Fairford SDF-02 Installation Instructions Manual Download Page 6

6

U

L1, L2, L3

S0, S1

U

T1, T2, T3

Flash
green

A1, A2

1 flash

ready

2 flash

starting

3 flash

run

4 flash

stopping

1 flash

ready

~½ second

with circuit breaker

with contactor

Flash Green

1

ready

2

starting

3

run

4

stopping

Flash Red (fault)

1

SCR / supply

2

thermal

3

Uc <24V

Settings - Einstellungen - Réglages - Regulazioni - 

Regulaciones

Start

Stop

Ie

70%

100%

12

0.5

12

0

Motor current:-

100% for standard rating
70% for smaller motors

Soft Stop time:-

0 = default
range 0 S to 12 S

Soft Start time:-

~5 = default
range 0.5 S to 12S

 

 

 

 

 

LED green - LED grün – DEL vert –

LED verde - LED verde

1

Ready for operation – Betriebsbereit –
Prêt à fonctionner –Pronto al funzionamento –
En condiciones para funcionamiento

2

Starting – in Rampe – en rampe – in rampa –
en rampa

3

Top of ramp – Rampenende erreicht –
Fin de rampe atteinte –Fine rampa – Fin de rampa

4

Soft-Stop – Soft stop – Arrêt progressif – Soft-Stop –
Paro suave

#

  

Fault LED red – Fehler LED rot – DEL erreur

rouge – LED errore rosso –LED error rojo

1

SCR or supply

2

Too hot

3

Control supply low volts

Summary of Contents for SDF-02

Page 1: ...ecchio adatto per uso in ambienti industriali EN 55011 22 Classe A El aparato es adecuado para uso en ambiente industrial EN 55011 22 clase A Electric shock risk Danger Only skilled or instructed pers...

Page 2: ...13 2 0 0 8 x 4 1L1 3L2 5L3 2T1 4T2 6T3 mm2 AWG mm Nm mm 35 1 17 3 0 1 2 x 6 5 Mountings suitable for M6 160mm x 125mm centres M6 8 Nm M6 8 Nm Dimensions Abmessungen Dimensioni Dimensiones Power cable...

Page 3: ...en Dimensioni Dimensiones A1 A2 S0 S1 13 14 23 24 mm AWG mm Nm mm 2 1 x 0 75 2 5 18 12 6 0 8 0 5 x 3 5 2 x 0 75 1 18 16 11 0 8 0 5 x 3 5 A1 A2 S0 S1 13 14 23 24 Control supply 24VDC Start stop 24VDC 1...

Page 4: ...level Bei Mehrleiteranschluss darf maximal ein DIN Normgr en Sprung zwischen den verwendeten Leitern liegen En cas de raccordement de plusieurs conducteurs il faut 1 cartement normalis max entre les...

Page 5: ...Semiconductor fuse for type 2 coordination in addition to Q1 Halbleitersicherung f r Zuordnungsart 2 zus tzlich zu Q1 Per avere la protezione del semiconduttore in coordinamento di tipo 2 necessario...

Page 6: ...70 for smaller motors Soft Stop time 0 default range 0 S to 12 S Soft Start time 5 default range 0 5 S to 12S LED green LED gr n DEL vert LED verde LED verde 1 Ready for operation Betriebsbereit Pr t...

Page 7: ...n the scope of the EU Directives the SDF soft starters and their accessories may be commissioned only provided it is established that the machine fulfils the protective requirements of Machine Directi...

Page 8: ...110kW 160A 90kW Operational Voltage Ue 230 460 VAC rms 3 Phase 15 10 Rated Frequency 50 60Hz 2Hz Form Designation Form 1 Index Rating Standard AC53a 3 5 99 10 Class 10A AC53a 3 12 99 10 Control Supply...