4. OPERATING INSTRUCTIONS
3. ASSEMBLING INSTRUCTIONS - CONTINUED
•
Position the heater on a flat, level, non-flammable & solid surface.
•
Indirect-fired heaters while used in indoors, must be connected to an exhaust
pipe to vent the fumes of combustion outside. To maintain an adequate Oxygen
rate, a minimum of 80 m3/h airflow from outside must occur.
•
For indirect-fired heaters: connect the heater to an exhaust duct. To get a proper
exhaust flow out, the fumes must rise throigh the flue. Avoid any elbows and
bends in the first part of the exhaust ducts for at least 3m.
•
Only position the heater in the normal upright position (on the wheels)
•
Do not place the heater near walls, corners or low ceilings.
• Do not place the heater below a power socket outlet.
• Do not place the heater on moving vehicles or where it can tip over.
•
Keep the heater away from flammable, combustible, explosive or corrosive
materials.
• Keep the heater away from curtains or similar materials that could block the air
inlet and outlet.
• Never block or restrict the air inlet and outlet for any reason.
•
Keep the power cable away from heat sources, sharp edges, cutting and
moving parts.
•
Do not expose directly to the weather or to excessive humidity.
•
Do not place the heater in the immediate surroundings of a bath, shower or
swimming pool.
• Ensure the following minimum safety clearances from materials or objects in the
surroundings of the heater:
Side:
0.6m
Air inlet side:
1m
Top:
1.5m
Hot air outlet side:
3m