Rev. 01
12/17
1.5.2. Measurements Map
Address
Description
Format
300
Phase A current IA
FLOAT INVERSE
302
Phase B current IB
304
Phase C current IC
306
Neutral current IN
308
Thermal Image TI
310
Maximum phase current IMAX
1.5.3. Settings Map
Settings
Address
Description
Format
Enumeration
Generals
600
(*)
Identification
ASCII20
-
800
(**)
610
(*)
Frequency
DENUM
0 → 60 Hz
1 → 50 Hz
810
(**)
612
(*)
Serial Number
LONG
-
812
(**)
614
(*)
Language
DENUM
0 → English
1 → Spanish
2 → Depends on Relay model
814
(**)
616
(*)
Active Setting Group
LONG
-
816
(**)
618
(*)
CT Phase Ratio
FLOAT INVERSE
-
818
(**)
620
(*)
CT Neutral Ratio
FLOAT INVERSE
820
(**)
622
(*)
Local COM Address
LONG
-
822
(**)
624
(*)
Password
ASCII4
-
824
(**)
626
(*)
Remote COM Address
LONG
-
826
(**)
628
(*)
Remote Baud Rate
DENUM
0 → 4800 Bd
1 → 9600 Bd
2 → 19200 Bd
3
→ 38400 Bd
828
(**)
Summary of Contents for SIA F
Page 17: ...www fanox com Rev 01 17 17...