EN_FANOXTD_GUIDE_SIL_OCEFPrimaryDist_SILA_R002.doc 33 / 36
•
51 Inverse time phase overcurrent protection:
TEST 1:
Settings:
-
Function Enable: YES.
-
Curve: IEC Inverse.
-
Dial (TMS): 0.05
-
Current Tap: 0.5xIn.
-
Theoretical tripping time= 3.67 seconds (Fault
current 0.55 A)
The following information will be checked:
-
Pick-up at 110% of the tap
-
Output 4 is activated
-
LED 2 is activated
TEST 2
Settings:
-
Function Enable: YES.
-
Curve: IEC Inverse.
-
Dial (TMS): 1
-
Current Tap: 0.5xIn.
-
Theoretical tripping time = 4.98 seconds (fault current 2 A)
The following information will be checked:
-
Pick-up at 110% of the tap
-
Output 4 is activated
-
LED 2 is activated
TEST 3
Settings:
-
Function Enable: YES.
-
Curve: IEC Inverse.
-
Dial (TMS): 0.5
-
Current Tap: 16xIn.
-
Theoretical tripping time = 5.01seconds (Fault current 32)
The following information will be checked
:
-
Pick-up at 110% of the tap
-
Output 4 is activated
-
LED 2 is activated