162236M User Manual GSM Gateway    

 

 

             Page 8 of 20 

4.  Battery 

The battery is supervised in two different ways. The first “low battery voltage indication” is activated 
when the battery voltage is too low for any reason. The second is a “battery fault alarm” activated 
when the battery capacity is too low and it is time to replace the battery. 

In case there is a battery alarm/low battery voltage indication, the GSM Gateway will change the dial 
tone; see section 

Technical Data

 for information on Dial tone battery alarm specifications. The 

emergency alarm will detect the new dial tone and send a battery alarm to the receiver. See section 5 
SMS functionality or 6.2 Setup for information on how to turn the Dial tone battery alarm off. 

4.1  Low battery voltage indication  

A “low battery voltage indication” is activated if the battery voltage drops below 4.6 VDC when the unit 
is powered by the battery. 

The indication is sent by SMS. Please view SMS functionality for information on settings or how to use 
the USB connector and Fältcom Manager Software.  

If the unit is powered by the battery and the battery voltage drops below 4.0 VDC the GSM Gateway 
will shut off to prevent permanent damage of the battery. These voltage levels are not programmable. 

4.2  Battery fault alarm  

A “battery fault alarm” is shown by a red LED, see section 2 above, and by a change of the normal dial 
tone, see section 5.2 below.  

The first battery test is made after 48 hours and the following every 24 hour. During a battery test a 
load is connected to the battery and the battery voltage measured. A battery test lasts for 5 

(1)

 minutes 

and if the voltage drops below 4.4 

(2) 

VDC during this time a “battery fault alarm” is activated.  

A battery test will not be performed when the GSM Gateway is powered by the battery. An active 
“battery fault alarm” is automatically reset after a passed battery test. 

Normally the battery will last 2-4 years but this is very much depending on the surrounding 
temperature and how much the battery is used. When the battery is failing, simply replace the battery 
with an equivalent type - replacement batteries are available from Fältcom sales. Fältcom batteries are 
designed with a wider temperature range and approved to be used with the product. Other types of 
batteries might damage the GSM Gateway. If other supplier of batteries are used Fältcom cannot 
guarantee functionality as the function may not be as good. Levels for battery alarm may also need to 
be changed. 

A polyswitch fuse is integrated in the battery package to prevent it from damage in case of high 
temperatures. The fuse is automatically reset when the temperature is normal again. 

(1) 5 minutes is the default setting. The time is programmable via USB (Fältcom Manager). 

(2) 4.4 V is the default setting. The levels for the “battery fault alarm” is programmable via USB 
(Fältcom Manager) or via SMS by the distributor. 

Summary of Contents for 252236

Page 1: ...GSM Gateway 252236 User Manual Art No 162236M V3 21D 2016 02 18...

Page 2: ...t alarm 8 5 SMS functionality 9 5 1 Low battery voltage indication 9 5 2 Dial tone battery alarm Dial tone 2 11 5 3 Status 12 5 4 Reset 13 5 5 Ask for the current Gain 13 5 6 Change the Gain 13 6 Upgr...

Page 3: ...G The product complies with the following standards norms EN 55022 2006 and A1 2007 EN 55024 1998 and A1 2001 and A2 2003 EN 60950 2006 and ETSI EN 301 511 Ume Sweden January 2013 Mikael L ngstr m CEO...

Page 4: ...the lift phone F ltcom ECII Flex and Power SIM Lift phone F ltcom ECII Flex in LIFT CAR TELE PHONE ANT Power Supply 12 24 VDC 230 VAC OR Battery ANTENNA SIM PIN code Activated or deactivated PIN code...

Page 5: ...se a mobile phone or other equipment to set the PIN code to 1234 At startup the GSM Gateway will automatically change the PIN code to a random 4 digit code to prevent misusage of the SIM card If the S...

Page 6: ...nformation please see section 5 3 LED Indicators LED Status Indicates PWR STAT 1000 ms ON 1000 ms OFF Normal status 100 ms ON 1500 ms OFF Backup power in use PHONE Red LED OFF Phone device is On hook...

Page 7: ...ngth Green LED S1 S2 Signal strength OFF OFF Bad ON OFF Good default 15 83 dBm ON ON Very good default 25 63 dBm Flash OFF Good Backup power in use Flash Flash Very good Backup power in use LED levels...

Page 8: ...by a change of the normal dial tone see section 5 2 below The first battery test is made after 48 hours and the following every 24 hour During a battery test a load is connected to the battery and th...

Page 9: ...t changed The GSM will acknowledge a correct programming by returning a SMS In the example below the battery alarm level is changed to 4 0 V 4000 mV In this example a Low battery voltage indication wi...

Page 10: ...ge level the following is sent from the GSM Gateway Both functions described above are switched off by sending the following to the GSM Gateway The Battery replaced SMS Bares function described above...

Page 11: ...taken off hook To deactivate the Dial tone battery alarm dial tone 2 send the SMS below to the GSM Gateway The GSM will acknowledge a correct programming by returning a SMS To reactivate the dial ton...

Page 12: ...l strength signal strength in dBm S H L Highest signal during last 24h lowest signal during last 24h since last restart UT Uptime counter presented in days hours and minutes LC Last called number not...

Page 13: ...word Gain The default Access code is 1111 and can be changed using the F ltcom Manager SW If the SMS is correct the Gateway will return the Gain settings Description table of the gain SMS Parameter De...

Page 14: ...rameter for signals from alarm receiver to Flex 4 20 POTS GSM Gain parameter for signals from Flex to the alarm receiver 3 20 If the received parameters are outside the range the Gateway will set the...

Page 15: ...local distributor Use a standard USB mini USB cable to connect the GSM Gateway to the PC Install the F ltcom Manager tool on your PC Connect the GSM Gateway to the PC using a standard USB mini B USB...

Page 16: ...y F ltcom or your local distributor Note The FW file always has the file extension bin e g gatewayFW bin Click on Update During the update you can follow the progress in the status bar Note Be careful...

Page 17: ...able the Battery fault alarm but still charge the battery If the lift has a battery backup system the battery in the Gateway can be removed uncheck the Mounted battery box to disable all battery charg...

Page 18: ...not improve try positive values If the receiver has trouble receiving and deciphers DTMF sent by the emergency alarm try adjusting the POTS PHONE to GSM 6 2 6 POTS1 power saving Note Do not use this...

Page 19: ...ass IP 20 External power 10 28 VDC Power consumption At rest 12V 180mA 24V 95mA Ongoing call 12V 330mA 24V 160mA Battery type NiMH 4 8V 1250mAh Battery power consumption At rest 120 mA Ongoing call 30...

Page 20: ...th freight paid on the assumption that the product is covered by warranty If the investigation shows that the re turned product has no defects the customer is charged a service fee and freight The cus...

Reviews: