LE-03MW CT – user manual
13
Register
Feature
Type R/W Quantity
Settings
Dec Hex
0
0 Serial number
U32
R
2
1
2 Meter Modbus address
U16 R/W
1
1÷247
2
3 Baud rate
U16 R/W
1
1200, 2400, 4800,
9600
3
4 Software version
Float R
2
6
6 Hardware version
Float R
2
8
8 Current transformer CT
U16 R/W
1
List of setting codes in
the table below
9
9 Configuration of the pulse output Float R/W
2
12000, 1200, 120, 12
11
B Parameter calculation option:
- Total active energy
- Total reactive energy
U16 R/W
1
1 – total energy
= consumed energy,
5 – total energy
= consumed energy,
+ energy exported
9 – total energy
= consumed energy
- energy exported
13
D View display time
U16 R/W
1
1÷30
14
E L1 – Phase voltage
Float R
2
16
10 L2 – Phase voltage
Float R
2
18
12 L3 – Phase voltage
Float R
2
20
14 Frequency
Float R
2
22
16 L1 – Phase current
Float R
2
24
18 L2 – Phase current
Float R
2
26
1 A L3 – Phase current
Float R
2
28
1C Total active power
Float R
2
30
1E L1 phase – active power
Float R
2
32
20 L2 phase – active power
Float R
2
34
22 L3 phase – active power
Float R
2
36
24 Total reactive power
Float R
2
38
26 L1 phase – reactive power
Float R
2