9.2 Current transformer
The current transformer ratio of the meter can be set remotely via the Modbus RTU interface or
locally using the PROG button.
To set it manually:
1) switch off and on the power supply of the meter;
2) press and hold down the PROG button;
3) release the PROG button after about 15 seconds;
4) the display will show a blinking CT value (for example 0005-5); the table of available settings is
shown below;
5) set the desired value of the current transformer ratio by pressing the button to the left or right;
6) wait until the transformer value disappears from the display.
Setting the transformer ratio via the RS485 interface requires the code value corresponding to the
selected current transformer to be written to register number 8.
Please note:
The code designation of the transformer is created by writing the value of the
transformer primary current as a BCD number.
Transformer
Code designation
Hexadecimal
Decimal
5/5
0x0005
5
30/ 5(*)
0x0030
48
40/5
0x0040
64
50/5
0x0050
80
60/5
0x0060
96
75/5
0x0075
117
80/ 5(*)
0x0080
128
100/5
0x0100
256
125/5
0x0125
293
150/5
0x0150
336
200/5
0x0200
512
250/5
0x0250
592
300/5
0x0300
768
400/5
0x0400
1024
500/5
0x0500
1280
600/5
0x0600
1536
750/ 5(*)
0x0750
1872
800/5
0x0800
2048
1000/5
0x1000
4096