Synergy Series Soft Start User Manual
MAN-SGY-017. Version 01. 27/06/2016
54
3.9 Advanced Menu (continued)
Menu
Description
Min
Max
Default
Unit
Reg. Type
PNU 896
Advanced
Stop Settings
↓
Stop Pedestal
Percentage of the supply voltage
applied to the motor at the end
of the soft stop
Increase if the motor crawls at
the end of the soft stop.
Decrease if a greater soft-stop
effect is required at the end of
the ramp.
10
40
10
%
Read/Write
PNU 53791
Advanced
Stop Settings
Stop Current Limit
Stop Current Limit
Trip
Selects trip or continue if the
stop current limit has been
active for too long
On : The Unit will trip
Off: The stop will continue
regardless of the motor current
level
Off
On
Off
Read/Write
PNU 28800
Advanced
Stop Settings
Stop Current Limit
Stop Current Limit
Level
The current in Amps at which the
soft stop ramp is not allowed to
go above.
Normally set to 350% motor FLC.
Increase if motor decelerates too
rapidly.
The current limit level will effect
actual time to stop the motor.
100% I-
motor
450% I-
synergy
350% I-
motor
A
Read/Write
PNU 28864
Advanced
Stop Settings
Stop Current Limit
Stop Current Limit
Time
The maximum time allowed for
the current limit.
If the current limit is still active at
the end of this period the Unit
will either trip or continue
1
300
10
s
Read/Write
3. Configuration and Parameters (continued)
Summary of Contents for synergy
Page 1: ...Innovation in soft start technology synergytm USER MANUAL MAN SGY 017 Version 01...
Page 20: ...Synergy Series Soft Start User Manual MAN SGY 017 Version 01 25 07 2016 20 Blank Page...
Page 27: ...Synergy Series Soft Start User Manual MAN SGY 017 Version 01 25 07 2016 27 Blank Page...
Page 33: ...Synergy Series Soft Start User Manual MAN SGY 017 Version 01 27 06 2016 33 Blank Page...
Page 84: ...Synergy Series Soft Start User Manual MAN SGY 017 Version 01 27 06 2016 84 Blank Page...
Page 100: ...Synergy Series Soft Start User Manual MAN SGY 017 Version 01 27 06 2016 100 Blank Page...
Page 106: ...Synergy Series Soft Start User Manual MAN SGY 017 Version 01 27 06 2016 106 Blank Page...
Page 112: ...Synergy Series Soft Start User Manual MAN SGY 017 Version 01 27 06 2016 112 Blank Page...
Page 129: ...Synergy Series Soft Start User Manual MAN SGY 017 Version 01 27 06 2016 129 Blank Page...
Page 197: ...Synergy Series Soft Start User Manual MAN SGY 017 Version 01 27 06 2016 197 Blank Page...
Page 204: ...Synergy Series Soft Start User Manual MAN SGY 017 Version 01 27 06 2016 204 Blank Page...
Page 231: ...Synergy Series Soft Start User Manual MAN SGY 017 Version 01 27 06 2016 231 Notes...
Page 232: ...Synergy Series Soft Start User Manual MAN SGY 017 Version 01 27 06 2016 232 Notes...
Page 233: ...Synergy Series Soft Start User Manual MAN SGY 017 Version 01 27 06 2016 233...