EN_FANOXTD_GUIDE_SIL_OCEFPrimaryDist_SILA_R002.doc 18 / 36
NOTE:
As it is described above, the options NOR4_LATCH and NAND4_LATCH are not
available in the relay. Although, using SICOM software allows the user to configure these
options, the relay will not recognize them, and it will not work properly.
By default, configuration is:
OUTPUT
LOGICAL GATE
BINARY STATES (Adaptation B) BINARY STATES (Adaptation C)
LEDs
LED 1
OR4_PULSES
•
Ready
•
Ready
LED 2
OR4_LATCH
•
50-1 Trip
•
50-2 Trip
•
51 Trip
•
50-1 Trip
•
51 Trip
LED 3
OR4_LACTH
•
50G1 Trip
•
50G2 Trip
•
51G Trip
•
50G1 Trip
•
51G Trip
LED 4
OR4_LACTH
•
50BF Trip
•
SHB
LED 5
OR4_LACTH
•
46 Trip
•
46 Trip
LED 6
OR4_LACTH
•
74TCS Alarm
•
74TCS Alarm
LED 52
OR4
•
52 Closed
•
52 Closed
LED 79
OR4
•
79 Standby
•
79 Standby
PHYSICAL
OUTPUTS
Output 1
OR4
•
Ready
•
Ready
Output 2
OR4
•
50BF Trip
•
46 Trip
•
46BC Trip
Output 3
OR4
•
79 Close time
•
Local close breaker
•
Remote Modbus close
breaker
•
Remote
protocol
close
breaker
•
79 Closing time
•
Local close breaker
•
Remote modbus close
breaker
•
Remote DNP3.0 close
breaker
Output 4
OR4
•
General trip
•
Local open breaker
•
General trip
•
Local open breaker
LOGICAL GATE
HMI SYMBOL
OR4
+
NOR4
OR4_LACTH
Ю
AND4_LACTH
Φ
OR4_PULSES
⌠
AND4
&
NAND4
§
AND4_PULSES
$
OR4_TIMER_UP
O
NOR4_TIMER_UP
P
AND4_TIMER_UP
Q
NAND4_TIMER_UP
R
OR4_PULSE
o
NOR4_PULSE
p
AND4_PULSE
q
NAND4_PULSE
r
NOR4_PULSES
t