- 10 -
Register parameters
address
description
type
atr
0
Meter address: range 1÷255
int
R/W
1
L1 voltage [V] (×0.01)
int
R
2
L2 voltage [V] (×0.01)
int
R
3
L3 voltage [V] (×0.01)
int
R
4
L1 current intensity [A] (×0.01)
int
R
5
L2 current intensity [A] (×0.01)
int
R
6
L3 current intensity [A] (×0.01)
int
R
7
L1 active power [kW] (×0.001)
int
R
8
L2 active power [kW] (×0.001)
int
R
9
L3 active power [kW] (×0.001)
int
R
10
L1+L2+L3 active power [kW] (×0.001)
int
R
11
Protection current [A] (×0.01)
int
R/W
12
Automatic operation mode
(0:OFF/1:ON)*
int
R/W
13
Current state of relay (0:OFF/1:ON)
int
R
14
Manual relay control (0:OFF/1:ON)
int
R/W
15
Frequency [Hz] (×0.01)
int
R
* Automatic operation is the mode with two active functions: automatic
relay disconnection if the set overcurrent threshold is exceeded and swit-
ching on the prepaid mode.