![fafnir SEPARIX-Control CT Technical Documentation Manual Download Page 9](http://html1.mh-extra.com/html/fafnir/separix-control-ct/separix-control-ct_technical-documentation-manual_3179401009.webp)
SEPARIX-C/-T and SEPARIX-Control CT
Page 6/37
In separators with an automatic closure device, the SEPARIX-C L Plus must
be installed at a height above the closure device appropriate to the dimen-
sions and operating conditions of the separator so that the system operator
still has enough time to take the necessary measures in the event of an
alarm.
The interface sensor is equipped with a non-detachable blue cable (7) (3 x 0.5 mm²)
(SEPARIX-C L Plus: 5 m long). This cable can be shortened or extended up to 250 m with the
use of a junction box (1) suitable for the environmental conditions concerned and an exten-
sion cable (2).
If used in a potentially explosive atmosphere, the extension cable must not
exceed the maximum permissible capacitance and inductance of the meas-
uring transducer (see section 4.5). To avoid disturbances or damage to the
sensor or measuring transducer, the selected junction box must offer suffi-
cient protection against the ingress of moisture or fluid in the environmental
and operating conditions in which it is used.
For connecting the sensor to the measuring transducer, please observe the
installation instructions for SEPARIX-Control CT in this or another user guide
for compatible FAFNIR measuring transducers.
The correct operation of the sensors is guaranteed only in conjunction
with a compatible and approved measuring transducer.
Figure 3: SEPARIX-C, installation
1 Junction box
2 Extension cable
3 Light liquid separator
4 Interface sensor
5 Switch point
6 Layer thickness
7 Sensor cable
Summary of Contents for SEPARIX-Control CT
Page 25: ......
Page 26: ......
Page 29: ......
Page 30: ......
Page 31: ......
Page 32: ......
Page 36: ......
Page 37: ......
Page 38: ......
Page 41: ...Blank Page...
Page 42: ...Blank Page...
Page 43: ...Blank Page...