VISY-Output 8 

8-Channel relay output module 

 

 
 
 

Version:  

Edition: 

2016-09 

Art. no.:  

350072 

Summary of Contents for VISY-Output 8

Page 1: ...IR GmbH Schnackenburgallee 149 c 22525 Hamburg Germany Tel 49 40 39 82 07 0 Fax 49 40 390 63 39 Technical Documentation VISY Output 8 8 Channel relay output module Version 3 Edition 2016 09 Art no 350...

Page 2: ...le of contents Copyright Reproduction and translation is only permitted with the written consent of the FAFNIR GmbH The FAFNIR GmbH reserves the right to carry out product alterations without prior no...

Page 3: ...6 Connection of the relay contacts 4 2 7 Connection to VISY Command 4 3 Configuration 5 3 1 Hold time after communication loss 5 3 2 Output action after hold time 6 3 3 Relay mode 6 3 4 Relay delay 7...

Page 4: ...Output 8 is designed for operation within the VISY X system only Modifications to the VISY Output 8 are prohibited without the prior consent of the manufacturer All installation and maintenance work w...

Page 5: ...The following figure shows the position of the connectors LEDs and controls on the board of the VISY Output 8 Figure 1 VISY Output 8 Design 2 4 1 Device information 1 Label with the serial number whi...

Page 6: ...data rate is comparatively low 6 4 way DIL switch currently without function 2 4 4 LEDs 7 Transmit LED red 8 Receive LED red 9 Output LEDs red one per output 10 Status LED yellow 11 Relay LEDs red one...

Page 7: ...SY X tank gauging system For the connection of VISY Input 8 a communication adapter VISY ICI 485 is required which must be installed inside VISY Command The communication between VISY ICI 485 and VISY...

Page 8: ...the configuration means to adopt VISY Output 8 to the requirements of the special application The following settings are possible 1 Hold time after communication loss 2 Output action after hold time...

Page 9: ...ergized active when the corresponding output is activated Fail safe mode In the fail safe mode the relay is normally energized active and will be de energized passive when the corresponding output is...

Page 10: ...ts caused by incomplete configuration The maintenance mode is turned on or off using the VISY Setup configuration software as far this function is supported by the used version During the maintenance...

Page 11: ...tus LED indicates the state of the communication between the VI interface card in the VISY Command and the VISY Output 8 The following table lists the possible states of the status LED and explains th...

Page 12: ...state In the fail safe mode the output LEDs and the relay LEDs have the opposite state 4 5 Operating voltage LED 12 The green operating voltage LED indicates whether VISY Output 8 is supplied with vol...

Page 13: ...ND to connect to VISY ICI 485 Outputs Eight relays each with potential free changeover contact load rating of the contacts AC U 250 VAC I 3 A P 300 VA cos 0 7 DC U 24 VDC I 2 A P 50 VA Table 4 Technic...

Page 14: ......