ISO 9001:2008
www.fanox.com
SIAC116B1011AB_Rev. 05
5 / 32
1.3.1. Keypad & LCD
•
Use the KEYPAD, ensure that all the push-buttons work correctly (no difficulties while
pushing them, check out if the relay reacts by pushing each of the buttons).
•
Use the KEYPAD to enter in the relay´s menu and make sure that no text is lost while
going from one menu to another.
•
Follow the sequence: Left ◄, Down ▼, Right ►, Up ▲, OK, C and RESET and the
following screen should be displayed:
•
If the
contrast of the LCD is not the correct one, enter to “
CONTRAST”
menu by holding
“◄“ for 3 seconds. Then, change it by using up or down buttons to increase or
decrease the contrast.
1.3.2. Test menu
NOTE
: When performing test menu, protection won´t be available and it will possible to
open circuit breaker. Only authorized personnel can do this job.
Press ◄,▼,► sequentially and hold
OK.
The relay will ask for the password “5555” to
enter to the test menu (or customer password if default “5555” has been modified).
It will be checked that the LEDs, Magnetic indicator flags and Outputs are activated if OK
key is pressed and it will be deactivated if OK key is pressed again. LEDs, Magnetic
indicator and outputs will be checked to verify the hardware is OK:
Action
Checking
OK
,
OK
Led 1
Led Vaux activated
▼
,
OK
Led 2
Led Self power activated
▼
,
OK
Led 3
Led Battery activated
▼
,
OK
Trip output
Trip output activated
▼
,
OK
Output 2
Output 2 activated
▼
,
OK
Output 3
Output 3 activated
▼
,
OK
Trip
Trip bistable activated
C
Skip from test menu