- 2 -

»

Laser distance sensor of the ToF (Time of Flight) type;

»

The detection range can be smoothly adjusted in the range of 

0.1 to 2 m;

»

A brightness sensor that prevents the light from being swit-

ched on when the brightness level is high;

»

Adjustable time of keeping the light on;

»

Separated relay output for direct control of 230 V circuits, or 

integration into any home automation system;

»

Possibility of direct control of electrical circuits with a load of 

up to 8 A (AC-1);

»

Compact size, can be mounted in a ø60 mm box;

»

LED indicating the operating status of the sensor;

»

Thermal protection against exceeding the acceptable tempe-

rature inside the housing.

1. The location of the mounting of the sensor should be selec-

ted in such a way that no fixed obstacles such as floor, wall, 

staircase step, etc. can be found in the detection cone of the 

sensor at the assumed operating distance. The diameter of the 

detection cone, depending on the set operating distance, can 

be read from the following figure:

Features

Mounting

Summary of Contents for DRL-60-230

Page 1: ...elow the value set on the sensor This solution is perfect for switching on lighting circuits for exam ple on open stairs where it is important that the sensor detects presence only on the stairs and i...

Page 2: ...ct control of electrical circuits with a load of up to 8 A AC 1 Compact size can be mounted in a 60 mm box LED indicating the operating status of the sensor Thermal protection against exceeding the ac...

Page 3: ...ncorrect operation of the distance and light intensity measurement system 3 Do not mount sensors opposite each other or mirrors as this can lead to unwanted sensor excitation 4 Prepare a hole for the...

Page 4: ...utomation controllers follow the documentation of the devices to be integrated 8 Use the dials to set the operating parameters of the detector detection range level of brightness below which switching...

Page 5: ...5 The sensor is designed for a power supply of 165 265 V AC Terminal Function N Sensor supply neutral wire L Sensor supply phase wire OUT Output relay contact Description of control terminals Settings...

Page 6: ...on condition is also met 2 LUX 2 500 Lx Brightness level setting If the light intensity is lower than the value set by the knob the light will switch on when the presence is detected in the detection...

Page 7: ...igher than 8 A or a load with a high starting current it is recommended to use external contactors or relays adapted to current surges e g PP 1Z LED 230 V In this case the DRL 60 230 switches an exter...

Page 8: ...the detection area An obstacle in the detection area has been detected The light was not switched on because the brightness level was too high An obstacle in the detection area has been detected The l...

Page 9: ...flashes at maximum brightness power supply 165 265 V AC maximum load current 8 A detection range adjustable 0 1 2 0 m brightness level adjustable 2 500 lx switch on time adjustable 0 10 min detection...

Page 10: ...dealer or directly with us F F Filipowski L P declares that the device is in conformity with the essential requirements of The Low Voltage Directive LVD 2014 35 EU and the Electromagnetic Compatibili...

Page 11: ......

Reviews: