the duct work so entire airflow is measured Measuring the airflow using station grid method Adjusting airflows A damper is integrated into the Fresh Air to Building collar This damper replaces the installation of a separate damper into the Fresh Air to Building ducting line The damper collar is pre set in the fully opened position If the procedure requires a re...

Page 13: ...referred indoor relative humidity range and ventilation mode for day and night conditions No battery to replace all programmed settings are retained during power outage Maintenance reminder indicator Error code messages reduce troubleshooting time EDF7 MODE button provides 3 modes of operations Ventilation Recircula tion and Standby User selected fan speed Reduced Medium Normal and 20 minutes per ...

Page 14: ...14 WIRING DIAGRAM Observe polarity on all accessory controls where applicable ...

Page 15: ...ECTION TO A COOLING SYSTEM On some newer furnaces and older thermostats energizing the R and G terminal at the furnace has the effect of energizing the Y at the thermostat and thereby turning on the cooling system If you identify this type of thermostat you must use the Alternate Furnace Interlock Wiring Standard Accessory Control Contact Alternative Accessory Control Contact As per building codes...

Page 16: ... power supply at site Have electrician check supply voltage Ductwork is restricting airflow Check duct installation Improper speed control setting Increase the speed of the ERV i e change unit control from REDUCED to NORMAL speed ERV airflow improperly balanced Have contractor balance ERV airflows Ducting has fallen down or been disconnected from ERV Have contractor reconnect ducting Supply air fe...

Page 17: ...mages incurred in the use of the ventilation system Fantech is not responsible for providing an authorized service centre near the purchaser or in the general area Fantech reserves the right to supply refurbished parts as replacements Transportation removal and installation fees are the responsibility of the purchaser The purchaser is responsible to adhering to all codes in effect in his area This...

Page 18: ...ore s air inlets facing down place it in a large sink bathtub or shower 4 Pour clean tap water through the face of the core facing upwards until it runs clear Ensure the entire surface is rinsed 5 Rotate the core so that its other air inlet is facing down and repeat step 5 6 With plates still oriented vertically allow the core to dry normally 2 3 hours 7 Slide back the core into the unit 8 Replace...

Page 19: ...very Cell 9 x 9 x 15 427473 4 Capacitors 8uF 410012 5 Kit PCB Replacement Board AC 422677 6 Door Switch 410867 7 Auto Transformer 411963 8 Control Switch 410213 9 Kit Drain Plug 40315 10 Collar 6 Balancing 10mm 403382 11 Collar 6 24mm LIP 410542 15 Temperature Probe 40286 16 Door Assembly 405532 Kit Chain 404261 Wall Support VHR120R 150R 426466 Wiring Diagram 423054 ...

Page 20: ...Fantech reserves the right to make technical changes For updated documentation please refer to www fantech net Fantech ...

Reviews: