VAPORIX Service Dongle and VAPORIX Diagnostics
Page 9/19
4.3
Testing the shutdown of the dispenser point
If you want to test the triggering of an alarm and the shutdown in normal
operation:
1. Turn coding switch to position "1" for dispenser side A or to "2" for dispenser
side B.
2. Press button.
The corresponding LED "A/B" on the VAPORIX-Control unit must now flash
orange instead of green. The alarm is triggered, and the 72-hour time limit
begins to run.
3. Press button again.
The LED on the VAPORIX-Control unit must now flash red instead of orange
and the fuel discharge of the dispenser concerned (side A or B) must be
blocked.
4. Turn coding switch to "5" for dispenser side A or to "6" for dispenser side B
in order to release the dispenser point.
5. To log out, turn coding switch to "9" and press button (yellow LED goes out).
If the test shutdown is not cancelled by the service personnel within
a period of 10 minutes, an automatic reset of the test shutdown is
performed by the VAPORIX-Control measurement analysis unit.
4.4
Releasing a dispenser point that is shut down, for testing
If a dispenser point has been automatically shut down due to a system error, it
can be temporarily released for service purposes (e.g. control measurements).
1. Turn coding switch to "3" for dispenser side A or to "4" for dispenser side B.
2. Press button.
The dispenser point is released until the dongle is logged out again.
3. To log out, turn coding switch to "9" and press button (yellow LED goes out)
or perform further service activities.
After 60 minutes, a release of the dispenser point for testing and
servicing purposes is reset by the VAPORIX-Control measurement
analysis unit, provided that a reset operation has not already been
performed by service personnel.